senva C-2330 User manual

WIRING EXAMPLES
INSTALLATION INSTRUCTIONS
senvainc.com 1-866-660-8864 (F)1-503-296-2529 9290 SW Nimbus Ave. Beaverton Oregon 97008
C-2330, Auto-Calibrating
Mini Split-Core Digital
Output
Failure to follow these instructions will result in
death or serious injury.
• Follow ALL requirements in NFPA 70E for safe work practices
and for Personal Protective Equipment (USA) and other appli-
cable local codes when installing this product
• Only qualied electrical personnel should install this product.
• Read, understand, and follow all instructions thoroughly
• Install only on insulated conductors
• Lock out and tag out all power sources prior to installation.
Use properly rated voltage sensing instrument to determine
no voltage is present
Failure to follow these instructions could result in
death or serious injury.
• Equipment monitored/operated by this device may start
without warning. Keep clear of apparatus at all times
IMPORTANT WARNINGS
• Only qualied trade installers should install this product
• This product is not intended for life-safety applications
• Do not install in hazardous or classied locations
• The installer is responsible for all applicable codes
• Thisproductmustbeinstalledinasuitableelectricalenclosure
Automated equipment may
start without warning
DANGER
WARNING
!
Hazard of electrical shock, explosion,
and arc flash
DANGER
WARNING
!
PRODUCT APPLICATION LIMITATION:
Senva products are not designed for life or safety applications. Senva products
are not intended for use in critical applications such as nuclear facilities, human
implantable device or life support. Senva is not liable, in whole or in part, for
any claims or damages arising from such uses.
CALIBRATION
1. No calibration is necessary for normal applications. Sensor
will automatically learn motor run current and adjust threshold
as needed.
2. To manually re-calibrate sensor, press and hold button for 1
second. LED will blink twice. Sensor will discontinue automati-
cally threshold adjustment.
3. To set sensor to go/no mode, press and hold button for 5
seconds. LED will blink 3 times.
INSTALLATION
1. Determine mounting location for the sensor near the
conductor to be monitored. The sensor should be located AT
LEAST 1/2” from any uninsulated conductor.
2. Sensor features a exible iris which allows the sensor to
hang on the conductor if local codes permit. A bracket is
included for screw mounting or attaching to DIN rail. For screw
mounting, drill two 3/32”pilot holes using the bracket as a
template; ensure no drill shavings are present in enclosure. At-
tach bracket with screws provided.
3. Clamp sensor around INSULATED CONDUCTOR ONLY,
600VAC MAX to be monitored.
4. Snap the sensor into the mounting bracket.
5. Wire the output of the sensor to a control panel digital
input loop not to exceed 30VAC/DC wetting voltage. Tighten
terminals to 3.5 in-lb.
Disconnect, lock out and tag out all
power supplies during installation
V+
DI
CONTROLLER
(SINKING)
(SOURCING) (AC)
INSULATED PRIMARY
AC CONDUCTOR
600VAC MAX
V+
DI
24VAC
DI
V+
DI
ALTERNATE
CONTROLLER ARRANGEMENTS
DI
DI VAC
GND
NOTE: Device is NOT polarity sensitive.
v
Status Output
0.5A @ 30VAC/DC
Normally Open
Fast learn mode:
Press/hold 1 sec
LED 2 fast blinks
Go/No mode:
Press/hold 5 sec
LED 3 fast blinks
Slow blink
Normal
Fast blink
Alarm
Optional Manual Setup:
3PZS
Not for use on variable speed drives.
Use C-2350-VFD for VFD applications.

TECH TIPS
On low current loads, wrap sensor multiple
times to increase sensitivity
CAUTION: Do not exceed sensor
maximum current. The current
detected by the sensor will
increase 1X with each wrap.
To monitor loads greater than the current sensor
maximum rating
Use of 5A CT is NOT recommended. Consult factory for
extended range version.
Part Number
C-2330
Amperage Range
2.5A (on)
~135A (200A Max.)
Output Type
NO, solid-state FET
Output Rating 1.0A@30VAC/DC Max.
Temperature Rating
-15
~60 ° C
Insulation Class 600V RMS. For use on insulated conductors only!
Use minimum 75 ° C insulated conductor
Sensor Power
Induced
Frequency Range
50/60Hz
Dimensions ( LxWxH)
2.51” x 2.23”x 0.82” (1.4” H with optional relay module)
Sensor Aperture
0.75”
OPERATION
The C-2330 output is closed whenever motor run current exceeds
learned setpoint. Setpoint adjusts automatically over time to compen-
sate for load changes caused by air balancing and other small changes
in normal run current.
Typical load status applications include:
zProof of ow
zBelt-loss detection
zCoupling shear
zContactor/Starter failure
DIMENSIONS
Troubleshooting
Symptom
Causes Remedy
Sensor output does
not change state
Amperage is below sensor
minimum threshold
Wrap monitored conductor
turns through sensor. See
Tech Tips
Testing with ohm meter
yields incorrect results
Output cannot be tested
with ohm meter
Incorrect control wiring Ensure control loop voltage
is present
Sensor reports “false”
alarms.
Sensor may be installed
on VFD. Use C-2350-VFD
2.23
2.50
2.12
O.18
.57
.82
Fan
Load “OFF”
Sensor
Output
Sensor
“RUN”
Air Balancing
(OA)
Output Energized
Auto-calibration
Sensor Recalibration
Belt Loss
Setpoint Maximum surrounding air ambient, 60 ° C.
For use in Pollution Degree 2 Environment.
152-0230-0A