Airstream TC5-2V4SA User manual

TC5-2V4SA
TemperatureController
USER'S MANUAL
HEATER 1
OFF. / DIFF. (T )
(T )
M 890-00103 rev. 06 REV. 00

2TC5-2V4SA rev.06
TABLE OF CONTENTS
PRECAUTIONS .............................................................. 3
FEATURES..................................................................... 4
LOCATION OF THE CONTROLS................................... 6
ControllerStatusLeds ...................................................... 7
InternalSwitches............................................................... 7
INSTALLATION .............................................................. 8
MountingInstructions ........................................................ 8
Connections ..................................................................... 8
MotorTypes ..................................................................... 9
Heating/CoolingOption ....................................................10
TemperatureProbes ........................................................11
CHANGING THE PARAMETER SETTINGS .................. 14
UsingtheDisplay..............................................................14
LockingtheParametersSettings...................................... 15
TEMPERATURE SETTINGS .......................................... 16
TemperatureUnits ............................................................16
ViewingTemperatures .....................................................16
TemperatureSetPoint .....................................................19
TemperatureCurve...........................................................20
VENTILATION SETTINGS.............................................. 24
CoolingOperation ............................................................24
MinimumVentilationCycle................................................26
HumidityCompensation ...................................................28
MinimumSpeedCurve ..................................................... 31
DifferentialSettings ..........................................................37
De-icing of Stage 2 Fans..................................................39
Mist Cooling .....................................................................41
HEATER SETTINGS....................................................... 44
ALARM SETTINGS......................................................... 49
TEST MODE.................................................................... 50
TROUBLESHOOTING GUIDE........................................ 51
TECHNICAL SPECIFICATIONS..................................... 55
FACTORY SETTINGS .................................................... 56
GLOSSARY..................................................................... 58
Page

3
TC5-2V4SA rev.06
We strongly recommend installing supplementary natural
ventilation as well as a back-up thermostat on at least one
cooling stage (refer to the wiring diagram enclosed with this
user's manual to connect the thermostat).
Although fuses at the input and outputs of the controller
protect its circuits in case of an overload or overvoltage, we
recommend installing an additional protection device on the
controller's supply circuit.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO 40°C).
To avoid exposing the controller to harmful gases or exces-
sive humidity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE CONTROLLER
PRECAUTIONS
FOR CUSTOMER USE
Entertheserialnumberlocatedonthe
sideofthecontroller below forfuture
reference.
Modelnumber:
Serialnumber: TC5-2V4SA

4TC5-2V4SA rev.06
The TC5-2V4SA is an electronic device used for environmental control in
livestock buildings. It allows the user to maintain a specified target tem-
perature by controlling the operation of ventilation and heating equipment.
Two stages of variable speed fans can be connected to the controller, as
well as two stages of constant-speed fans and two stages of either con-
stant-speedfansorheatingunits.Inaddition, one of the constant-speed fan
stages can be configured as a mist cooling stage.
ThemainfeaturesoftheTC5-2V4SAareas follows:
THREE-DIGITDISPLAY
A three-digit display provides a high level of accuracy, allowing the user to
specify a temperature to within one tenth of a degree (in Fahrenheit or Cel-
sius units).
PILOT LIGHTS
Pilot lights indicating the state of outputs allow the user to monitor the
operation of the system without having to enter the building.
MINIMUMVENTILATION CYCLE
Whenventilationisnotrequiredforcooling, the first stage fans can be oper-
atedeithercontinuouslyorintermittentlytoreducethelevelofhumidityand
supply oxygen to the room.
TEMPERATUREAND MINIMUM VENTILATIONSPEED CURVES
Thecontrollercanbeset to automatically change the temperature set point
andtheminimumventilation speed overagivenperiodof time inaccordance
withthe user's requirements by specifying a temperature curve and a mini-
mum ventilation speed curve with up to six different points each.
CHOICE OF TEN MOTOR TYPES
Thevariationin motor speed resulting from a change in voltage will depend
onthemakeandcapacityofthemotor. Inorderto achieve a high degree of
compatibilitybetweencontroller andmotor,theuser canchoosefromamong
tendifferent motor types, thus ensuring that the correct voltageissupplied.
ZONEDORCASCADING HEATERS
HIGH/LOW TEMPERATUREALARM OUTPUT
FEATURES

