Turbovex TX 250A User manual

Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 - email: [email protected]k
www.turbovex.com
Installation, Operation and
Maintenance Manual
TX 250A
TX 500A
TX 750A
TX 1000A
Rev. 2023.10.23

Page 2 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
1.0 Table of contents
1.0 Table of contents ....................................................................................... 2
2.0 General information .................................................................................. 3
2.1 Introduction..........................................................................................................................3
2.2 Fields of application .............................................................................................................3
2.3 Misuse ..................................................................................................................................3
2.4 Contents of delivery .............................................................................................................3
2.5 Operating principle...............................................................................................................4
2.6 Main components: ...............................................................................................................5
3.0 Installation................................................................................................. 6
3.1 Dimensions ...........................................................................................................................6
3.2 Placement.............................................................................................................................7
3.3 Minimum distance................................................................................................................9
3.4 Wall- or ceiling mounted unit ............................................................................................10
4.0 Connection............................................................................................... 16
4.1 Water connection...............................................................................................................16
4.2 Frost protection of water heating coil ...............................................................................16
4.3 Power connection ..............................................................................................................18
4.4 Power connection for accessories .....................................................................................19
5.0 Technical specifications............................................................................ 20
6.0 Operation ................................................................................................ 21
6.1 Regulation of airflow..........................................................................................................21
6.2 Heat regulation...................................................................................................................21
6.3 Master / slave.....................................................................................................................21
7.0 Service ..................................................................................................... 22
7.1 Change of filter...................................................................................................................22
7.2 Cleaning of heat exchanger................................................................................................23
8.0 Declaration of conformity........................................................................ 24

Page 3 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
2.0 General information
2.1 Introduction
This user manual contains technical information about installation, operation and
maintenance of the unit.
2.2 Fields of application
TX Comfort is designed for comfort ventilation in institutions, offices, dining spaces,
conference rooms and indoor spaces occupied by people.
2.3 Misuse
TX Comfort is designed for the living spaces described above in section 3.2.0. The system
is not designed for the purpose of local exhaust ventilation.
2.4 Contents of delivery
The TX Comfort unit is delivered with the following main components:
1.
Turbovex TX Comfort unit
2.
Suspension bracket
3.
TX electronic controller
1
.
2
.
3
.

Page 4 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
2.5 Operating principle
Turbovex TX Comfort is a decentralized ventilation system with built-in heat recovery for
ventilation of comfort rooms in particular in indoor living spaces.
TX Comfort operates with an aluminium counter flow heat exchanger (5) to ensure maximum
heat recovery. The unit utilizes warm indoor air to heat up inflowing fresh outdoor air. The
counter flow heat exchanger’s sole function is for heat retention.
Airflow:
The air supply ventilator (6) (Figure 2) creates inflow of fresh outdoor air through the filter
(10), leading the inflow through the heat exchanger (5), and further through the air supply
grate (4) and out into the room.
At the same time the air exhaust ventilator (7) creates outflow of indoor air leading it through
the exhaust pipe (2) and further out to the open air outside.
The desired temperature of the air supply is regulated on the control panel. A sensor records
the actual temperature of the flowing air supply. If the temperature is lower than the setpoint,
the control system reduces the flow of the air supply warming it as it flows through the heat
exchanger.

Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 - email: [email protected]k
www.turbovex.com
2.6 Main components:

Page 6 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
3.0 Installation
3.1 Dimensions
Dimension [mm]
TX 250A
TX 500A
TX 750A
TX 1000
A
595
828
895
1050
B
403
493
565
665
C
500
710
766
917
D
313
382
442
542
E
1156
1506
1767
2067
F
1141
1491
1750
2050
G
1200
1550
1800
2100
H
906
1156
1355
1630
I
135
189
210
235
J
160
205
235
235
K
137
187
203
253
L
280
350
390
465
M
185
245
280
310

Page 7 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
3.2 Placement
The unit is generally placed on a wall directly under the ceiling. This location best exploits
the coanda effect as it leads the air further into the room along the surface of the ceiling. In
this way inflowing air can mix with the room’s existing air for a longer period of time and
thereby prevent draught. This location, as the point for supply and exhaust airflow, provides
optimal circulation within a room.
Standard placement
The TX Comfort series also has the possibility of locating the unit in false ceilings. In this
way, the unit is less visible.
Installation in false ceiling

Page 8 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
The TX Comfort series offer the possibility of installing ducts through the wall or the roof.
Fresh air can also flow in through a wall duct while exhaust air flows out through the roof.
This results in optimal conditions in comparison to a set up with close proximity between
the air supply and the air exhaust.

Page 9 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: info@turbovex.dk –
www.turbovex.com
3.3 Minimum distance
Minimum allowed distance between the unit and walls, cupboards or other surfaces.
It is important to check that there is sufficient space for the sides of the unit to be fully opened
during installation. The minimum distance must be the length L as indicated in the illustration
above.
Dimension(mm)
TX 250A
TX 500A
TX 750A
TX 1000A
E
1156
1506
1767
2067
L
600
850
950
1100

Page 10 of 24
Turbovex A/S
Industrivej 45, DK – 9600 Aars
Telefon: +45 96 98 14 62 – email: [email protected]k –
www.turbovex.com
3.4 Wall- or ceiling mounted unit
When the unit is wall- or ceiling mounted, the required outward free space from the centre
of each of the two ducts must be the distance M
The location of the suspension bracket and the measurements for mounting the bracket are
indicated in the illustrations below.
Dimension[mm]
TX 250A
TX 500A
TX 750A
TX 1000A
M
142
192
209
259
N
906
1156
1355
1630
O
137
187
218
218
P
112
162
193
218
Q
137
187
203
253
The location of the unit in relation to the ducts (Please note that the unit is viewed from the
rear in the figure below).
Wall-mounted with wall ducts
Ceiling-mounted with ceiling ducts
Other manuals for TX 250A
1
This manual suits for next models
3
Table of contents
Other Turbovex Fan manuals
Popular Fan manuals by other brands

ELTA FANS
ELTA FANS H03VV-F installation guide

Hunter
Hunter 20714 Owner's guide and installation manual

Emerson
Emerson CARRERA VERANDA CF542ORB00 owner's manual

Hunter
Hunter Caraway Owner's guide and installation manual

Panasonic
Panasonic FV-15NLFS1 Service manual

Kompernass
Kompernass KH 1150 operating instructions