Daikin BRC1H71W User manual

Wired Remote
Controller
Installation Manual
MODEL BRC1H71W
English
+
-
• Be sure to read before conducting the installation of this product, and conduct
installation according to this manual.
• Refer to this manual together with the installation manual of the indoor unit.
It is possible to perform settings of some functions from
a smart phone app.
01_EN_EM19A026_IM.indd 1 2020/09/08 14:20:58

01_EN_EM19A026_IM.indd 2 2020/09/08 14:20:58

English 1
Contents
Safety Considerations ........................................................ 2
Accessories ........................................................................ 3
Remote controller installation procedure............................ 4
Button Locations and Descriptions................................... 11
Overview of screens......................................................... 12
Setting screen list ............................................................. 13
Names and Functions ...................................................... 15
Starting up the system...................................................... 16
Switching the Changeover Master.................................... 19
Installer Menu................................................................... 23
Field Setting ..................................................................... 24
R/C Setting ....................................................................... 28
Installer Password Setting ................................................ 32
Other Service Settings ..................................................... 33
Certication ...................................................................... 34
License ............................................................................. 35
01_EN_EM19A026_IM.indd 1 2020/09/08 14:20:58

2 English
Safety Considerations
The original instructions are written in English. All other languages are translations of the original
instructions.
All phases of the eld-installation, including, but not limited to, electrical, piping, safety, etc. must be in
accordance with manufacturer’s instructions and must comply with national, state, provincial and local
codes.
Read these SAFETY CONSIDERATIONS carefully before installing the remote controller.
After completing the installation, ensure that the remote controller operates properly during startup
operation.
Train the customer to operate and maintain the remote controller. Inform customers that they should
store this Installation Manual with the Operation Manual for future reference.
Always use a licensed installer or contractor to install this product. Improper installation can result in
electrical shock, re, or explosion.
Meanings of WARNING, CAUTION, and NOTE Symbols.
WARNING Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
It may also be used to alert against unsafe practices.
NOTE Indicates situations that may result in equipment or property-damage
accidents only.
WARNING
Only qualied personnel must carry out the installation work.
Consult your Daikin dealer regarding relocation and reinstallation of the remote controller.
Improper installation work may result in electric shocks or re.
Electrical work must be performed in accordance with relevant local and national regulations and
with instructions in this installation manual.
Improper installation may cause electrical shocks or re.
Use only specied accessories and parts for installation work.
Failure to use specied parts may result in electric shocks, re, or the unit falling.
Do not disassemble, reconstruct, or repair.
Electric shock or re may occur.
Make sure that all wiring is secured, that specied wires are used, and that no external forces act on
the terminal connections or wires.
Improper connections or installation may result in re.
Before touching electrical parts, conrm the power is off to the unit.
CAUTION
Keep water out of the remote controller.
To avoid electric shock due to entry of water or insects, ll the wiring through-hole with putty.
Do not wash the remote controller with water as it may result in electrical shocks or re.
Do not touch the remote controller buttons with wet ngers.
Touching the buttons with wet ngers can cause an electric shock.
01_EN_EM19A026_IM.indd 2 2020/09/08 14:20:58

English 3
CAUTION
Do not install the remote controller in the following locations:
(a) Where a mineral oil mist or oil spray or vapor is produced, for example, in a kitchen.
Plastic parts may deteriorate.
(b) Where corrosive gas, such as sulfurous acid gas, is produced.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the control system and cause the unit to malfunction.
(d) Where ammable gas may leak, where there is carbon ber or ignitable dust suspension in the
air, or where volatile ammables such as thinner or gasoline are handled.
Operating the unit in such conditions can cause a re.
(e) High temperature areas or areas with direct ames.
Overheating and/or re can occur.
(f) Moist areas where there is exposure to water. If water enters the inside of the remote controller,
it may cause electric shock and electrical components may fail.
NOTE
Install the control wires for the indoor unit and the remote controller at least 3.5 feet (1 meter) away
from televisions or radios to prevent image interference or noise. Depending on the radio waves, a
distance of 3.5 feet (1 meter) may not be sufcient to eliminate the noise.
When the remote controller’s temperature sensor is used, select the installation location as per the following:
• A place where average temperature in the room can be detected.
• A place where it is not exposed to direct sunlight.
• A place where it is far away from any heat source.
• A place where it is not affected directly by outside air.
Accessories
The following accessories are included.
Drywall screw Drywall anchor Operation Handbook Installation Handbook
(3 pcs.) (3 pcs.) (3 pcs.) (1 pc.)
Mounting plate
(Metal)
Mounting plate
(Plastic)
Screw for mounting plate
(M3.5×10)
Screw for mounting plate
(M4×40)
(1 pc.) (1 pc.) (3 pcs.) (2 pcs.)
01_EN_EM19A026_IM.indd 3 2020/09/08 14:20:59

