CBS2000 – ING
3
INSTRUCTION FOR INSTALLATION
1) Connect Mains Voltage to input terminal: (0 - 230 -400 Vac) of battery charger.
2) Connect the "POSITIVE BATTERY" output directly to positive battery terminal.
3) Connect the "NEGATIVE BATTERY" output directly to negative battery terminal.
Use cable with minimum 2,5 smmq section.
INSTRUCTION FOR SETTING
The battery charger is supplied set for charging lead batteries at a level of 2,18V for element,
in automatic charger.
AUTOMATIC CHARGER (2,18 V / ELEMENT)
If this value is not extractly what is needed, proceed as follows:
1) Connect positive and negative battery tarminals to the battery charger.
2) Connect a multimeter to battery charger’s output terminals:
it should indicate a DC voltage around 13V for a 12V device around 26,2V for a 24V battery
charger (rated values).