Slycma ARIANE 3.1 Quick start guide

Ref : 26702 1 07/01/15
LINEAR OPERATOR CARD
ARIANE 3.1
180W Asynchronous – Brushless Motors
COMMISSIONING MANUAL
Parc d’Activités Lyon Sud Ouest – 4 route du Dôme – F - 69630 CHAPONOST
Tel : (0033) 04 78 86 81 00 / Fax : (0033) 04 78 86 81 08

Ref : 26702 2 07/01/15
!! DISCLAIMERS !!
Your ARIANE 3.1 operator card was pre-adjusted in the factory.
After wiring according to the electrical schematic diagram attached to the
manual’s backpage, switch on the card. Then simply proceed with:
- its configuration with respect to the controller (direction of the limit
switches signals, shock, master or slave mode, car cell management by
the card, etc.),
- the learning of the travel (CMD1 mode) with an associated landing door
- the adjustment of the test door operating parameters (speeds,
slowdowns, torques, closing and opening sensitivities) with the commands
CMD3, 5 and 7,
The card has many parameters to allow it to adapt to all renovation
solutions, but it is not necessary to intervene on all these values. The
factory parameter setting allows an immediate correct operation of the
door.
A few particularities :
-Driving the Asynchronous or Brushless motor
The ARIANE 3.1 card allows driving both of these types of motors with a 230V voltage
and a 180W maximum power rating.
-Taking into account the Inspection mode
Inspection signal input to be mandatorily wired to prohibit automatic door movements
during technical services.
-Managing glazed doors (VITR and DURF parameters)
This option controls finger jammings when the door opens.
Standard EN81 – 1/2 articles 7.2.36 and 8.6.7.5
-Master 2 mode
The door opens when the cell beam is passed through and closes when the cell beam
is no longer hidden.
-Necessity of connecting the Close limit switch signal
As long as the close limit switch signal is not given, the door can re-open in case of a
skate closing problem. Therefore, the controller must wait for this signal to move the
car.
.
-Driving the auxiliary functions
Two programmable relays allow triggering a buzzer, an electro-cam, an electromagnetic
suction disc or an intermediate end stop.

Ref : 26702 3 07/01/15
ARIANE 3 OPERATING GUIDE
When the card is switched on, it executes the controller orders.
To intervene on ARIANE, you may choose from among 3 display modes, a
parameter setting mode and a manual commands mode :
Scroll the menu by successively pressing the key and make your
choice by pressing the key (If you do not validate within 3 seconds,
the default value "Fr00" is displayed).
Display modes:
- "Fr00" →display of the motor output frequency (Hz)
- "0000" →display of the position (encoder points)
- " _ _ " →display of the card Input / Output state
Parameter setting mode : - PARA →Changing the parameters
In the PARA mode, you can access all the door configuration
parameters and operating values.
Scroll the configuration parameters : successively press
Scroll the operating values : successively press
To read the value, press
To change the value, press or
To save the new value, press
To quit the mode, simultaneously press and
.
Manual commands mode : - CMD Commands CMD1 to CMD8
In the CMD mode (CMD for command), you can operate the door
independently from the controller orders
Scroll the commands mode : successively press or
To select a command, press (the display flashes)
To quit the mode, press

