1. Introduction
This manual covers the following detectors:
DMP-100 - conventional multisensor smoke and heat detector (Fig. 1);
DRP-100 - conventional optical smoke detector (Fig. 2);
DCP-100 - conventional fixed temperature / rate-of-rise heat detector (Fig. 1 – a red ring is
painted on the enclosure of detector to differentiate it from the DMP-100).
These detectors can detect the early stages of fire development when there is some visible
smoke (DMP-100 and DRP-100) and/or temperature rise (DMP-100 and DCP-100). They are
designed to be used in conjunction with the CSP-104, CSP-108, CSP-204 and CSP-208 fire
alarm control panels.
Prior to installation, please read this manual carefully in order to avoid any mistakes and/or
errors which might result in malfunctioning of or even damage to the equipment. The manual
contains guidelines for installation of the detectors.
2. Features
EN54-7 compliant visible smoke sensor (DMP-100 and DRP-100).
EN54-5 compliant heat sensor (DMP-100 and DCP-100).
Detection of optical chamber fouling (DMP-100 and DRP-100).
Red LED indicator.
Installation in DB-100 base.
Optional connection of remote alarm indicator.
3. Functional description
3.1 Smoke detection (DMP-100 and DRP-100)
An optical method is used for the detection of visible smoke. When the concentration of
smoke in the optical chamber exceeds a given threshold, an alarm is triggered. The detector
automatically compensates for gradual changes in the optical chamber caused by deposition
of dust. In the case of DMP-100 multisensor detector, the smoke sensor operating
parameters are adjusted according to the temperature changes recorded by the heat sensor
(thermistor).
3.2 Heat detection (DMP-100 and DCP-100)
The heat sensor operates according to the requirements of Class A1R (EN 54-5). The alarm
will be triggered after exceeding a certain threshold temperature (54°C - 65°C) or in the event
when the temperature rises too rapidly (see Table 1).

2 DMP-100 ●DRP-100 ●DCP-100 SATEL
Rate of rise of air
temperature Lower limit of response
time Upper limit of response
time
1 °C/min 29 min 40 min 20 s
3 °C/min 7 min 13 s 13 min 40 s
5 °C/min 4 min 9 s 8 min 20 s
10 °C/min 1 min 4 min 20 s
20 °C/min 30 s 2 min 20 s
30 °C/min 20 s 1 min 40 s
Table 1. Rate-of-rise response time limits for the heat sensor
3.3 Optical alarm signaling
The alarm is signaled by steady light of the red LED, thus making it easier to locate the
detector which issued the alarm. If the detector is mounted in a hard-to-reach location and
the LED is not visible, a remote alarm indicator installed in a visible place can be connected
to the detector.
4. Installation
The detectors are designed for indoor installation. In the typical home or office applications,
the detector should be installed on the ceiling, at a distance of at least 0.5 meters from the
walls or other objects.
Do not install the detector in places with high concentration of dust, with
formation and condensation of water steam and/or in the vicinity of air
conditioning vents.
The detector should not be installed near heaters and cookers.
The detector is designed for installation in the DB-100 base, to which cables are connected.
Having installed the detector into its base, protect it temporarily with the plastic dust cover
included in the detector delivery set, if any work which might cause fouling of the detector is
being carried out in the building.
Note: It is advisable to keep the dust cover in case repair work is conducted in the future.
5. Maintenance
The detectors should be subject to regular checks to ensure they are working correctly.
Periodic checks should be conducted at least every six months.
5.1 Cleaning the optical chamber
The DMP-100 and DRP-100 detectors are monitoring the state of the optical chamber.
Deposition of dust in it may lead to malfunctioning of the device. It is recommended that you
have the optical chamber cleaned at least once a year. Cleaning the chamber is necessary
when the LED indicates fouling of the chamber (one flash every 30 seconds).
Below, the procedure of cleaning the DMP-100 optical detector is described. For the
DRP-100 detector, in which no thermistor is installed, proceed in the same way, skipping the
steps 3, 4, 8 and 9.
1. Turn the detector counter-clockwise (Fig. 3) and remove it from the DB-100 base (Fig. 4).
2. Push outward the catches (Fig. 5) and take out the electronics board with the optical
chamber (Fig. 6).
3. Remove the thermistor cover (Fig. 7).

SATEL DMP-100 ●DRP-100 ●DCP-100 3
4. Push aside the thermistor and its wires (Fig. 8).
5. Push outward the catch securing the optical chamber cover (Fig. 9) and remove it
(Fig. 10).
6. Using a soft brush or compressed air, clean the labyrinth in the cover, as well as the base
of the optical chamber, paying attention to the recesses where LEDs are installed.
7. Replace the cover of the optical chamber.
8. Place the thermistor leads in their grooves.
9. Replace the thermistor cover.

