Jung 10911ST Series User manual

KNX push-button universal / KNX push-button standard / KNX push-button
extension
KNX push-button universal 1-gang
Art. no.: ..10911ST
KNX push-button universal 2-gang
Art. no.: ..10921ST
KNX push-button standard 1-gang
Art. no.: ..10711ST
KNX push-button standard 2-gang
Art. no.: ..10721ST
KNX push-button extension 1-gang
Art. no.: ..10911TE
KNX push-button extension 2-gang
Art. no.: ..10921TE
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
These instructions are an integral part of the product, and must remain with the end customer.
1 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
2 Device components
Figure1: Device components 1-channel
Figure2: Device components 2-channel
(1) Design frame (accessories)
(2) Status LED
(3) Operating rockers (accessory)
2 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on loadable soft-
ware and attainable functionality as well as the software itself can be obtained from the manu-
facturer´s product database.
The device can be updated. Firmware can be easily updated with the Jung ETS Service App
(additional software).
The device is KNX Data Secure capable. KNX Data Secure offers protection against manipula-
tion in building automation and can be configured in the ETS project. Detailed specialist know-
ledge is required. A device certificate, which is attached to the device, is required for safe com-
missioning. During mounting, the certificate must be removed from the device and stored se-
curely.
Planning, installation and commissioning of the device are carried out with the aid of the ETS,
version 5.7.3 and above.
Intended use
– Operation of loads, e.g. light on/off, dimming, Venetian blinds up/down, brightness values,
temperatures, colour values, calling up and saving scenes, etc.
– Mounting in appliance box according to DIN 49073
Product characteristics
– Operating concept (rocker or button) adjustable for every operating area
– Button assessment (single-area operation or dual-area operation) adjustable
– One or two functions per operating area
– Integrated bus coupling unit
Depending on the version:
– Completion with 1-gang or 2-gang rocker
Universal:
– Alarm message, optionally with confirmation by pressing any button
– Disable or function switch-over of all or of individual button functions possible
– Brightness of Status LEDs adjustable
– Measurement of the room temperature
– One status LED per operating area – red, green or blue adjustable
– Connection of possible
– Connection of external switching contacts possible
Standard:
– One status LED for each operating area - red
Extension:
– Connection to Push-button universal possible
– Version with single and dual rocker without status LED
3 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
4 Energy saving mode
The device optionally switches to the energy saving mode after a preset time or by an external
telegram. In energy saving mode all LED functions are switched off.
The device leaves the energy saving mode – depending on programming – on operation or by
an external telegram.
Button or rocker operations with activated energy saving mode are executed immediately.
5 Operation
The operation of functions or electrical consumers can be set individual for each device:
Operation concept single-area operation dual-area operation
Rocker function - Each rocker can perform an indi-
vidual function.
Button function Two buttons above one another per-
form the same function.
Each button can perform an indi-
vidual function.
Universal: For the rocker functions Dimming, Venetian blind and 2-channel operation, full-
surface operation can be programmed, which can trigger another function.
Operating a function or load
– Switching: Short press on button / rocker.
– Dimming: Long press on the button / rocker.
– Moving Venetian blind: Long press on button / rocker.
– Stopping or adjusting Venetian blind: Short press on button / rocker.
– Setting value: Short press on button / rocker.
– Adjusting value: Long press on button / rocker
– Opening scene: Short press on button / rocker
– Saving scene: Long press on button / rocker
– Operating channel 1: Short press on button / rocker
– Operating channel 2: Long press on button / rocker
– Operating controller extension: Short press on button / rocker
4 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
6 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Cover up live parts in the installation environment.
6.1 Fitting and electrical connection
Mounting and connecting the device (Figure 3)
Figure3: Fitting the device
(1) Design frame
(3) Operating rocker (top = narrow side)
(4) Retaining spring
(5) Screw
(6) Retaining clamp
(7) Supporting frame
(8) Device module
DANGER!
Danger of electric shock
When mounting with 230 V socket outlets under a common cover, there is a danger
of electrical shocks in the event of a fault.
Use only the enclosed plastic screws for fastening to the supporting frame!
■ Mount supporting frame in the right orientation on an appliance box.
Note marking TOP and marking A (= in front).
Use the supplied box screws.
■ Connect device to the KNX using KNX connecting terminal (red= +, black = -).
■ Optional: Connect (see accessories) to connection terminal (Figure 4).
■ Optional: Connect external switching contacts (e.g. push-button or reed contacts) to the
connection terminal (Figure 5).
■ In secure operation: It is advisable to remove the secure certificate from the device.
5 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
■ Attach device onto the supporting frame.
■ Optional: Screw the device to the supporting frame. Tighten the plastic screws only lightly.
■ Snap on rockers.
The rockers suitable for the device must be ordered separately (see accessories).
The device should be used in an air-tight appliance box. Drafts cause incorrect temperat-
ure values to be measured.
connecting (Figure 4)
Only possible with Push-button universal.
■ Connect to Push-button universal with a separate line (e.g. J-Y(St)Y 2×2×0.8). Note col-
our coding: black = SW, red = RT, white = WS, yellow = GE
The connection terminal blocks are included with the .
Do not exceed the cable length (max. 30 m).
One Push-button universal can be connected per .
Do not connect any external voltage.
Figure4: Connecting push-button extension
Connecting external switching contacts (Figure 5)
Only possible with Push-button universal.
■ Connect external switching contacts (e.g. push-button or reed contacts) with a separate
line (e.g. J-Y(St)Y 2×2×0.8) to Push-button universal (connection terminal K / WS GE).
A suitable device connection terminal is available as an accessory (2050GEWS).
Do not exceed the cable length (max. 30 m).
A maximum of 20 external switching contacts can be connected in parallel or in series.
6 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
Do not connect any external voltage.
Figure5: Connecting installation push-button
7 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
6.2 Commissioning
Preconditions in secure operation
– A dedicated application program is required.
– Secure commissioning is activated in the ETS.
– Device certificate entered/scanned or added to the ETS project. A high resolution camera
should be used to scan the QR code.
– Document all passwords and keep them safe.
Programming the physical address and application program
Project design and commissioning with ETS from version5.7.3and above.
Figure6: Buttons for activating Programming mode
Activation of the programming mode without attached rockers.
Precondition: The device is connected and ready for operation.
■ Activate programming mode: Press and hold push-button at the upper left (9). Then press
push-button at the lower right (10) (Figure 6).
The status LEDs flash rapidly (approx. 8 Hz). Programming mode is activated.
■ Load the physical address into the device.
The status LEDs return to their previous state – off, on, or flashing. Physical address is
programmed.
■ Write the physical address on the device label.
■ Load the application program into the device.
The status LEDs flash slowly while the application program is programmed (approx. 0.75
Hz). As soon as the programming is successfully completed, the status LEDs carry out
their parameterised function.
If the device contains no – or an incorrect – application program, both status LEDs flash
slowly (approx. 0.75 Hz).
Safe-state mode
The safe state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis functions and pro-
gramming of the device are possible.
Activating the safe-state mode
■ Switch off the bus voltage.
■ Press and hold down the top left button and bottom right button (Figure 6).
■ Switch on the bus voltage.
The safe-state mode is activated. The status LEDs flash slowly (approx. 1 Hz).
Only release the the top left and bottom right buttons when the LEDs flash.
8 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
Deactivating safe-state mode
■ Switch off bus voltage or carry out ETS programming.
Master reset
The master reset restores the basic device setting (physical address 15.15.255, firmware re-
mains in place). The device must then be recommissioned with the ETS.
During secure operation: A master reset deactivates device security. The device can then be re-
commissioned with the device certificate.
Performing a master reset
Precondition: The safe-state mode is activated.
■ Press the top left button and bottom right button (Figure 6) and ho,d for more than 5
seconds.
The device performs a master reset. The status LEDs flash rapidly (approx. 4 Hz).
The device restarts. The status LEDs flash slowly (approx. 0.75 Hz).
Only release the the top left and bottom right buttons when the LEDs flash.
Restoring the device to factory settings
Devices can be reset to factory settings with the ETS Service App. This function uses the firm-
ware contained in the device that was active at the time of delivery (delivery state). Restoring
the factory settings causes the devices to lose their physical address and configuration.
Flashing sequence of the status LEDs
Status LED status Flash frequency
Application discharged / stopped approx. 0.75 Hz
Safe-state mode approx. 1 Hz
Status display flashes approx. 2 Hz
Alarm signal approx. 2 Hz
Master reset approx. 4 Hz
Programming mode approx. 8 Hz
Full-surface operation approx. 8 Hz
9 / 12
82402103 19.02.2020
J0082402103