Ref : 26702 4 07/01/15
CONTENTS
PART 1 : Connection of the ARIANE 3.1 card
Mains power connection ........................................................... Page 5
Asynchronous motor connection ............................................... Page 5
Brushless motor connection ..................................................... Page 5
Encoder connection ................................................................. Page 6
Safety chain connection ........................................................... Page 6
Controller orders connection...................................................... Page 6
Car input cell connection .......................................................... Page 7
Controller signals connection .................................................... Page 7
Multifunction relay connection .................................................. Page 8
Wire function terminals list ...................................................... Page 8
PART 2 : Configuration according to the controller
Setting of mandatory parameters .............................................. Page 9
Details about the configuration parameters ...............................Page 10
PART 3 : Commissioning the ARIANE 3.1 card
Mechanical efficiency checking .................................................Page 13
Travel learning ......................................................................Page 13
PART 4 : Adjustment of the door operation
Operating diagrams ...............................................................Page 14
Changing a parameter ............................................................Page 14
Operating values ................................................................... Page 15
Value range table ..................................................................Page 16
PART 5 : Saving the parameters
Saving the parameters ...........................................................Page 17
Recording your own parameters ...............................................Page 18
PART 6 : Details about the command modes (CMD)
The command modes (CMD) ...................................................Page 19
Special case of a double opening travel .....................................Page 20
PART 7 : Details about the ARIANE 3.1 operations
Basic operation .................................................................... Page 21
Reset operation .....................................................................Page 22
Inspection operation ..............................................................Page 22
Parameterizable relays operation ..............................................Page 23
Fail soft operation ..................................................................Page 24
Operation with Car door locking device .....................................Page 24
Energy save operation ............................................................Page 24
PART 8 : Maintenance operations
Card Inputs/Outputs display ....................................................Page 25
Operating faults display ..........................................................Page 26
Details about operating faults ..................................................Page 27
Encoder position display .........................................................Page 28
Numbers of cycles display .......................................................Page 28

Ref : 26702 5 07/01/15
Part 1 : The Ariane 3 card connections
The card efficiency is first subjected to a mechanical
setting in conformity with the door.
Necessary connectors are supplied in a bag.
MAINS POWER CONNECTION – 3x7.62 – 230V 50Hz – 2A connector
The 230 V power supply must not come
from the primary of a 110/230/400V
transformer because a damaging
overvoltage can occur if the transformer
is not loaded.
The connector must not be handled with power switched on
If the voltage between neutral and ground is very different from 0 volts,
power the card via an insulating transformer (example : case of connection
in TI state).
ASYNCHRONOUS MOTOR CONNECTION : 4x minifit (made in
factory)
Make sure that the motor cable shielding
is properly connected to the Ariane card
package.
Make sure that the motor’s ground is
connected to the connector (EMC
requirement).
BRUSHLESS MOTOR CONNECTION : 4x motor minifit and 6x hall
effect sensors microfit (made in factory)
Make sure that the motor cable shielding is
properly connected to the package and that
the 3 phase wires are properly installed on
the minifit connector.
Make sure that the 6x hall effect sensors microfit
connector of the Brushless motor is properly
connected to the right side of the ARIANE body.

Ref : 26702 6 07/01/15
ENCODER CONNECTION – 4x microfit connector (made in factory)
For an Asynchronous motor
Connection of the counting cells.
Make sure that the encoder’s 6 wires are
properly connected, that the crimpings are in
good condition, and that the wire is
immobilized
For a Brushless motor
Connection of the encoder integrated with the
motor
Make sure that the 4 wires are crimped
correctly and that the cable is immobilized
SAFETY CHAIN CONNECTION – 2 x 5.08 connector
Connect the safety chain to the 2 x 5.08 connector. Check
the factory wiring of the door contacts on the 4 x 5.08
connector is conformity with the electrical drawing regarding
there is one or two contacts. (One in lateral opening, 2 in
central opening)
There is no interaction between the card’s operation and the
safety contacts.
CONTROLLER COMMANDS CONNECTION – 6 x 5.08 connector
All the orders must come from dry contacts which switch
the 0V common supplied by the card.
It is not necessary to apply voltages to these inputs.
Warning : When an operator driven by contactors is
replaced, do not use the old contactors flakes as
command contacts, but use relays which switch low
currents (20 mA at 12 VDC).

