CDVI TERENA User manual

Range: Integrated Access Control / Gamme : Contrôle d’Accès intégré
Group products
MANUEL D’INSTALLATION
INSTALLATION MANUAL
FR
EN
FRANCAIS
ENGLISH
TERENA
TERENA16

INSTALLATION
- Make the necessary wire connections for the central unit.
- Connect the cross-over network cable between the central control unit and the PC.
- Ensure that the SD card is properly inserted into the correct slot.
- Check the 4 DIP switch positions: Switches 1 and 4 should be in the ON position
and switches 2 and 3 in the OFF position.
- Connect the battery.
- Connect the central unit and switch it on (with the fuse holder inserted).
- Remove the lithium battery protection (CR2032) and install the battery.
- Wait a few moments and then check that the green light (PWR) comes on next
to the USB socket.
CONFIGURING YOUR PC
Assign a static IP address (IPv4) to the PC network card, for example: address
192.168.0.101, netmask 255.255.255.0 and leave the other elds empty.
CONFIGURING THE CENTRAL CONTROL UNIT
- Open the internet browser on your PC (minimum requirements: IE 8, FireFox 3.6,
Chrome 5, Safari 4 or Opera 10.5), Preferably, we recommend the use of Firefox.
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
2cdvi.com
cdvigroup.com
EN

- In the address bar in your browser, enter the following address:
http://192.168.0.100:8087/admin and then conrm.
- Enter the login (admin) and the password (terena) and click OK.
- Select the appropriate language.
- Click on Initialize data, then at the end of the operation, click OK.
- Enter your network settings as well as the date and time in the elds on the right.
- Click on Apply the settings, then at the end of the operation, click OK.
- Click on the Restart icon and click OK. Conrm the operation by clicking OK.
Wait a few moments for the message “Please wait… Rebooting the system” and click OK.
The green light (PWR) goes off.
- Close your internet browser.
- Wait for the green light (PWR) to come on next to the USB socket on the TERENA unit
and for the ashing light (LOW BATT) to come on.
HOW TO USE THE CONTROL UNIT
- Open the internet browser on your PC (minimum requirements: IE 8, FireFox 3.6,
Chrome 5, Safari 4 or Opera 10.5).
- In the address bar in your browser, enter http://192.168.0.100:8087/ and then conrm.
- Enter the login (superviseur) and the password (12345), then click OK.
- The central control unit is now ready to use.
RECOMMENDATIONS
- Do not store the central control unit without protecting the CR2032 lithium battery.
- After an update, you should clear the cache in your browser. To do so,
press CTRL+SHIFT+DEL in FireFox or IE.
- If you lose sensitive data such as the login, passwords and IP settings, connection
to the TERENA unit will be impossible.
SECURE SHUTDOWN
To ensure that the central unit shuts down safely, the DIP switch 2 on the 4-position
DIP switch terminal should be in the ON position. The LOW BAT LED ashes, indicating
that a secure shutdown procedure is in progress. Wait until the RX, TX, AL and SCR LEDs
go off before disconnecting the TERENA and the battery. After a shutdown to reboot,
do not forget to set the DIP switch 2 back to the OFF position (for normal functioning).
Reconnect the battery rst before connecting the mains cable (the battery alone cannot
power up the TERENA).
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
3
cdvi.com
cdvigroup.com
EN

1] PRESENTATION OF THE PRODUCT .........................................................P. 3
2] REMINDERS AND RECOMMENDATIONS ..................................................P. 3
3] CHOICE OF SETUP ..............................................................................P. 4
4] ASSEMBLY KIT ....................................................................................P. 5
5] ELECTRONIC BOARD ...........................................................................P. 5
6] THE DOOR CONTROLLER (INTBUSW) AND READERS ...............................P. 8
7] SUPPLEMENTARY MODULES ..................................................................P. 8
8] WIRING DIAGRAM ..............................................................................P. 11
9] ASSEMBLY ..........................................................................................P. 12
10] CONFIGURATION OF THE TERENA .......................................................P. 12
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
4cdvi.com
cdvigroup.com
EN

