Verasys LC-SBH200-0 User manual

LC-SBH200-0, LC-VZC100-0, LC-VEC100-0, LC-ZEC510-0, LC-ZEC310-0, LC-BYP200-0, LC-
VAC1000-0, LC-VAC1001-0, LC-VAC1002-0, LC-VAC1100-0, LC-VAC3000-0, LC-IOM3711-0
Building Technologies & Solutions
www.johnsoncontrols.com
2021-04-08
Verasys System Product Bulletin
LIT-12012342
Release 4.0

2 Verasys System Product Bulletin

Contents
ContentsIntroduction to the Verasys system............................................................................................................. 5
Features and benefits.................................................................................................................................... 5
Verasys documentation................................................................................................................................. 7
SBH user interface......................................................................................................................................... 9
Supported controllers.................................................................................................................................. 10
Zone and Bypass Damper controllers............................................................................................ 10
VAV box controllers........................................................................................................................... 10
Verasys Equipment and Application Controllers (VEC and VAC)................................................. 11
Verasys Equipment Controller (VEC100)......................................................................................... 11
Verasys Lighting controller (VAC1001)............................................................................................ 11
Input/Output Module....................................................................................................................... 11
Controller features................................................................................................................................... 12
Constant Volume application........................................................................................................... 12
Sideloop application.......................................................................................................................... 12
Verasys Zone Coordinator................................................................................................................ 12
TEC30xx or TEC36xx Thermostat controllers................................................................................. 12
Verasys Pro Wireless Field Bus System........................................................................................... 13
Ideal applications..................................................................................................................................... 13
Applications to avoid............................................................................................................................... 13
PENN A52x refrigeration controllers............................................................................................... 14
Third-party BACnet controllers........................................................................................................ 14
Verasys application coverage..................................................................................................................... 14
Ordering information.................................................................................................................................. 16
Technical specifications............................................................................................................................... 21
North American emissions compliance..................................................................................................... 32
United States...................................................................................................................................... 32
Canada................................................................................................................................................ 32
Product warranty......................................................................................................................................... 33
Software terms............................................................................................................................................. 33
Patents........................................................................................................................................................... 33
Single point of contact................................................................................................................................. 33
Contact information..................................................................................................................................... 33
Verasys System Product Bulletin 3

4 Verasys System Product Bulletin

Introduction to the Verasys system
The Verasys system provides bundled equipment and controls solutions that use recognized
and trusted brands. Verasys is a plug-and-play solution that is part of the Johnson Controls®
Smart Systems. The Verasys system features simple, configurable controllers that you can bundle
with HVACR equipment from the factory or install in the field. You can use Verasys to configure
various HVACR controls applications for one building or an entire enterprise without using special
programming tools or control engineering.
The Verasys system features advanced direct digital control (DDC) controllers bundled with Johnson
Controls single packaged units (SPU), actuators, sensors, and damper assemblies. All devices self-
configure, and the Verasys Smart Building Hub (SBH) monitors the devices. Through the SBH,
you can access the system using either a laptop, smart phone, or tablet. The SBH connects to an
Ethernet backbone to enable remote connectivity and additional features, such as email and text
alarms. Verasys supported devices automatically connect the point, alarm, trend, and graphical
definitions. The points appear when you connect devices to the system, thereby making Verasys an
easy-to-use, light commercial building automation system (BAS).
Figure 1: Devices in the Verasys system
Features and benefits
Multi-client connectivity
Access all identifiable devices connected to the BACnet® MS/TP trunk.
Browser-based interface
Local display replacement solution so you can access device information through any supported
web browser.
5Verasys System Product Bulletin

