WAGNER TITANUS RACK-SENS 1U User manual

Contents TITANUS RACK·SENS®1U
Data: 03/09
TRS_A_Inhalt-en-e
Contents
0General 0 – 1
0.1 Introduction 1
0.2 Safety Information 1
0.3 Warranty 2
0.4 Copyright 2
0.5 Packaging 3
0.6 Disposal 3
0.7 Instructions for the user 4
1Product Description 1 – 1
1.1 Features of the TITANUS RACK·SENS®1U
air sampling smoke detection system 1
1.2 Areas of Application 4
2Technical Description 2 – 1
2.1 System description 1
2.1.1 Functional description 2
2.1.2 Display panel 4
2.2 TITANUS RACK·SENS® 1U and accessories 6
2.2.1 Overview 6
2.2.2 TITANUS RACK·SENS® 1U
air sampling smoke detection system 7
2.2.3 Operation 10
2.2.4 Diagnostics tool 12
2.2.5 Optical Indicator 13
2.3 Pipe system 14
2.3.1 Complete overview of available pipe components 15
2.3.1.1 Standard sampling pipe 16
2.3.2 Aspiration Reduction Films 17
2.3.3 Integrated air filter 18
2.3.4 Shutdown module 18
2.3.5 Temperature sensor 19
2.3.6 Door contact switch 19
3Technical Data 3 – 1
3.1 TITANUS RACK·SENS®1U 1
3.2 Pipe system TITANUS RACK·SENS®1U 3
3.3 TITANUS RACK·SENS®1U accessories 4
www.acornfiresecurity.com
www.acornfiresecurity.com

TITANUS RACK·SENS®1U Contents
TRS_A_Inhalt-en-e Data:03/09
Contents
4Design 4 – 1
4.1 General 1
4.1.1 Regulations 1
4.1.2 Positioning the TITANUS RACK·SENS® 1U
and the pipe system for detection 2
4.2 Project planning – Smoke aspiration 3
4.2.1 TITANUS RACK·SENS®1U 3
4.3 Project planning for 19” cabinets 4
4.3.1 Smoke detection in 19” cabinets with standard sampling pipe 4
4.3.2 Smoke detection in 19” cabinets with customised sampling pipe 6
4.3.3 Protection for cabinets in rows or consecutive cabinets 11
4.4 General pipe system project planning 14
4.4.1 Pipe system configurations 14
4.4.2 Sensitivity 17
4.4.3 Pipe Design 19
4.4.3.1 Simplified Pipe Design (local application protection) 19
4.4.3.2 I-Pipe system 19
4.4.3.3 U-Pipe system 20
4.4.3.4 M- Pipe system 21
4.4.3.5 Double-U-Pipe system 22
4.5 Temperature monitoring 23
4.6 Device shutdown 23
4.7 Door contact switch 23
4.8 Air flow monitoring 24
4.8.1 General project planning instructions
for shutdown and cooling shutdown 25
4.10 Calculating detection sensitivity 26
4.11 Power Supply 27
4.11.1 Calculating capacity for external power supply 27
5Installation and wiring of
TITANUS RACK·SENS®1U 5 – 1
5.1 General 1
5.2 Installation site 2
5.2.1 Mounting the TITANUS RACK·SENS®1U
air flow smoke sampling system 2
5.2.2 TITANUS RACK·SENS®1U installation 3
5.2.3 Connection for sampling pipe 4
5.2.4 TITANUS RACK·SENS®1U electrical connection 5
www.acornfiresecurity.com
www.acornfiresecurity.com

Contents TITANUS RACK·SENS®1U
Data: 03/09
TRS_A_Inhalt-en-e
Contents
5.2.5 Connecting the external 24 V supply 7
5.2.6 Connection to mains supply 230 V 8
5.2.7 Circuit diagram TITANUS RACK·SENS®1U for
connecting to a fire alarm panel with potential-free contacts 9
5.2.8 Device “reset” circuit diagram for individual
TITANUS RACK·SENS®1U devices 10
5.2.9 Device “reset” circuit diagram for several
TITANUS RACK·SENS®1U devices 11
5.2.10 Installation and connection of door contact switch 12
5.2.11 Installation and connection of temperature sensors 15
5.2.12 Installation and connection of shutdown module (low power) 17
5.2.13 Installation and connection for device shutdown (high power) 19
5.2.14 Connecting the response indicator to the
TITANUS RACK·SENS®1U 20
6Installation of the Pipe System 6 – 1
6.1 Patented Air Sampling Points 4
6.2 Monitoring in Forced Air Flow Systems
(Ventilation or Climatic Applications) 6
6.2.1 Detection at Air Inlets/Outlets 6
7Commissioning 7 – 1
7.1 Operating TITANUS RACK·SENS®1U 1
7.1.1 Key switch 1
7.1.2 Config. Temp. button 1
7.1.3 Reset and buzzer off button 2
7.1.4 Air flow initialisation 3
7.2 Commissioning TITANUS RACK·SENS®1U 4
7.2.1 Termination of unused inputs 4
7.2.2 Commissioning procedure 5
7.2.3 Settings adjustment with the diagnostics tool 7
7.2.4 Settings for main board and detector module 8
7.2.4.1 Alarm delay setting 9
7.2.4.2 Air flow range setting 9
7.2.4.3 Fault delay setting 10
7.2.4.4 Pre-warning period setting 10
7.2.4.5 Buzzer setting 11
7.2.4.6 Fault indicator setting 11
7.2.4.7 Dynamic air flow setting 11
7.2.4.8 Sensitivity setting (main alarm) 12
7.2.4.9 Pre-alarm threshold setting 12
7.2.4.10 Setting LOGIC·SENS 12
7.2.5 Air flow initialisation setting 13
7.2.5.1 Setting height above Normal Sea Level (NN) 14
7.2.5.2 Setting the current air pressure 14
7.2.5.3 Fan voltage setting 14
7.2.6 Setting the programmable relays and the temperature alarm 15
www.acornfiresecurity.com
www.acornfiresecurity.com