Ref : 26702 7 07/01/15
The required standards are the open order, the close order and the inspection
information signal.
If only the close order is available, the open order must
be bypassed. The close and nudging orders have priority
over the open order.
The inspection connection is mandatory
to inhibit any untimely door movement
during a technical service. (Standard
EN81 – 1/2 article 14.2.1.3 a)
CAR CELL CONNECTION – 3 x 5.08 connector
If the car cell is controlled by the card, a NC (normally closed) dry
contact must be connected between the card’s OV common and
the Cell information signal input.
This input may also be used for a ’ReOpening pushbutton in the
carequipped with a NC contact. It may be connected in series
with the cabin cell’s NC signal input.
If necessary for the cell, a +12V power supply is provided.
The use of this input is conditioned by the CELLand MODE
parameters.
CONTROLLER SIGNALS CONNECTION – 6 x 5.08 connector
Connect the Limit switch and Shock signal returns to
the controller.
These signals are dry contact relay outputs which
require minimum switching currents of 10mA.
The direction of the NO (normally open) or NC
(normally closed) limit switches is selected with the
FDC(Limit switch) parameter.
The shock signal also restores the car cell signal if
the car cell is connected to the card.
The direction of the NO or NC Shock signal is
selected by the CHOC(SHOCK) parameter.
Warning : the closing limit switch connection is mandatory so that
the car starts moving only when the close cycle is totally complete
(skate closed, for example) and not as soon as the door contact
closes.

Ref : 26702 8 07/01/15
MULTIFUNCTION RELAY CONNECTION – 4 x 5.08 connector
Two programmable commands may be
connected to the RMF1 and RMF2 outputs, which
are two dry contact relays.
The driven device type is selected with the
RMF1and RMF2parameters, namely :
- A buzzer, which will be activated during the
learning, reset, nudging and fail soft operation.
- An electromagnetic suction disc, which will keep
the door panels closed
- An electro-cam, which will unlock swinging
doors or articulated sliding doors
- An electromagnetic intermediate open end stop
External power supplies must be provided for the
devices
The maximum interrupting capacity of the relays is
6A for 250 VDC and 15A for 400 VAC
WIRE FUNCTION ASSIGNMENTS LIST

Ref : 26702 9 07/01/15
Terminal n° Assignment
Ph, N, T Mains power supply
L1, L2, L3, T Motor connection
5, 6 Safety chain connection
7, 8, 9, 10 Door contacts connection
14, 15 Shock signal
16, 17 Closing limit switch stop signal
18, 19 Opening limit switch stop signal
25 + 12 VDC
26, 27 NC (normally closed) Cell input
28 Inspection NO (normally opened) command input
29 Nudging NO Command input (forced closing)
30 Closing NO command input
31 Intermediate Opening NO command input
32 Complete opening NO command input
33 Common 0V of the commands
PART 2 : Configuration according to the controller
Scroll the menus by successively pressing ,
and select PARAby pressing .
Scroll the parameters with
To read the value, press
To change the value, press
To save the new value, press
SETTING OF THE MANDATORY PARAMETERS
Display order of the parameters :
→MSTF Hold under voltage closing OUI(YES) /NON(NO)/DEPL Set in Factory
→MSTO Hold under voltage opening OUI (YES)/NON(NO) Set in Factory
→MODE Operating mode : ESCL/MAI1/MAI2
→CHOC Shock contact direction / Controller : NO or NF
→FdC Limit switch contact direction / Controller : NO or NF
→SMOT Motor rotating direction DIR/INV Set in Factory

Ref : 26702 10 07/01/15
→VITR Glazing option OUI/NON Set in Factory
→CELL Cell management : NON/OUI/LIMI
→TYPE Door type: Mobile (MOBI), Swinging (BATT), Fixed (FI) Set in Factory
MOBI or FI are the type of skate on automatic doors
→rMF2 MULTIFUNCTION RELAY 2 : buZZ/butE/Vent/CAME
→rMF1 MULTIFUNCTION RELAY 1 : buZZ/butE/Vent/CAME
→PINI Factory parameters INI, SAVE, IN01, ..., IN30 Set in Factory
→CYCL No. of cycles performed x 1000 Information
→ERR Last 10 recorded errors, Errx/EFFA Information
→MOTR ASYN/BRUS motor type selection Set in Factory
→BAUD CAN parameter Not used
→PRTE CAN parameter Not used
END of CONFIGURATION
To exit the parametersmenu, simultaneously press and .
If the card has never been started, it displays APPr
Table of contents