5
TC5-2V4SA rev.06
TC5-2V4SA
HUMIDITYCOMPENSATION
Thestage1 minimum speed can be adjusted automatically as a function of
relative humidity. As humidity increases, the minimum speed of stage 1
fans increases proportionally to compensate for the change.
FULL-SPEED FAN START-UP
In order to overcome the inertia of the ventilation system components and
de-ice the fan blades in cold weather conditions, the controller supplies
maximumvoltagetothevariable speed fans during the 2 seconds immedi-
ately following each start-up.
DE-ICINGCYCLE
Ade-icing cycle is provided for de-icing stage 2variable-speedfans in cold
weatherconditions.
FOURINDEPENDENT TEMPERATURE PROBE INPUTS
Uptofourtemperatureprobescan be connected to the controllerinorderto
obtain a more accurate reading of the average room temperature and a
faster reaction time.
OVERLOADAND OVERVOLTAGEPROTECTION
Fuses are installed at the input and outputs of the controller to protect its
circuitryinthecase of an overload or overvoltage.
COMPUTERCONTROL
The controller can be connected to a computer, thus making it possible to
centralizethemanagementof information and diversify control strategies.
CONTROL OF AIR INLET MOVEMENT
IftheTC5-2V4SA is used in combination with a PF-5B controller, the move-
mentoftheairinletscanbe coordinated with the operation of the fansusing
a potentiometer located on the panel drive. This allows the air inlets to be
adjusted correctly, without the influence of uncontrollable factors such as
windorair from adjoining rooms.
TEST MODE
Atestmodeallowsyoutosimulatetemperaturechangesandverifycontrol-
lerperformance.

6TC5-2V4SA rev.06
LOCATION OF THE CONTROLS
SETTINGS
FUNCTIONS

7
TC5-2V4SA rev.06
TC5-2V4SA
CONTROLLER STATUS LEDS
#OFF ON
1UNLOCKED PARAMETERS LOCKED PARAMETERS
2FAHRENHEIT DEGREES CELSIUS DEGREES
3PROBE 2 DISABLED PROBE 2 ENABLED
4PROBE 3 DISABLED PROBE 3 ENABLED
5PROBE 4 DISABLED PROBE 4 ENABLED
6NO HEATING STAGES HEATING
71 HEATER 2 HEATERS
8CASCADING HEATERS ZONED HEATERS
9MIST OFF MIST ON
10 RESERVED
11 RESERVED
12 RESERVED
INTERNAL SWITCHES
The internal switches are located on the inside of the front cover. When
the controller is shipped from the factory, all the switches are set to OFF.
ON
2
134 6 75 8 9 11
10 12
LED MEANING
STAGES 1-2 FLASHES WHEN STAGE 1 FANS ARE ON AND STAYS ON WHEN
STAGE 2 FANS ARE ON.
STAGES 3-4 FLASHES WHEN STAGE 3 FANS ARE ON AND STAYS ON WHEN
STAGE 4 FANS ARE ON.
STAGE 5 /
HEATER 2 TURNS ON WHEN STAGE 5 FANS OR HEATING UNITS ARE ON.
STAGE 6 /
HEATER 1 TURNS ON WHEN STAGE 6 FANS OR HEATING UNITS ARE ON.
To /MIN.SPEED
CURVE FLASHES WHEN THE TEMPERATURE CURVE IS ACTIVATED. TURNS
ON WHEN THE MINIMUM VENTILATION SPEED CURVE IS ALSO ON.
DEF. PROBE/
ALARM TURNS ON WHEN AN ALARM IS DETECTED. BLINKS WHEN A
DEFECTIVE PROBE IS DETECTED
LOCKED TURNS ON WHEN THE PARAMETERS ARE LOCKED.
COMPENSATION TURNS ON WHEN THE COMPENSATION ON STAGE 1 MINIMUM
VENTILATION SPEED IS IN EFFECT OR WHEN THE COMPENSATION
ON THE MIST STAGE IS IN EFFECT.

