Aritech 2000 Series User manual

2000 SERIES SENSORS
Revision 3.1 : June 1997
INSTALLATION GUIDE
Downloaded from: http://www.guardianalarms.net


2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
CONTENTSCONTENTS
1. INTRODUCTION 1
1.1 SCOPE 1
1.2 2000 SERIES PRODUCTS OVERVIEW 2
2. INSTALLATION 3
2.1 GENERAL 3
2.2 AUTOMATIC FIRE SENSORS 3
2.2.1 Where To Place Automatic Fire Sensors 3
2.2.2 Mounting Bases & Wiring Diagrams 4
2.2.3 Addressing 7
2.2.4 Technical Data 7
2.2.5 7-Segment Indication 8
2.2.6 Diagnostics and Sensitivity Test Modes 9
2.2.7 Testing, Maintenance and Cleaning 10
2.3 MANUAL CALL POINT (MCP) DM2000 DM2010 DM2020 12
2.4 ISOLATOR IU2016 14
2.5 FIRE MONITORING CONTROLLERS 16
2.5.1 Zone Monitoring Unit IU2051 16
2.5.2 Indicating Circuit Controller IU2080 19
2.6 INPUT / OUTPUT UNITS 27
3. LOOP LOAD CALCULATIONS 30
3.1 GENERAL 30
3.2 CALCULATION PROCEDURE 30
3.2.1 Standby Current 31
3.2.2 Alarm Current 31
3.2.3 Loop Resistance 32

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
1. INTRODUCTION
1.1 SCOPE
This document is a guide for the installation of the Aritech 2000 Series Range of Analogue
Addressable Fire Monitors and Aritech 2000 Series Monitoring Controllers and Input / Output
Units.
Other manuals are:
Product Code
FP2000 Series Reference Guide LKFP2503
FP2000 Series Network Configuration Guide LKFP2303
FP2000 Series End User Instruction Manual LKFP2403

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
1.2 2000 SERIES PRODUCTS OVERVIEW
Product Part Number Base
Temperature Monitors:
Single LED without remote LED driver DT2053 DB2001(U)
Single LED, 7-segment display, remote LED driver DT2073 DB2002(U)
Two LED with remote output DT2063 DB2002(U)
Ionisation Smoke Monitors:
Single LED without remote LED driver DI2052 DB2001(U)
Single LED, 7-segment display, remote LED driver DI2072 DB2002(U)
Two LED with remote output DI2062 DB2002(U)
Optical Smoke Monitors:
Single LED without remote LED driver DP2051 DB2001(U)
Single LED, 7-segment display, remote LED driver DP2071 DB2002(U)
Two LED with remote output DP2061 DB2002(U)
Manual Call Points:
Manual Call Point DM2000 —
Manual Call Point : IP66 DM2010 —
Manual Call Point : yellow for gas release DM2020 —
Isolator:
Isolator IU2016 DB2003
Fire Monitoring Controllers:
Zone Monitoring Unit IU2051 —
Indicating Circuit Controller IU2080 —
Input / Output Units:
4 Inputs / 4 Outputs IO2034 —
2 Inputs / 2 Outputs IO2032 —
2 Inputs / 1 Output IO2031 —
4 Inputs IO2014 —
Optional Housing for I/O units
(123mm (W) x 173mm (L) x 50mm (H)) IOBOX —
Table 1: Aritech 2000 Series Products

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
2. INSTALLATION
2.1 GENERAL
The FP2000 Series Analogue Addressable Fire Panels can address up to 128 Aritech
devices on a two-wire ring circuit (loop) using digital communication.
The following paragraphs will describe the connection and addressing of Aritech devices
in a fire protection system.
2.2 AUTOMATIC FIRE SENSORS
2.2.1 Where To Place Automatic Fire Sensors
SITING AND SPACING DETECTORS
Please consult local regulations and follow Fire Brigade requirements.
The following apply for flat, horizontal ceilings:
SMOKE
DETECTORS HEAT
DETECTORS
Max. area coverage 100m250m2
Max. horizontal distance between any point in
the area and the nearest detector 6m 5m
Max. ceiling height (general limits) 12m 6m
Note that these values change if:
•appliance is in small corridors
•there are obstructions
•appliance is in the apex of a pitched roof

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
SUITABLE LOCATIONS FOR SMOKE & HEAT DETECTORS
General rule : ION :Flaming Fire
OPTICAL :Smouldering Fire
HEAT :Full Combustion Fire
LOCATION ION OP
THEAT REMARKS
Corridor / Walkway # Air current may exist
Elevator Shaft / Duct # Air current is present
General Office / Day Room #
Hotel Foyer #
Dining Room #
Theatre Stages / Audience
Hall #
Warehouse # Not if diesel fork lifts
are used
School #
Clinic / Nursery Room #
Laboratory #
Studio / Recording Room # Possibility of flaming
fire
Factory #
Church / Chapel #
Cargo Handling Area # Presence of air current
& dust
Spirit Fuel Store # Fast, clean burning fire
Library Room #
Central Heating Room #
Dryer Room #
Kitchen # Avoid locations over
ovens
Smoky Atmosphere #
Closed Parking Area #(1) # (1) : delayed or double
knock
2.2.2 Mounting Bases & Wiring Diagrams
All connectors on the base are numbered and have the following function:
1:(+) remote LED
2:(-) remote LED
5:(+) line in and out
6:(-) line in and out
Earth : to continue ground shield

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
There are 4 different Mounting Bases available for the 2000 Series Sensors:
DB2001 :sensor base without remote LED connectors (Ø 10 cm)
DB2001U :sensor base without remote LED connectors (Ø 15 cm)
DB2002 :sensor base with remote LED connectors (Ø 10 cm)
DB2002U :sensor base with remote LED connectors (Ø 15 cm)
When sensors with remote LED drivers are being installed (for example DT2073,
DI2072, DP2071), the DB2002 or DB2002U should be used.
Please refer to Figure 1for Class A, and Figure 2for Class B (no return) wiring.
It is not necessary to observe polarity on terminals 5 and 6 as the fire monitors are not
polarity sensitive, but when the remote LED driver is being used, polarity must be
observed !
To install a detector head, insert the head and rotate it clockwise until it is properly
aligned and "sets" into the base (Figure 3). Then rotate it an additional 15º to lock it in
place.
Each 2000 Series Universal Mounting Base is equipped with a moulded locking
mechanism to prevent unauthorised removal of the sensor head (Figure 4). If you want
detectors to be locked into the base, remove tab before inserting into the base. To
remove the sensor head, insert a small screwdriver into the slot on the side of the base
and press in while simultaneously turning the sensor head counter clockwise (Figure 5).
The different Aritech Mounting Bases are designed so that the fire sensors will not
operate in the Isolator Mounting Base DB2003 and vice versa. The 2000 Series Range
of Fire Sensors will also not fit the base of another Aritech Range of Sensors.
A ground shield is strongly recommended, but not required. The shield must be
connected to the earth ground at one point only, preferably via an earth stud in the fire
control panel.
Address tags are available to write the address of the detector on. The address tag
should be positioned before the base is mounted.
Figure 1: Class A Wiring

2000 SERIES SENSORS INSTALLATION GUIDE Revision 3.1 June 1997
Figure 2: Class B Wiring
Figure 3Figure 4Figure 5