Velux KFX 210 User manual

VAS 453812-2019-11
KFX 210/211/212/213/214
KFC 210/220
For information on VELUX smokeventilation, please contact your VELUX sales company:
Tel. 01592 778 225 (UK),Tel. 01 848 8775 (IE)
SMOKE
VENTILATION
25-09-2014 07:44:14
Instructions for VELUX control
system for smoke ventilation
ENGLISH

2 VELUX®

VELUX®3
Important information 4-6
Contents of packaging 8-9
Overview of printed circuit board 10-11
Break-glass point KFK 100 12
Smoke detector KFA 100 13
Rain sensor KLA 200 14
Ventilation switch KFK 200 15
Motor terminals 16
Wiring 17
Setting of switches 18-19
Operation of and signals from control unit 20
Back-up batteries 21
Mains connection 22
Status and error indication in control system 23-25
Connected control units 26-31
- Transmit alarm from one control unit KFC to another 26
- Receive and transmit error indications
from one control unit KFC to another 27
- Ventilation switch 28
- Rain sensor 29
- Receive alarm from a primary, external control system 30
- Transmit alarms or error indications
to other external equipment 31
Replacement of frame in control unit 32
Technical data 33
Contents

4 VELUX®
Please read instructions carefully before proceeding and keep them for
future reference behind the battery holder inside the control unit.
Safety
• Control system for smoke ventilation
KFX 210/211/212/213/214 and control unit for
smoke ventilation KFC 210/220 can be used by
persons (aged 8 years and above) with sufficient
experience and knowledge if they have been given
instruction concerning safe use and understand
the hazards involved. Cleaning and user mainte-
nance must not be made by unsupervised chil-
dren.
• Children must not play with the control system.
• The installer must instruct the owner in the
function of the control system including reset-
ting of alarms and position of data plate and
instructions.
• The data plate is placed in the control unit.
• When resetting alarms, be sure not to touch
conductive parts and make sure that no body
parts can get caught in the window when reac-
tivated.
• WARNING! Make sure to use ESD protection
when touching the printed circuit board for
example during installation and service.
Important information

VELUX®5
Product
• The control system has been designed for use with genuine VELUX prod-
ucts. Connection to other products may cause damage or malfunction.
• The control system is in conformity with the Low Voltage Directive and
the EMC Directive for use in household, trade, industry and light industry.
• When installed, the control system complies with protection degree
IP 42.
• The control system can operate smoke ventilation windows with a total
power consumption of 10 A (KFC 210) and 2 x 10 A (KFC 220) respec-
tively.
• The packaging must be disposed of in accordance with national regula-
tions.
• Products, including batteries if any, marked with the crossed out
wheeled bin are regarded as electrical and electronic equipment and
contain hazardous materials, components and substances. The crossed
out wheeled bin symbolises that electrical and electronic equipment
waste must not be disposed of together with household waste. It must
be collected separately at recycling stations or other collection sites or
retrieved directly from households to increase the possibilities of recyc-
ling, reuse and utilisation of electrical and electronic equipment waste.
By sorting electrical and electronic equipment waste with this symbol,
you contribute to reducing the volume of incinerated or buried waste and
to reducing any negative impact on human health and the environment.
Further information can be obtained from the local municipality's techni-
cal administration or from your VELUX sales company.
• If batteries can be removed, product and batteries must be disposed of
separately.
Installation
• Installation must be carried out by a certified person in accordance with
current national regulations.
• The control system must be connected directly to the mains supply in ac-
cordance with national regulations. Ensure that the mains supply cannot
be disconnected unintentionally. It is recommended that disconnection
is only possible using the mains switch or a key switch. At least one of
these means for disconnection must be incorporated in the fixed wiring in
accordance with national wiring requirements.
Maintenance and service
• Disconnect mains supply and back-up batteries before carrying out any
maintenance or service work to the control system and ensure that they
cannot be reconnected unintentionally during this time.
• The control system must be tested after installation, service work and
alterations to the system. It must be inspected by qualified personnel at
least once a year. Tests and inspections must be documented in accord-
ance with national regulations.
• At the yearly inspection, the connected products must be checked ac-
cording to their instructions.
• The printed circuit board monitors the time between inspection periods.
If more than 15 months have passed since the last inspection, the yellow
light-emitting diode is on and an acoustic alarm sounds.
• The batteries must be checked at the yearly inspection. We recommend
that the batteries are replaced at least every four years.
• If you have any technical questions, please contact your VELUX sales
company, see telephone list or www.velux.com.
Important information