1] PRESENTATION OF THE PRODUCT
2] REMINDERS AND RECOMMENDATIONS
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
5
cdvi.com
cdvigroup.com
- TERENA = 128 Doors,
- TERENA16 = 16 Doors.
IP20
-20°C to +50°C
CE Certication
WEEE
285,40
295,40
8
81,40
295,40
89,40
291,40
285,40
8
81,40
89,40
280
Wiring
- An INTBUSW door controller is required for each
reader connected on the RS485 BUS.
- The distance between the central control unit
and the last door controller (INTBUSW)
or supplementary module (C14D/A, C14A/E,
C14A/S or C1410S) may not exceed 1000m.
- Pay extreme care not to install wires close to high
power cabling (for example : 230 V AC).
- Recommended wires > 1 twisted pair, SYT1 8/10ths
shielded wire (EIA-485 standard), refer to the
article below : “An EIA-485 line may interconnect
several devices in parallel, with each one featuring
an emitter and a receiver. Maximum distances
of up to a kilometre are possible, depending on
the congured transfer rates. However, practical
experience has shown that if the transmission
line exceeds about ten metres then the reference
potentials (0V) of each device need to be networked
(in reality in this case the RS485 link requires
three wires – two plus the shielding) to ensure
that the voltages between equipment grounds,
as well as those between equipment grounds
and earth grounds, cause no damage”.
Environment
The central control unit must be installed in a closed
environment, protected from external climatic
conditions.
Installation Recommendations
- To secure the installation, do not forget to insert
a 120 ohm resistor between A and B, on the last
door controller or supplementary module
(C14D/A, C14A/E, C14A/S or C1410S)
of the RS485 BUS.
- It is strongly recommended that you equip
the TERENA with a back-up battery (Optional,
Ref : B7AH).
To secure the system, the following points
must be checked :
A. The central unit must be connected
to the mains using a cable with a ground lead
which is in compliance with safety standards.
Management of 56 elevator oors.
Management of 112 alarm points :
56 inputs and 56 outputs (BMS-CTM).
Administrator management.
Multi-language : A choice of interface languages
available on the SD card.
3-wire RS485 Bus.
Possibility of linking up to a DGM1D system,
via an interface for access to the user events log.
Integrated transformer : 16/40 VA class 2.
Input voltage : 230 V AC ± 10% ; 50/60 Hz.
Power consumption: 60 mA.
EN

B. The ground lead must be connected to the terminal
block on the cabinet as shown in the wiring diagram
on Page 9. This guarantees that the installation
has a fully protective ground connection.
C. La connection between the cabinet door
and the ground protection is ensured using
a conductor tted with a lug (see the wiring
diagram on page 9 and the xation point
for the ground protection lug marked on the cabinet).
Connection between the cabinet structure and the
ground is ensured directly via the terminal block.
D. The system must be installed within an electrical
installation which is in accordance with legally
required security standards. It must be tted
with a circuit breaker to ensure security in the
event of a fault.
E. Before operating for the rst time, ensure correct
grounding of all parts of the cabinet (structure
and door).
F. The mains wire must be connected securely
but without tightening too heavily.
Others aspects to be respected :
A. Within the framework of normal use of the Terena
system, the cabinet must remain closed and locked
using the supplied key to avoid unnecessary
contact with any live components.
B. For any cleaning or maintenance operations,
the system must be disconnected before opening
the cabinet door.
C. Any contact with the area connected
to the mains
supply is FORBIDDEN.
This danger area is indicated
by the attached sticker.
D. In the event of a battery installation, please
respect the recommended specications : 12 V / 7AH.
E. When connecting the battery, pay special care
to respect wire polarities.
Certication:
This product is certied conform to European standards:
- 2004/108/CE relative to electromagnetic compatibility.
- 2006/95/CE relative to low voltage security.
On condition that the constructor’s installation
recommendations and warnings are respected.
If the installation is not carried out exactly
according to the constructor’s recommendations,
this may result in serious damage with regard
to functioning and security.
3] CHOICE OF SETUP
MODE : DIRECT ACCESS
MODE : ETHERNET
MODE : INTERNET
Hub or Switch
Router (Wi) Internet
DCHP or DNS Ethernet server (issues
TCP/IP addresses)
RJ45 crossover cable
(supplied)
DCHP or DNS Ethernet server
(issues TCP/IP addresses)
Terena
Terena
Terena
OR
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
6cdvi.com
cdvigroup.com
EN