8TC5-2V4SA rev.06
Toconnectthecontroller,refertothewiringdiagramenclosedwiththisuser's
manual.
nSet the voltage switch to the appropriate voltage.
nUse the electrical knockouts provided at the bottom of the enclosure.
Donotmake additionalholesinthe enclosure,particularlyonthe side
oftheenclosurewhenusingacomputercommunicationsmodule.
nIf Stage 5 or 6 is used for heating, it may be necessary to install a
transformerinordertosupplytheappropriatevoltagetotheheatingunit.
ALARMCONNECTION: Therearetwotypesofalarmsonthemarket. One
typeactivateswhencurrentiscutoffatitsinput,whereastheotheractivates
whencurrentissuppliedatitsinput. Foranalarmofthefirsttype,usetheNO
terminalasshownonthewiringdiagram. Foranalarmofthesecondtype,use
theNCterminal.
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRI-
CIAN AND MUST COMPLY WITH APPLICABLE CODES, LAWS
AND REGULATIONS. BE SURE POWER IS OFF BEFORE DO-
INGANYWIRINGTOAVOIDELECTRICALSHOCKSANDEQUIP-
MENT DAMAGE.
INSTALLATION
MOUNTINGINSTRUCTIONS
CONNECTIONS
Openthelatchandliftthecover.Removetheblackcapslocatedoneachof
thefourmountingholes. Mounttheenclosureonthewallusingfourscrews.
Besure the electrical knockouts are at the bottom oftheenclosurein order
topreventwaterfromenteringthecontroller.Insertthescrewsinthemounting
holesandtighten. Fastenthefourblackcapsprovidedwiththecontrolleronto
the four mounting holes. The enclosure must be mounted in a location that
will allow the cover to be completely opened right up against the wall.
!
WARNING

9
TC5-2V4SA rev.06
TC5-2V4SA
The relationship between the voltage supplied to a motor and its operating
speed is described by a motor curve. This curve varies with the make and
capacityofthemotor. Thevariousmotorsavailableintheindustryhavebeen
dividedinto ten categories and the controller has been programmedwitha
different motor curve for each of these categories. To ensure that the
controller supplies the correct voltages, an appropriate curve must be
selected for Stage 1 and Stage 2 according to the type of fan motors used.
1
Selecting a Motor Type for Stage 1
Refertothelistofmotorsenclosedwiththisuser'smanualtodeterminewhich
type number (1 to 10) is appropriate for the motors used.
nSet the selection knob to STAGE
1 — BANDWIDTH/TIMER. The
Stage 1 bandwidth is displayed
andflashes.
nPressthepush-buttonthreetimes.
Thecurrentlyselectedmotortype
is displayed, alternating with the
letters"tYP".
nUsetheadjustmentknobtoadjustthemotortypetothedesiredvalue.
nReturn to the Stage1bandwidthdisplay by pressingthepush-button
once again.
2
Selecting A Motor Type for Stage 2
Refertothelistofmotorsenclosedwiththisuser'smanualtodeterminewhich
type (1 to 10) is appropriate for the motors used.
MOTOR TYPES

10 TC5-2V4SArev.06
TC5-2V4SA
HEATING / COOLING OPTION
67
ON
nSet the selection knob to STAGE 2 — OFFSET/BANDWIDTH.
The offset is displayed, alternating with the letters "OFT".
nPress the push-button twice. The currently selected motor type
flashes.
nUsetheadjustmentknobtoadjustthemotortypetothedesiredvalue.
nReturn to the Stage 2 offset display by pressing the push-button
once again.
Stages 5 and 6 can operate as heating or cooling stages.
ðSet switches # 6 and # 7 to OFF to
use both stages for cooling.
ðSet switch # 6 to ON and switch # 7
to OFF to use Stage 6 for heating
and Stage 5 for cooling.
ðSet switches # 6 and # 7 to ON to
use both stages for heating.
Note that if only one stage is used for heating, it must be Stage 6.
Table of contents
Other Airstream Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

SMC Networks
SMC Networks Thermo-con INR-244-639 Operation manual

eltherm
eltherm Ex-TC It Series operating instructions

Omron
Omron C200H-TV Series Operation manual

industrie technik
industrie technik CA1 instructions

KRAL
KRAL EET 32 operating instructions

dixell
dixell XR420C Installing and operating instructions