10 IOM-T-294EXP 2214 © 2022 tekmar
The power LED operates as follows.
LED Operation
On Power applied and control is operating correctly
Off No power or the control is faulty
When powered on, the Smart Boiler Expansion 294EXP communicates to the Smart Boiler Control 294. The communication LED
operates as follows.
LED Operation
On Communication with 294
Off No communication with 294
All boiler relays are normally off and the modulating outputs at 0 V (dc) or 4 mA. The Smart Boiler Control 294EXP responds to
commands from the 294 to turn on a boiler, the modulating signal, and the boiler pump or valve. The status on the 294EXP
display will match the 294 Boiler Status menu.
Output LED Operation
Boiler 5, 9, 13 On Boiler enable 5, 9, 13 relay is closed
Off Boiler enable 5, 9, 13 relay is open
Boiler 6, 10, 14 On Boiler enable 6, 10, 14 relay is closed
Off Boiler enable 6, 10, 14 relay is open
Boiler 7, 11, 15 On Boiler enable 7, 11, 15 relay is closed
Off Boiler enable 7, 11, 15 relay is open
Boiler 8, 12, 16 On Boiler enable 8, 12, 16 relay is closed
Off Boiler enable 8, 12, 16 relay is open
Boiler Pump/Valve 5, 9, 13 On Boiler pump/valve 5, 9, 13 relay is closed
Off Boiler pump/valve 5, 9, 13 relay is open
Boiler Pump/Valve 6, 10, 14 On Boiler pump/valve 6, 10, 14 relay is closed
Off Boiler pump/valve 6, 10, 14 relay is open
Boiler Pump/Valve 7, 11, 15 On Boiler pump/valve 7, 11, 15 relay is closed
Off Boiler pump/valve 7, 11, 15 relay is open
Boiler Pump/Valve 8, 12, 16 On Boiler pump/valve 8, 12, 16 relay is closed
Off Boiler pump/valve 8, 12, 16 relay is open
Two DIP switches located on the top left side of the control. The DIP switch positions determine the boiler groups that the Smart
Boiler Expansion 294EXP operates.
Boilers DIP Switch 1 DIP Switch 2
5 to 8 Off Off
9 to 12 On Off
13 to 16 Off On
Sequence of Operation
Power On LED
Communication LED
Boiler Output Operation
DIP Switches