KNX push-button universal / KNX push-button standard / KNX push-button
extension
6.3 Dismantling
Dismantling the operating rockers (Figure 7)
The operating rockers can be dismantled using a dismantling wedge or a screwdriver (Figure 8).
The recesses are intended for a blade width of up to 4 mm.
Figure7: Dismantling rocker from the side
Figure8: Dismantling rocker from above
10 / 12
82402103 19.02.2020
J0082402103
This manual suits for next models
5
Table of contents
Other Jung Switch manuals

Jung
Jung 1701 SE User manual

Jung
Jung FA10EB User manual

Jung
Jung FAS180 Series User manual

Jung
Jung FMAS816REG User manual

Jung
Jung 1704ESE User manual

Jung
Jung 3281-1 Series User manual

Jung
Jung 3181-1 Series User manual

Jung
Jung FMAS10ZS User manual

Jung
Jung KNX 4071.0 LED Series Operator's manual

Jung
Jung 567 S Series User manual

Jung
Jung 1704ESE User manual

Jung
Jung 52921 ST User manual

Jung
Jung 1701PSE User manual

Jung
Jung Home User manual

Jung
Jung AS 1280-1 Series User manual

Jung
Jung 1180 Series User manual

Jung
Jung A3181-1-01 User manual

Jung
Jung 1202 URE User manual

Jung
Jung 10911STRF Series User manual

Jung
Jung 1701SE User manual