Tamper
switch for
box
Tamper
switch for
Wall
Cabinet
lock 120 Ohm
resistor Battery
wires
RJ45
crossover
cable
125V
7A
Fuse
250V
315mA
Fuse
Ty-rap
strap
TERENA
TERENA16
11111 Red
1 Black 1111
4] ASSEMBLY KIT
5] ELECTRONIC BOARD
IJH3
D E F G3
G2
G1
H1
H2
A
B
H4
C
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
7
cdvi.com
cdvigroup.com
EN

1 Giga octet SD Card, which must be inserted.
A SD CARD CONNECTOR
- ON = event with user name*,
- OFF = event without user name**.
- OFF = the “OFF” position allows normal
functioning of the TERENA system.
- ON = if the dipswitch 2 is in the “ON” position,
the “LOW BAT” LED ashes, indicating
that a secure shut-down procedure is in progress.
Wait until the “RX”, “TX”, “AL” and “SCR” LEDs
are no longer lit up before disconnecting the TERENA.
After the TERENA has been shut down
with the dipswitch 2:
- Set the dipswitch back to the “OFF” position,
- Disconnect the battery and the mains supply,
- Then reconnect to the mains and battery
(the battery alone cannot power up the TERENA).
- Reserved.
- ON = Site reset, authorized on the administration page,
- OFF = Normal mode.
When an event is displayed and printed, the user
name of the person who presented his/her tag
appears.
When an event is displayed and printed, the user
name of the person who presented his/her tag
does not appear, the tag is simply recognized.
B DIPSWITCH CORRESPONDENCE
Reserved
E RS232 CONNECTOR
- Direct PC connection in local mode (crossover cable)
or using a HUB or Switch (straight-through cable).
- Connection to a local network (straight-through
cable) to the network distribution rack .
- Connected to the Ethernet network (RJ45 cable)
to the Ethernet router (BOX).
F ETHERNET CONNECTOR
Reserved
D USB DEVICE CONNECTOR
Reserved (CMPP)
C USB HOST CONNECTOR
3 point terminal block
G1 BAT+ + Battery 12 V - 7A
BAT-
- Battery 12 V - 7A
3 point terminal block
G2
AC Power supply AC - 12 V (transformer)
AC Power supply AC - 12 V (transformer)
Ground (Yellow/Green)
17 point terminal block
G3
1Contact arming board 1 (Alarms)
2Common
3Contact arming board 2 (Alarms)
4Contact arming board 3 (Alarms)
5Common
6Contact arming board 4 (Alarms)
AA - RS485 Bus
GND Cable shielding
BB- RS485 Bus
NO Alarm contact (readers) normally open
C1 Common
NC Alarm contact (readers) normally closed
NO
Alarm contact (alarm board) normally open
C2 Common
NC
Alarm contact (alarm board) normally closed
S1 Tamper contact
S2 Tamper contact
G TERMINAL CORRESPONDENCE
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
8cdvi.com
cdvigroup.com
EN

CR2032 lithium battery - 70 mA. Saves date and time.
I BACKUP BATTERY
Standard position for this dipswitch.
J DIPSWITCH CENTRAL
H1
BATT ON Battery on charge
BATT.CHECK Battery test
A.C Mains voltage presence
H2
AL
Alarm in progress (readers, alarm boards,
auto-protection)
SCR
Readers are being checked (1 reader
installed)
RX RS485 Bus reception
TX RS485 Bus emission
H3
WP Write-protected SD Card
ON SD Card active
CD SD card is present and detected
LOW BATT Battery status (voltage levels)
H4
HOST “HOST” Mode peripheral recognized
PWR “HOST” USB output powered
DEV “HOST” connected
CONN Connected in “DEVICE” mode
H WARNING LIGHT CORRESPONDENCE - Battery monitoring is stopped, (the “LOW BAT”
LED is lit up and the “BAT ON” and “BAT CHECK”
LEDs are not lit up),
- The system comes to a complete halt if the
TERENA is not connected to the mains supply.
If the TERENA is connected to the mains without
a battery, the “BAT ON” and “BAT CHECK” LEDs
are not lit up. If the TERENA is functioning on
battery power, the battery charge status is analyzed
(VHIGH = 14.4V, VLOW=11.5V and VCRITICAL = 10.2V)
in order to dene what action needs to be taken.
1] When the battery charge level is above VHIGH :
- Data is backed up
- Battery monitoring is stopped, the “LOW BAT”
and “BAT ON” LEDs are not lit up.
2] If the battery charge level is between “VHIGH”
and “VLOW”, the system functions normally.
The “LOW BAT” LED is not lit up and the “BAT ON”
LED is lit up. A verication procedure is carried
out every 2 minutes (the “BAT check” LED is lit up).
3] If the battery charge level is between “VLOW”
and “VCRITICAL”, the battery is put on to charge.
The “LOW BAT” and “BAT ON” LEDs are lit up.
A verication procedure is carried out every
2 minutes (the “BAT check” LED is lit up).
4] If the battery charge level is below “VCRITICAL” :
- A back-up of the memory is done on the SD card,
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
9
cdvi.com
cdvigroup.com
EN