Wi-Fi connectivity
Commission, configure, and access building automation equipment using Wi-Fi-enabled smart
devices or laptops.
Advanced features
View device and site alarms, events, and trends. Modify schedules and commission devices.
Browser-based remote building management
Remote management of building systems.
BACnet MS/TP integration
Add third-party devices into the Verasys ecosystem through BACnet MS/TP integration.
Simple interlocks to IOM controllers
Connects different systems to the Verasys network, such as exhaust and lighting systems.
Schedule synchronization
Combines common schedules with the schedule synchronization feature.
Zone groups for scheduling
Create schedules for multiple controllers in the same zone group.
Easy-to-use intuitive user interface (UI)
Uses color-coded bars on point listings so that you can quickly view the most important statuses
from a long list of points.
Wireless end device solutions
Uses the Verasys Pro Wireless system to connect the TEC3000 Thermostats to a SBH using wireless
signals.
Enterprise connectivity
Verasys Enterprise is a cloud-based solution that provides a multi-site aggregation of equipment,
data, alarms, setpoints, and schedules to authorized users. The enterprise application provides
a holistic view of an enterprise and the information that is required to manage HVAC, lighting,
energy, and input and output data for customers who have large building portfolios.
New user experience for facility
Offers continued improvement and equipment relationship for simple user view for end-users
and contractors. Included is a summary page for all HVAC devices serving spaces that includes
indicators for Name, Temperature, Status, and Occupancy, and a single area to change the
setpoint of the facility.
Data share
Share data from one source to multiple destinations. For example, share an outside air temperature
(OAT) from a SMART Equipment rooftop unit (RTU) to multiple TEC3000 devices using only one OAT
source.
Device cloning
Copy configuration parameters to other devices of the same type.
Backup and restore
Provides a simple interface to back up all SMART Equipment devices in the system. Store the backup
files on the SBH or download the file to any smart mobile device or computer that is connected to
the SBH.
Verasys System Product Bulletin6

Support for European light commercial to mid-market architecture
Uses Advanced Terminal Unit controllers (ATC) and application-specific, configurable Verasys
controllers in Europe only. A typical application contains small mini-chillers, boilers, an air handling
unit (AHU), and fan coil units (FCU).
Support for European light commercial to mid-market by the integration of York mini-chillers
to the Verasys system. Chiller model numbers:
• YMAA: software version 3.0.0.1114
• YLAA: software version 3.0.0.1114
• YLPA: software version 3.0.0.1114
Verasys documentation
The following table contains a list of the most important Verasys documents. For more
documentation and resources, visit http://www.verasyscontrols.com.
Table 1: Verasys documentation
Information Document title LIT or Part No.
Using the SBH user
interface for tenant
users
Verasys Tenant User Guide LIT-12013613
Using the SBH to
configure the Verasys
system
Verasys System User's Guide LIT-12012371
Overview of Verasys
system components,
features, and
operating modes
Verasys System Operation Overview Technical
Bulletin
LIT-12012370
Overview of Verasys
BACnet MS/TP
communication
Verasys BACnet MS/TP Communications
Technical Bulletin
LIT-12012362
BACnet MS/TP device
integration into
Verasys
Verasys BACnet MS/TP Integration Technical
Bulletin
LIT-12013606
Installing the SBH Verasys Smart Building Hub (SBH) Installation
Guide SBH200
Part No. 24-10737-00237
SBH network and IT
guidance
Verasys Smart Building Hub (SBH) Network
and IT Guidance Technical Bulletin
LIT-12012324
BACnet over IP
integration
Verasys BACnet over IP Integration User Guide LIT-12013287
Verasys Enterprise
overview
Verasys Enterprise Product Bulletin LIT-12013647
Using the Verasys
Enterprise user
interface
Verasys Enterprise Configuration and User
Guide
LIT-12012995
7Verasys System Product Bulletin

Table 1: Verasys documentation
Information Document title LIT or Part No.
Verasys Enterprise
security and IT
overview
Verasys Enterprise Security and IT Guide LIT-12013026
Wireless system
overview
Verasys Pro Wireless Field Bus System Technical
Bulletin
LIT-12013020
Verasys ZEC310 Zone Damper and BYP200
Bypass Damper Controllers Installation Guide
Part No. 24-10143-1248
Verasys Zone Coordinator (VZC) Installation
Guide
Part No. 24-10143-1280
Verasys Equipment Controller (VEC) Installation
Guide
Part No. 24-10143-1272
Verasys Input/Output Module (IOM)
Installation Guide
Part No. 24-10143-1256
Verasys ZEC510 VAV Controllers Installation
Guide
Part No. 24-10143-01485
Verasys 18 Point 240 VAC Application
Controller Installation Guide
Part No. 24-10143-01507
Verasys 32 Point 24 VAC Application Controller
Installation Guide
Part No. 24-10143-01515
Verasys 18 Point 24 VAC Application Controller
Installation Guide
Part No. 24-10143-01477
Verasys Input/Output Module Installation
Guide
Part No. 24-10143-01736
ZFR1821/ZFR1822 Pro Wireless Router
Installation Guide
Part No. 24-10325-00150
Installing Verasys
controllers
ZFR1825 Wireless Field Bus Coordinator
Installation Guide
Part No. 24-10325-00142
Verasys System Product Bulletin8