6 VELUX®
Declaration of Conformity
We herewith declare that the VELUX control systems for smoke
ventilation
KFX 210 (control unit 3FC F21 (model BD-SC001), smoke detector
KFA 100/3FA F01 and break-glass point KFK 100/3FK F00),
KFX 211 (control unit 3FC F21 (model BD-SC001), smoke detector
KFA 100/3FA F01 and break-glass point KFK 101/3FK F01),
KFX 212 (control unit 3FC F21 (model BD-SC001), smoke detector
KFA 100/3FA F01 and break-glass point KFK 102/3FK F02),
KFX 213 (control unit 3FC F21 (model BD-SC001), smoke detector
KFA 100/3FA F01 and break-glass point KFK 103/3FK F03),
KFX 214 (control unit 3FC F21 (model BD-SC001), smoke detector
KFA 100/3FA F01 and break-glass point KFK 104/3FK F04) and
VELUX control units for smoke ventilation KFC 210 (3FC F21 (model
BD-SC001)) and KFC 220 (3FC F22 (model BD-SC002-01))
− are in conformity with the provisions of Low Voltage Directive
2014/35/EU, EMC Directive 2014/30/EU and the RoHS Directive
2011/65/EU
− have been manufactured in accordance with the harmonised
standards EN 61000-3-2(2014), EN 61000-3-3(2013),
EN 55014-1(2006)+A1(2009)+A2(2011), EN 50130-4(2011),
EN 60335-1(2012)+A11(2014) and EN 62233(2008) and
− have been assessed in accordance with the harmonised standard
EN 50581(2012).
When one of the above-mentioned VELUX control systems or VELUX
control units are connected to a VELUX smoke ventilation window
GGL -K-- ----40, GGU -K-- ----40 or CSP, the total system is to be
considered as a machine, which is not to be put into service until it has
been installed according to instructions and requirements.
The total system then complies with the essential requirements of the
Council Directives 2014/35/EU, 2014/30/EU and 2006/42/EC.
The control systems and control units also comply with the Construction
Products Regulation (EU) No. 305/2011. For Declaration of Performance,
please go to www.velux.com.
VELUX A/S: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(Jens Aksel Thomsen, Test Engineer, Market Approval)
Ådalsvej 99, DK-2970 Hørsholm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CE DoC 940402-02
11-11-2019

VELUX®7

8 VELUX®
9 10 11
x 10
EXTRACTOR DE HUMOR
RØGLEM
ROO
SMOKE VENT
ABV-CENTRAL
ESCAP
3
2
1
x 4
7
8
4
5
6
1Control unit for smoke ventila-
tion KFC 210 or KFC 220 – see
type designation in the control
unit.
2Frame with instructions
3Keys, rubber bushes, screws
and cable ties
4Labels
5Back-up batteries
6Battery holder
7Cables for batteries
8Blank lid
9Break-glass point
KFK 100-104*)
10 Smoke detector KFA 100*)
11 Coloured frame*)
*) Is delivered depending on type
of control system.
Contents of packaging

VELUX®9
1
ON
23456
Keep the instructions behind the battery holder in the control unit.
Stick the supplied label "SMOKE VENTILATION" onto the indicated area
on the control unit.

10 VELUX®
2132541
LINK
DET.21DET.21
NL
NL
PENL
230V
230V
ALARMMOTOR 2MOTOR 1230V/50Hz
24V
H I
M M
230 V
50 Hz
BA C
AMains connection 19
BMotor 1 14-15
CMotor 2 14-15
DSmoke detector 11
ERain sensor 12
FVentilation switch 13, 25
GBreak-glass point 10
HAlarm signals 23-24, 27-28
ILink 24
JRain signal - output 26
Overview of printed circuit board
Other manuals for KFX 210
1
This manual suits for next models
23
Table of contents
Other Velux Control System manuals

Velux
Velux KFX 210 User manual

Velux
Velux KFX 100 User manual

Velux
Velux WUX 101 User manual

Velux
Velux KLR 300 User manual

Velux
Velux KUX 100 User manual

Velux
Velux KUX 100 User manual

Velux
Velux Integra Kux 110 User manual

Velux
Velux ACTIVE KIX 300 User manual

Velux
Velux Integra Kux 110 User manual

Velux
Velux Vario User manual