Call 800.879.8585 for Technical Support
OPERATION
Manual ON and OFF control is always available by pressing the ON/OFF button.
Automatic-OFF and Automatic Delayed-OFF are always enabled regardless of
other Setup Mode options.
When set for Automatic-ON mode (see SETUP section), the AS-100 turns ON
the load when it receives the Automatic-ON signal from a Watt Stopper lighting
control panel or other lighting control system.
Automatic Control Signals
Automatic commands to turn OFF or turn ON the load connected to the AS-100
come from the lighting control panel interrupting power to the AS-100 for the
amount of time shown below (timing must be +/- one-quarter of a second):
Command Power Function Description
Interrupt
Duration
• Automatic-ON 3 sec. Lights turn ON (if Automatic-ON Setup Mode
option is enabled).
• Automatic-OFF 5 sec. Lights turn OFF when power is interrupted (for
5 seconds), turn back ON for 7 seconds, then
turn OFF.
• Automatic
Delayed-OFF 1 – 2 sec. Initiates a five-minute delay period before
shutting OFF lights. At any time, pushing the
ON/OFF button before the lights turn OFF
cancels the countdown and keeps the lights
ON until the next control signal from the
lighting control panel, or until the AS-100 is
manually turned OFF.
During the Delayed-OFF period:
1. The lights flash once when power is
interrupted (for 1–2 seconds).
2. The center (red) locator LED begins to blink
once every two (2) seconds.
3. An audible beep sounds once every minute
(if enabled, see Setup section).
4. During the final minute, the LED blinks
once every second and the beep sounds
every five (5) seconds (if enabled) until the
lights are turned OFF.