Table 1: Verasys documentation
Information Document title LIT or Part No.
VEC100 Generic RTU Controller, Modulated
Heating and Modulated Cooling Application
Note
LIT-12013484
VEC100 Generic RTU Controller, Modulated
Heating and Staged Cooling Application Note
LIT-12013361
VEC100 Generic RTU Controller, Staged
Heating and Modulated Cooling Application
Note
LIT-12013485
VEC100 Generic RTU Controller, Staged
Heating and Staged Cooling Application Note
LIT-12013443
VEC100 Generic RTU Heat Pump Controller
Application Note
LIT-12013452
Verasys Constant Volume Controller
Application Note
LIT-12013067
Verasys Input Output Module Application Note
LC-VAC1002-0
LIT-12012992
Verasys Lighting Controller Application Note LIT-12012524
Verasys Sideloop Controller Application Note LIT-12013364
Using Verasys
applications
Verasys System Changeover Bypass Zoning
System Design Application Note
LIT-12012331
List of alarms from
Verasys controllers
Verasys Alarms Summary Technical Bulletin LIT-12013648
SBH user interface
The SBH provides a wireless, intuitive UI optimized for mobile use.
Figure 2 shows the Facility view. Within this view, you can review the entire system to validate the
conditions of the facility by viewing temperature, mode, and occupancy.
Figure 2: Facility feature
9Verasys System Product Bulletin

The SBH UI scales to the device you are using. The main menus and screens are side-by-side on a
computer screen or tablet. On a phone display, you see either the menu or the screens you selected
from that menu, for example, the TEC3000 Home screen. When you view the UI on a phone or
smaller tablet, drag the screen from the left or right to display the required menu or screens.
Supported controllers
The Verasys system supports the following controllers:
• Zone and Bypass Damper controllers
• VAV box controllers
• Verasys Equipment and Application controllers
• Smart Equipment controllers
• TEC30xx/TEC36xx Thermostats
• Terminal Unit controllers (TUC and ATC)
• PENN® A52x refrigeration controllers
• Third-party BACnet controllers
In the following sections you can read about the controllers in more detail.
Zone and Bypass Damper controllers
The Zone Damper (ZEC310) and Bypass Damper (BYP200) controllers are components of the
Verasys zoning system. The Zone and Bypass Damper controllers run a pre-engineered HVAC
zoning application and provide the inputs and outputs required for this application. These
controllers are factory-configured for field installation on a zone or bypass damper assembly when
they are shipped.
The Zone and Bypass Damper controllers include advanced operating modes and multiple features
that ensure occupant comfort. A carbon dioxide (CO2) demand controlled ventilation (DCV) mode
in the Zone Damper regulates CO2 levels within a zone by adding fresh air into the zone during
occupied times. The controller uses occupancy sensing capability to switch from occupied mode to
standby mode based on local activity. To maximize energy savings, standby mode uses setpoints
that are higher than the occupied cooling setpoint and lower than occupied heating setpoint.
VAV box controllers
The VAV box zone controllers run a pre-engineered HVAC zoning sequence and provide the inputs
and outputs that the VAV application requires.
The ZEC510 controller contains multiple features to ensure occupant comfort. Because of an
optional occupancy sensing capability, the ZEC controller can switch from occupied mode to
standby mode based on zone activity. To maximize energy savings, standby mode uses setpoints
that are higher and lower than the occupied mode setpoints.
The ZEC510 controller also uses plug-and-play technology to detect the connected network sensor
types.
To commission VAV controllers, you can use the Verasys SBH, the MAP Gateway, or the VAV
Balancing Thermostat.
Verasys System Product Bulletin10
This manual suits for next models
11
Table of contents
Other Verasys Control System manuals