Pilz PNOZ mmc11p User manual

PNOZ mmc11p
Operating Manual 1002697-EN-03
}Configurable compact control systems PNOZmulti Mini

Preface
This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for internal purposes. Suggestions and comments for improving this documentation will be
gratefully received.
Source code from third-party manufacturers or open source software has been used for
some components. The relevant licence information is available on the Internet on the Pilz
homepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual PNOZ mmc11p
1002697-EN-03 3
Section 1 Introduction 4
1.1 Validity of documentation 4
1.2 Using the documentation 4
1.3 Definition of symbols 4
Section 2 Overview 6
2.1 Scope of supply 6
2.2 Unit features 6
2.3 Front view 7
Section 3 Safety 8
3.1 Intended use 8
3.2 System requirements 8
3.3 Safety regulations 9
3.3.1 Use of qualified personnel 9
3.3.2 Warranty and liability 9
3.3.3 Disposal 9
3.3.4 For your safety 9
Section 4 Function description 10
4.1 Operation 10
4.2 Input and output data 10
4.3 Assigning the inputs/outputs in the PNOZmulti Configurator to the Ether-
CAT inputs/outputs
10
4.4 Block diagram 11
Section 5 Installation 12
5.1 General installation guidelines 12
5.2 Dimensions in mm 12
5.3 Connect the base unit and expansion modules 13
Section 6 Commissioning 14
6.1 General wiring guidelines 14
6.2 Connecting the supply voltage 14
6.3 Interface assignment 15
6.4 Download modified project to the PNOZmulti safety system 15
6.5 Preparing for operation 15
6.6 Connection example 16
Section 7 Operation 17
7.1 Messages 17
Section 8 Technical details 18
Section 9 Order reference 20
9.1 Product 20
9.2 Accessories 20

Introduction
Operating Manual PNOZ mmc11p
1002697-EN-03 4
1 Introduction
1.1 Validity of documentation
This documentation is valid for the product PNOZ mmc11p. It is valid until new documenta-
tion is published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
1.2 Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
1.3 Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

Introduction
Operating Manual PNOZ mmc11p
1002697-EN-03 5
INFORMATION
This gives advice on applications and provides information on special fea-
tures.

Overview
Operating Manual PNOZ mmc11p
1002697-EN-03 6
2 Overview
2.1 Scope of supply
}Expansion module PNOZ mmc11p
}Jumper
2.2 Unit features
Using the product PNOZ mmc11p:
Expansion module for connection to a base unit from the configurable control system
PNOZmulti Mini .
The product has the following features:
}Can be configured in the PNOZmulti Configurator
}Network protocols: EtherCAT
}Supports CANopen over EtherCAT (DS301 V4.02 compliant)
}Status indicators for communication with EtherCAT and for errors
}24 virtual inputs and outputs on the control system PNOZmulti can be defined in the
PNOZmulti Configurator for communication with the fieldbus EtherCAT . The number of
inputs and outputs can be extended to 128. Please note that when the extended inputs
and outputs 24 - 127 are used they have different properties (see document entitled
"Communication Interfaces").
}Max. 1 PNOZ mmc11p can be connected to the base unit
}Plug-in connection terminals:
either spring-loaded terminal or screw terminal available as an accessory (see order
reference)
}For details of the PNOZmulti Mini base units that can be connected, please refer to the
document "PNOZmulti System Expansion".

Overview
Operating Manual PNOZ mmc11p
1002697-EN-03 7
2.3 Front view
Legend:
}X1: EtherCAT IN
}X2: EtherCAT OUT
}X4: 0 V, 24 V:
Supply connections
}: Functional earth
}LEDs:
– Power
– Run
– Error
– L/A 1
– L/A 2
is registered trademark and patented technology, licensed by Beckhoff
Automation GmbH, Germany

Safety
Operating Manual PNOZ mmc11p
1002697-EN-03 8
3 Safety
3.1 Intended use
The expansion module PNOZ mmc11p is used for communication between the configur-
able control system PNOZmulti with EtherCAT.
EtherCAT is designed for fast data exchange at field level. The expansion module PNOZ
mmc11p is a passive EtherCAT subscriber (Slave). The basic communication functions
with EtherCAT conform to the system description published by the EtherCAT User Group.
The central controller (master) reads input information from the slaves and writes output in-
formation to the slaves as part of each cycle.
The expansion module may only be connected to a base unit from the configurable control
system PNOZmulti (please refer to the document "PNOZmulti System Expansion" for de-
tails of the base units that can be connected)
The configurable control system PNOZmulti is used for the safety-related interruption of
safety circuits and is designed for use in:
}E-STOP equipment
}Safety circuits in accordance with VDE0113 Part 1 and EN60204-1
The expansion module may not be used for safety-related functions.
Intended use includes making the electrical installation EMC-compliant. The product is de-
signed for use in an industrial environment. It is not suitable for use in a domestic environ-
ment, as this can lead to interference.
The following is deemed improper use in particular:
}Any component, technical or electrical modification to the product
}Use of the product outside the areas described in this manual
}Use of the product outside the technical details (see chapter entitled “Technical De-
tails”)
3.2 System requirements
Please refer to the "Product Modifications PNOZmulti" document in the "Version overview"
section for details of which versions of the base unit and PNOZmulti Configurator can be
used for this product.