4 English
Remote controller installation
procedure
Deciding where to install the remote controller
Select the installation location based on “Safety Considerations” (see page 2) and obtain
consent of the customer.
Creating a wiring through-hole in the wall (when opening a
hole in the wall and installing)
If the hole size is too large or not in the
proper location, it may be seen after the
remote controller is installed.
NOTE
3-11/64 (80.5)
13/64
(5)
33/64 (13)
1-47/64 (44)
9/32 (7)
R3/32(2.5)
R3/32(2.5)
13/64
(5)
41/64
(16.25)
1-47/64 (44)
35/64
(13.75)
3-11/64 (80.5) Back plate
Through-hole
Align the center of the wall
hole with the center of the
access hole on the controller
back plate when planning the
installation.
Access hole
[Unit : inch (mm)]
Back plate
Through-hole
Access
hole
CAUTION
• Note that if the wiring through-hole is large or deviates from the specied position, the hole may be
exposed.
01_EN_EM19A026_IM.indd 4 2020/09/08 14:20:59

English 5
Determining the wire routing direction for the back plate
Before mounting the controller, determine the wiring direction and remove a piece of the
controller’s back plate accordingly (i.e.: a, b, c). The wiring can be routed from the top, the
left, or the bottom of the back cover. Remove a piece of the back plate according to the
following gure.
After removing a thin piece with a tool such as clippers, remove burrs using a le, etc.
a Wiring from top
b Wiring from left
c Wiring from bottom
a
b
c
CAUTION
In case you are routing the wiring from the rear, you don’t have to remove anything.
When routing the wiring from the top, rear, left, bottom, or when installing on a mounting plate etc., be
sure to route the wiring to the upper casing before securing the back plate.
01_EN_EM19A026_IM.indd 5 2020/09/08 14:20:59

6 English
Securing the back plate
Wall installation
1 : Take the drywall screws and drywall anchors out of the accessory bag.
2 : Mount the back plate to a at surface.
Drywall screws
Drywall anchors
In case of installing in the electrical component box
1 : Take the screws for the mounting plate (M3.5×10 and M4×40), and the mounting
plates (metal and plastic) out of the accessory bag.
2 : Attach the mounting plate (metal) to the electrical component box with the screws for
the mounting plate (M4×40).
3 : Attach the back plate and mounting plate (plastic) with the screws for mounting plate
(M3.5×10).
CAUTION
• For the installation surface, select as at a location as possible.
•
Choose a place where there is no gap between the wall and the screw xing part of the back plate.
• If there is an empty space between the back plate and the screw xing part (nut part) due to the
structure of the wall, install with a torque of 20 N · cm or less.
• If the upper casing comes o easily, loosen the drywall screws to lessen the deformation.
• If tightened too much, the back plate will be deformed and the upper casing will come o easily.
If the upper casing comes o easily, loosen the screws and correct the deformation.
01_EN_EM19A026_IM.indd 6 2020/09/08 14:21:00

English 7
Connecting the electrical wiring
All wiring must comply with the following requirements:
Wire specification Value
Wiring type Non-shielded, 2-conductor, Stranded copper wire
Wiring size AWG-18
Wiring length Maximum 1640 feet (500 m)
Prepare the wiring for connection to the remote controller following these instructions:
Approx. 3/8 inch (10 mm)
Remove the wire jacket
and insulation
To simplify the wiring, maintain
a 3/8 inch (10 mm) dierence
between the length of the two
conductors.
Cutting guideline
L
Wiring outlet L
Top ±5.5 inch (140 mm)
Left ±4.3 inch (110 mm)
Bottom ±3.5 inch (90 mm)
Rear No requirements
Connect the terminals (P1, P2) of the remote controller to the terminals (P1, P2) of the
indoor unit. (P1 and P2 are not polarity sensitive.)
CAUTION
• Before working, shut o all power supplies.
• Do not touch the remote controller circuit board directly with your hands.
01_EN_EM19A026_IM.indd 7 2020/09/08 14:21:00

8 English
Top outlet
P1P2
P1P2 terminal
Rear outlet
P1P2
Left outlet
P1P2
01_EN_EM19A026_IM.indd 8 2020/09/08 14:21:00
Other manuals for BRC1H71W
3
Table of contents
Other Daikin Remote Control manuals

Daikin
Daikin BRC1D527 User manual

Daikin
Daikin BRC1E73 User manual

Daikin
Daikin BRC7E530W User manual

Daikin
Daikin BRC7C51W User manual

Daikin
Daikin G17 User manual

Daikin
Daikin GS02 User manual

Daikin
Daikin BRC1H81K User manual

Daikin
Daikin BRC1E63 User manual

Daikin
Daikin Madoka Simplified User manual

Daikin
Daikin BRC1H519W User manual

Daikin
Daikin BRC1E62 User manual

Daikin
Daikin DCS303A51 User manual

Daikin
Daikin BRC7E830 User manual

Daikin
Daikin BRC7M634F User manual

Daikin
Daikin BRC1E61 User manual

Daikin
Daikin BRC7M675 User manual

Daikin
Daikin OM-GS02-02110 User manual

Daikin
Daikin ARC433A Series User manual

Daikin
Daikin SRC-COA User manual

Daikin
Daikin BRC7CB58 User manual