Code +050004036 Rel. 1.0 – 11/03/2008 10
d: Defrost parameters
Display Parameter and description Measurement
unit Min Max Bn
1 Bn
2 Bn
3 Bn
4 Bn
5 Bn
6
d0
Type of defrost
0=defrost with elec. element ends with
temperature or time
1=defrost with hot gas ends with temperature or
time
2=defrost with elec. element ends with time
3=defrost with hot gas ends with time
4= defrost with elec. element ends with time or
temperature (if defrost ends with time ED1 and ED2
are not displayed)
Select 0 4 2 0 0 2 0 0
dI Interval between 2 defrosts Time 0 250 8 8 6 12 8 6
dt1 Temperature at end of evaporator defrost °C/°F -50 200 4 4 4 4 4 4
dt2 Temperature at end of aux. evaporator defrost °C/°F -50 200 4 4 4 4 4 4
dP1 Maximum evaporator defrost duration Min 1 250 45 45 30 45 45 30
dP2 Maximum aux. evaporator defrost duration Min 1 250 45 45 30 45 45 30
d3 Delayed defrost activation Min 0 250 0 0 0 0 0 0
d4 Defrost when the controller is switched on
0=no
1=yes
Select 0 1 0 0 0 0 0 0
d5 Delay defrost when the controller is switched on Min 0 250 120 240 240 120 240 240
d6 Block display during defrost
0=alternating display of temperature and DEF
1=display temperature present before defrost
2=always display DEF
- 0 2 2 2 2 2 2 2
dd Dripping duration after defrost Min 0 15 0 4 4 0 4 4
d8 High-temperature alarm (AH) exclusion duration
after defrost and/or door open Time 0 15 1 1 1 1 1 1
d8d Alarm timer after door opening (alarm “dor”) Min 0 250 2 2 2 2 2 2
d9 Priority defrost for delayed compressor
start/stop
0=respected
1=not respected (priority defrost)
Select 0 1 0 0 0 0 0 0
d/1 Read defrost probe 1 °C/°F - - - - - - - -
d/2 Read defrost probe 2 °C/°F - - - - - - - -
dC Defrost duration time base
0=hours/minutes
1=Minutes/seconds Select 0 1 0 0 0 0 0 0
d10
Smart defrost: Compressor running time with an
evaporator temperature below D11 to start
defrost
0=function disabled
>0 =running time
dC 0 250 0 0 0 0 0 0
d11 Temperature threshold for smart defrost °C/°F -20 20 1 1 1 1 1 1
d12
Auto-adaptive advanced defrost
0=skip defrost disconnected, automatic variation
disconnected
1=skip defrost disconnected, automatic variation
connected
2= skip defrost connected, automatic variation
disconnected
3= skip defrost connected, automatic variation
connected
- 0 3 0 0 0 0 0 0
dn Average defrost duration in percentage in
relation to dt1 or dt2 - 1 100 65 65 65 65 65 65
dH Proportional variation factor of dI - 0 100 50 50 50 50 50 50