Safety
Operating Manual PNOZ mmc11p
1002697-EN-03 9
3.3 Safety regulations
3.3.1 Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current pro-
fessional activity, has the specialist knowledge required to test, assess and operate the
work equipment, devices, systems, plant and machinery in accordance with the general
standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who:
}Are familiar with the basic regulations concerning health and safety / accident preven-
tion
}Have read and understood the information provided in this description under "Safety"
}And have a good knowledge of the generic and specialist standards applicable to the
specific application.
3.3.2 Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended
}Damage can be attributed to not having followed the guidelines in the manual
}Operating personnel are not suitably qualified
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
3.3.3 Disposal
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
3.3.4 For your safety
The unit meets all the necessary conditions for safe operation. However, you should always
ensure that the following safety requirements are met:
}This operating manual only describes the basic functions of the unit. The expanded
functions are described in the PNOZmulti Configurator's online help. Only use these
functions once you have read and understood the documentations.
}Do not open the housing or make any unauthorised modifications.
}Please make sure you shut down the supply voltage when performing maintenance
work (e.g. exchanging contactors).

Function description
Operating Manual PNOZ mmc11p
1002697-EN-03 10
4 Function description
4.1 Operation
The virtual inputs and outputs that are to be transferred via EtherCAT are selected and con-
figured in the PNOZmulti Configurator. The base unit and the expansion module PNOZ
mmc11p are connected via a jumper. After the supply voltage is switched on or the
PNOZmulti control system is reset, the expansion module PNOZ mmc11p is configured and
started automatically.
The connection to EtherCAT is made via the two RJ45 sockets.
LEDs indicate the status of the expansion module on EtherCAT.
The configuration is described in detail in the PNOZmulti Configurator's online help.
4.2 Input and output data
The data is structured as follows:
}Input area
The inputs are defined in the master and transferred to the PNOZmulti. Each input has
a number, e.g. input bit 4 of byte 1 has the number i12.
}Output range
The outputs are defined in the PNOZmulti Configurator. Each output that is used is
given a number there, e.g. o0, o5... The status of output o0 is stored in bit 0 of byte 0;
the status of output o5 is stored in bit 5 of byte 0 etc.
}Output range only: Byte 3
Bits 0 … 4: Status of LEDs on the PNOZmulti
– Bit 0: OFAULT
– Bit 1: IFAULT
– Bit 2: FAULT
– Bit 3: DIAG
– Bit 4: RUN
Bit 5: Data is being exchanged.
Detailed information on data exchange (tables, segments) is available in the document
"Communication Interfaces" in the section entitled "Fieldbus modules".
4.3 Assigning the inputs/outputs in the PNOZmulti Configurator
to the EtherCAT inputs/outputs
Virtual inputs on PNOZmulti Configurator i0 ... I7 i8 ... i15 i16 ... i23
Input data EtherCAT Byte 0: Bits 0 … 7 Byte 1: Bits 0 … 7 Byte 2: Bits 0 … 7
Virtual outputs on PNOZmulti Configurator o0 ... o7 o8 ... o15 o16 ... o23
Output data EtherCAT Byte 0: Bits 0 … 7 Byte 1: Bits 0 … 7 Byte 2: Bits 0 … 7
The number of virtual inputs and outputs can be extended to 128 (see document "Commu-
nication Interfaces" in the section entitled "Fieldbus modules")
Table of contents
Other Pilz Control System manuals

Pilz
Pilz PSS u2 ES 16DI User manual

Pilz
Pilz PNOZmulti Mini User manual

Pilz
Pilz PMCprimo C2 User manual

Pilz
Pilz PSS67 PLC1 16FDI User manual

Pilz
Pilz PNOZ m ES EtherCAT User manual

Pilz
Pilz PSSuniversal User manual

Pilz
Pilz PSS u2 ES 16DOD 0.5A User manual

Pilz
Pilz PSS u2 EF 8DI User manual

Pilz
Pilz PNOZ m ES CC-Link User manual

Pilz
Pilz PNOZ m ES 14DO User manual

Pilz
Pilz PSSu E F PS1 User manual

Pilz
Pilz PNOZ m B0 Instruction Manual

Pilz
Pilz PSS u2 ES 4IOL User manual

Pilz
Pilz PNOZ ms1p User manual

Pilz
Pilz PNOZ mmc6p User manual

Pilz
Pilz PNOZ mmc2p User manual

Pilz
Pilz PMCprimo C User manual

Pilz
Pilz PNOZ m ES Profinet User manual

Pilz
Pilz PNOZmulti User manual

Pilz
Pilz PSS u2 ES 4DO SR 0.5A User manual