4 DMP-100 ●DRP-100 ●DCP-100 SATEL
10.Secure the electronics board with the optical chamber in the cover mounting catches. The
board must be mounted so that the LED coincides with the light guide.
11.Insert the detector into the DB-100 base and turn it clockwise.
6. Specifications
Supply voltage ................................................................................................... 10.5...26 V DC
Quiescent current DMP-100 .......................................................0.04 mA
DRP-100........................................................0.03 mA
DCP-100......................................................0.022 mA
Alarm current DMP-100 ..........................................................23 mA
DRP-100...........................................................23 mA
DCP-100...........................................................23 mA
Class according to EN 54-5 (heat sensor) ..........................................................................A1R
Minimum static response temperature ..............................................................................54 °C
Maximum static response temperature .............................................................................65 °C
Operating temperature range..................................................................................-25...+50 °C
Maximum humidity ..........................................................................................................93±3%
Enclosure dimensions DMP-100 / DCP-100............................ ø108 x 49 mm
DRP-100 .............................................. ø108 x 42 mm
Weight DMP-100 .............................................................94 g
DRP-100.............................................................. 94 g
DCP-100.............................................................. 94 g

SATEL DMP-100 ●DRP-100 ●DCP-100 5
The DCP-100 heat detector meets essential requirements of the European Union Directives:
CPD 89/106/EEC Construction Products Directive;
EMC 2004/108/EC Electromagnetic Compatibility Directive;
An EC Certificate of Conformity No. 1438/CPD/0316 was issued by the CNBOP-PIB Jozefow
Certification Body for the DCP-100 heat detector to confirm its compliance with the
requirements of PN-EN 54-5:2003 standard.
The Certificate of Conformity can be downloaded from the www.satel.eu website.
14
38
SATEL Sp. z o.o. • ul. Franciszka Schuberta 79 • 80-172 Gdańsk • POLAND
13
1438/CPD/0316
EN 54-5
DCP-100 conventional, detachable, spot type heat detector for fire alarm systems
used in buildings.
Class A1R
Application – fire safety.
Technical specifications – please refer to this manual.
The DRP-100 smoke detector meets essential requirements of the European Union
Directives:
CPD 89/106/EEC Construction Products Directive;
EMC 2004/108/EC Electromagnetic Compatibility Directive;
An EC Certificate of Conformity No. 1438/CPD/0340 was issued by the CNBOP-PIB Jozefow
Certification Body for the DRP-100 smoke detector to confirm its compliance with the
requirements of PN-EN 54-7:2004 + PN-EN 54-7:2004/A2:2009 standards.
The Certificate of Conformity can be downloaded from the www.satel.eu website.
14
38
SATEL Sp. z o.o. • ul. Franciszka Schuberta 79 • 80-172 Gdańsk • POLAND
13
1438/CPD/0340
EN 54-7
DRP-100 conventional spot type optical smoke detector, operating on light scattering
principle, for fire alarm systems used in buildings.
Application – fire safety.
Technical specifications – please refer to this manual.

6 DMP-100 ●DRP-100 ●DCP-100 SATEL
The DMP-100 smoke and heat detector meets essential requirements of the European Union
Directives:
CPD 89/106/EEC Construction Products Directive;
EMC 2004/108/EC Electromagnetic Compatibility Directive;
An EC Certificate of Conformity No. 1438/CPD/0341 was issued by the CNBOP-PIB Jozefow
Certification Body for the DMP-100 smoke and heat detector to confirm its compliance with
the requirements of PN-EN 54-5:2003 and PN-EN 54-7:2004 + PN-EN 54-7:2004/A2:2009
standards.
The Certificate of Conformity can be downloaded from the www.satel.eu website.
14
38
SATEL Sp. z o.o. • ul. Franciszka Schuberta 79 • 80-172 Gdańsk • POLAND
13
1438/CPD/0341
EN 54-5
EN 54-7
DMP-100 conventional spot type multisensor heat and smoke detector, operating on
light scattering principle, fixed temperature / rate-of-rise, for fire alarm systems used
in buildings.
Class A1R
Application – fire safety.
Technical specifications – please refer to this manual.
This manual suits for next models
2
Table of contents
Other Satel Security Sensor manuals

Satel
Satel abax 2 ADD-200 User manual

Satel
Satel ARD-100 User manual

Satel
Satel AGD-100 User manual

Satel
Satel AQUA LUNA User manual

Satel
Satel SLIM-DUAL-PRO User manual

Satel
Satel AQUA RING S User manual

Satel
Satel MAGENTA User manual

Satel
Satel GRAPHITE User manual

Satel
Satel AQUA S User manual

Satel
Satel AGD-100 User manual

Satel
Satel AFD-100 User manual

Satel
Satel OPAL User manual

Satel
Satel micra MXD-300 User manual

Satel
Satel AQUA PET User manual

Satel
Satel GREY User manual

Satel
Satel ASD-100 User manual

Satel
Satel IVORY User manual

Satel
Satel AVD-100 User manual

Satel
Satel XD-2 User manual

Satel
Satel ABAX 2 APD-200 User manual