WORK DISPLAY OPTIONS
COMBUSTIBLE GAS SCALE AND RESOLUTION
The combustible gas reading will be automatically displayed in one of three scales on the SENSIT
GOLD G3: PPM, %LEL, and/or %VOL. By default, the reading starts in the %LEL scale (from 0.0%LEL)
and will automatically switch to %VOL at ≥100%LEL (equal to 5.0%VOL by default, see the section on
LEL Definition), if equipped with a TC sensor.
If the %LEL option is disabled, the G3 will display in %VOL through the entire scale (either up to 5%VOL
if the TC sensor is not equipped, or up to 100%VOL if equipped).
If the PPM option is enabled, the G3 will instead start at 0ppm, and automatically scale to either %LEL
(if enabled) or %VOL at the specified upper limit. By default, this is 2,000ppm. Other options are
5,000ppm, 10,000ppm, or 50,000ppm. If set to 50,000ppm, the G3 will not scale to %LEL even if it
is enabled, because at the highest LEL Definition, 50,000ppm is equal to 100%LEL.
In addition, the display resolution for the PPM and %LEL scales are customizable. The default display
resolutions and options for each scale, while on the work display, are listed below.
DEFAULT RESOLUTION
PPM Disabled 1ppm or 10ppm
%LEL 0.1%LEL 0.1% - 2.0%LEL
[0.1% increments]
%VOL (FOR TC UNITS) <5.0%VOL: 0.01%VOL
≥5.0%VOL: 0.1%VOL
Not adjustable
%VOL (FOR NON-TC UNITS) Disabled
H2S RESOLUTION
If the SENSIT GOLD G3 is equipped with a hydrogen sulfide (H2S) sensor, it will have a resolution of
1ppm by default (0-100PPM range). There is an optional Expert Menu adjustment for this to increase
the resolution to 0.1ppm.
HCN RESOLUTION
If the SENSIT GOLD G3 is equipped with a hydrogen cyanide (HCN) sensor, it will have a resolution of
0.1ppm by default (0-30ppm range). There is an optional Expert Menu adjustment for this to decrease
the resolution to 1ppm.
LEL DEFINITION
By default, the SENSIT GOLD G3 defines the lower explosive limit (LEL) as 5.0%VOL methane and
2.2%VOL propane. This is factory adjustable between 4.0% and 5.0% for methane and 1.8% and
2.2% for propane, in 0.1% increments,
based on company or industry
requirements. This will affect how the
instrument displays the %LEL scale.
For example, if the LEL definition is
4.0%VOL, 2.5%VOL methane will
display as 62.5%LEL. Reference the
methane/natural gas chart below.