7] SUPPLEMENTARY MODULES
The door controller (Ref : INTBUSW)
Elevator controller boards (C14D/A)
The readers (Wiegand format)
6] THE DOOR CONTROLLER (INTBUSW) AND READERS
- An INTBUSW door controller is required for each
reader connected on the RS485 BUS.
- The distance between the central control unit
and the last door controller (INTBUSW) may not
exceed 1000m.
- Pay extreme care not to install wires close to high
power cabling (for example : 230 V AC).
- Recommended wires > 1 twisted pair, SYT1 8/10ths
shielded wire (EIA-485 standard).
- The controller is connected to the central control
unit using a 2 wire cable (RS485 BUS >
Recommended cables : 1 twisted pair, SYT1
8/10ths shielded wire (EIA-485 standard).
- 14 “alarm contact” inputs (C14A/E) or 14 “relay contact”
outputs (C14A/S)
- C14D/E and C14A/S address settings are done
using dipswitches (max. 4 per central unit).
- The readers are connected to the door controller
(INTBUSW) using 7 or 8 wires depending
on the technology.
- The 26, 30 or 44 bit format depends on the type
of head used (refer to the attached table
of Wiegand reader formats (factory settings).
- The door controller is connected to the central
control unit using a 2 wire cable (RS485 BUS >
Recommended cables : 1 twisted pair, SYT1
8/10th shielded wire (EIA-485 standard).
- The readers must be daisy-chained.
- To secure the installation, do not forget to insert
a 120 ohm resistor between A and B, on the last
door controller or supplementary module (C14A/E,
C14A/S, C14D/A or C1410S) of the RS485 BUS.
TERMINAL CORRESPONDENCE
CCommon contact relay
1NO Contact relay 1
2NO Contact relay 2
3NO Contact relay 3
4
NO Contact relay 4
5
NO Contact relay 5
6NO Contact relay 6
7NO Contact relay 7
8NO Contact relay 8
9NO Contact relay 9
10
NO Contact relay 10
11
NO Contact relay 11
12 NO Contact relay 12
13 NO Contact relay 13
14 NO Contact relay 14
MRS485 Cable shielding
A“A” of the RS485 BUS
B“B” of the RS485 BUS
V12 V DC Power Supply
V12 V DC Power Supply
Card 1 Card 3
Card 2 Card 4
TERENA - TERENA16
Web Based Access Control
INSTALLATION MANUAL
10 cdvi.com
cdvigroup.com
EN
This manual suits for next models
1
Table of contents
Other CDVI IP Access Controllers manuals

CDVI
CDVI DGLIWLC User manual

CDVI
CDVI Ievo User manual

CDVI
CDVI PASS KCPASS User manual

CDVI
CDVI PROMI500 User manual

CDVI
CDVI KCPROXWLC User manual

CDVI
CDVI STAR1M User manual

CDVI
CDVI micro IEVO-M User manual

CDVI
CDVI GALEOR User manual

CDVI
CDVI Digicode Mifare PCV123D User manual

CDVI
CDVI NANOPW User manual

CDVI
CDVI Digicode Mifare PCV123D User manual

CDVI
CDVI DGLIWLC User manual

CDVI
CDVI DGLIEWLC User manual

CDVI
CDVI MOONARW User manual

CDVI
CDVI KCPROXWLC User manual

CDVI
CDVI SOLARPW User manual

CDVI
CDVI KCPROXWLC User manual

CDVI
CDVI SOLARPW User manual

CDVI
CDVI BIOSYS 1 User manual

CDVI
CDVI SOLARPB Instruction Manual