TITANUS RACK·SENS®1U Contents
TRS_A_Inhalt-en-e Data:03/09
Contents
7.3 Data logging 18
7.3.1 Example of a commissioning log (2 pages) 19
7.4 Testing the detection unit and alarm forwarding 21
7.5 Testing response behaviour in cabinets 22
7.6 Testing air flow monitoring 23
7.7 Testing Fault Forwarding 24
7.8 Installing the diagnostics software and the USB driver 25
7.8.1 Installing the USB driver 26
7.8.2 TITANUS RACK·SENS®1U operation using DIAG 3 27
8Maintenance 8 – 1
8.1 Procedure for servicing 1
8.2 Trouble shooting 2
8.3 Inspection 3
8.3.1 Visual Inspection 3
8.4 Testing Detector and Alarm Forwarding 3
8.5 Filter replacement in the integrated air filter 4
8.6 Backup battery replacement 5
8.7 Checking the air flow sensor adjustment 7
8.8 Checking the detector status 9
8.9 Testing Air Flow Monitoring 9
8.10 Testing Fault Forwarding 9
8.11 Maintenance intervals 10
Appendix
System Product List
Testing Record
Commissioning Record
www.acornfiresecurity.com
www.acornfiresecurity.com

TITANUS RACK·SENS® 1U General
TRS_A_00-en-e Stand: 04/08 0– 1
0 General
0.1 Introduction
This manual is designed for people which are planning, installing and
servicing fire alarm systems. These are mainly engineers, service techni-
cians, and installers etc who have specialist knowledge in the field of fire
alarm technology but who may be working with this equipment for the first
time.
WAGNER Group GmbH, referred to below as WAGNER, accepts no li-
ability for damage and breakdowns which occur because of a failure to
comply with this manual.
This manual relates to the TITANUS RACK·SENS®1U aspirating smoke
detection system which is to be used exclusively for early and earliest fire
detection.
0.2 Safety Information
The following symbols identify parts of the text in this manual which re-
quire special attention so that damage can be avoided and so that opera-
tions can run smoothly.
This symbol warns against actions which might cause damage if it is
ignored.
This symbol warns against actions which could cause operational break-
downs if it is ignored.
Operational improvements can be achieved if this symbol is observed.
ATTENTION
INSTRUCTION
TIP
www.acornfiresecurity.com
www.acornfiresecurity.com

General TITANUS RACK·SENS®1U
0– 2 Data: 03/09 TRS_A_00-en-e
0.3 Warranty
The manual is subject to technical modification without notice and makes
no claim to be complete.
In principle our “Terms and Conditions of Supply and Assembly” apply.
Warranty and liability claims for damage to persons or property are ex-
pressly excluded if they are based on one or more of the following
causes:
•Inadequate compliance with instructions regarding project planning,
installation of the air sampling smoke detection system, installation
of the pipe system, commissioning and maintenance
•Improper use of the air sampling smoke detection system
•Inadequate monitoring of wear and tear elements
•Incorrectly performed repairs
•Own structural modifications to the air sampling smoke detection
system
•Force majeure
0.4 Copyright
WAGNER holds the copyright to this technical manual.
The manual is designed for use by the fitter and their employees only.
Reproducing the manual or extracts from it is not permitted. The manual
may only be copied or distributed in any way whatsoever after prior writ-
ten authorization from WAGNER.
www.acornfiresecurity.com
www.acornfiresecurity.com

TITANUS RACK·SENS® 1U General
TRS_A_00-en-e Stand: 04/08 0– 3
0.5 Packaging
The individual air sampling smoke detection systems are packed in ac-
cordance with the anticipated transport conditions. Exclusively environ-
mentally friendly materials were used for the packaging.
The packaging is intended to protect the air sampling smoke detection
system from being damaged until it is installed. For that reason, it should
only be removed from its packaging shortly before installation.
The packaging material is to be disposed of in accordance with applica-
ble statutory provisions and local regulations.
zDispose of the packaging materials in an environmentally friendly
manner.
zObserve local disposal regulations.
Packaging materials are valuable raw materials and in many cases can
be re-used or expediently processed and recycled. Improper disposal of
packaging materials can harm the environment.
0.6 Disposal
If no take-back or disposal agreements have been made, disassembled
components are to be taken for recycling:
zTake metal parts for scrapping.
zTake plastic parts to be recycled.
zSort the remaining components by material quality and dispose of
them.
INSTRUCTION
www.acornfiresecurity.com
www.acornfiresecurity.com

General TITANUS RACK·SENS®1U
0– 4 Data: 03/09 TRS_A_00-en-e
0.7 Instructions for the user
zRegular visual inspections and functional tests must be carried out to
ensure the system remains functional. Such tests are an integral part
of the system documentation and must be set out by the installer of the
system in accordance with the system parameters.
Any physical modification to the protected object must be coordinated
with the installer to ensure the system remains fully functional.