Rf-t AVANTAGE DP Series User manual

www.rft.be
en
RF-Technologies , 9860 Oosterzele, Belgium. [email protected] . Distributed in the UK and Ireland by: Smoke Control Dampers Ltd.
6 Avon Gorge Industrial Estate, Avonmouth, Bristol, BS11 9LQ. T:+44 (0) 117 938 1666. [email protected]
AVANTAGE DP
Motorised dual purpose CE marked AOV for protected
lobby to shaft ventilation.

2Table of content
Table of content
Declaration of performance 3
Product presentation AVANTAGE DP 4
Range and dimensions AVANTAGE DP 1V60/1V120 4
Evolution - kits 5
Options - at the time of order 5
Storage and handling 6
Installation 6
Operation and mechanisms 10
Electrical connection 10
Weights 11
Selection graphs 12
Selection data 14
Approvals and certificates 14
Explanation of the abbreviations and pictograms
Wn = nominal width
Hn = nominal height
Sn = free air passage
E = integrity
I = thermal insulation
S = smoke leakage
60/120 = fire resistance time
Pa = pascal
o -> i = meets the criteria from the outside
(o) to the inside (i)
i <-> o = fire side not important
AA = automatic activation
multi = multiple
1500 = pressure level 3 (1500Pa)
ved = vertical duct
hod = horizontal duct
V = volt
W = watt
V AC = Volt alternating current
V DC = Volt direct current
E.ALIM = power supply magnet
E.TELE = power supply motor
Auto = automatic
Tele = remote controlled
Pnom = nominal capacity
Pmax = maximum capacity
DAS MOD = modular product
OP = option (delivered with the product)
KIT = kit (delivered separately for repair or
upgrade)
PG = connection flange to the duct
GKB (type A) / GKF (type F): "GKB" stands
for standard plasterboards (type A accor-
ding to EN 520) while "GKF" plasterboards
offer a higher fire resistance for a similar
plate thickness (type F according to EN
520)
Cal-Sil = calcium silicate
ζ [-] = pressure loss coefficient
Q = air flow
∆P = static pressure drop
v = air speed in the duct
Lwa = A-weighted sound power level
optimal free air passage and minimal pressure loss

3
Declaration of performance
B-01/2016CE_DoP_Rf-t_V17_EN
DECLARATION OF PERFORMANCE
Declarationofperformance
CE_DoP_Rf-t_V17_EN
B-01/2016
1. Unique identication code of the product-type: Smoke control damper
1. Unique identication code of the product-type: AVANTAGE DP
2. Intended use/es: Smoke control damper to be used in smoke control systems, in multi-compartment applications at re temperatures, or in single-compartment applications.
3. Manufacturer: Rf-Technologies NV, Lange Ambachtstraat 40, B-9860 Oosterzele
4. System/s of AVCP: System 1
5. Harmonised standard, notied body/ies, certicate of constancy of performance: EN 15650:2010, Efectis with identication number 1812, 1812_CPR_1042
6. Declared performance according to EN 12101-8:2011 (re resistance according to EN 1366-10, classication according to EN 13501-4)
Essential characteristics Performance
350x385 mm ≤ Avantage 1V
DP ≤ 700x1075 mm
Avantage 60 Shaft Promatect L500 ≥ 30mm 1 EI 60 (ved i no) S 500 C10000 AA multi
Geoam ≥ 30mm 1 EI 60 (ved i no) S 500 C10000 AA multi
Tecniver ≥ 35mm 1 EI 60 (ved i no) S 500 C10000 AA multi
Glasroc F V500 ≥ 35mm 1 EI 60 (ved i no) S 500 C10000 AA multi
Avantage 120 Promatect L500 ≥ 50mm 1 EI 120 (ved i no) S 500 C10000 AA multi
Geoam ≥ 45mm 1 EI 120 (ved i no) S 500 C10000 AA multi
Geoam Light ≥ 35mm 1 EI 120 (ved i no) S 500 C10000 AA multi
Exthamat ≥ 45mm 1 EI 120 (ved i no) S 500 C10000 AA multi
Tecniver ≥ 50mm 1 EI 120 (ved i no) S 500 C10000 AA multi
Glasroc F V500 ≥ 50mm 1 EI 120 (ved i no) S 500 C10000 AA multi
1 Type of installation: shaft-mounted 0/180°
Nominal activation conditions/sensitivity: Pass - automatic activation
Response delay (response time): closure time Pass - automatic activation
Operational reliability: cycling 10000 cycles (no load)
Durability of response delay: Pass
Durability of operational reliability: Pass
Approved accessories KAP mounting frame; motor VA DP MEC; with
grill; option BLACK (700 x 1075 mm)
High operational temperature (HOT 400/30): NPD (no performance determined)
Harmonised standard
EN 12101-8:2011
The performance of the product identied above is in conformity with the set of declared performance/s.This declaration of
performance is issued, in accordance with Regulation (EU) No 305/2011, under the sole responsibility of the manufacturer identi-
ed above.
Signed for and on behalf of the manufacturer by:
Barbara Willems, Technical Manager
Oosterzele, 01/2016

4Product presentation AVANTAGE DP
Product presentation AVANTAGE DP
The Smoke Control Damper Avantage DP is available as single (1V) shutter units, with a double action actuator that allows the remote
opening and resetting of the blade. The Avantage DP is a CE marked product certified in accordance with EN12101-8 suitable for
vertical mounting within apertures in ducts or structures. It has a C10000 reliability classification that is suitable for use in combined
smoke control and environmental systems and it offers a fire-resistance of 60 or 120 minutes (see the classification overview), and
ensures minimum pressure loss.
Smoke control dampers are suitable for use in ventilating protected lobbies, venting to shafts either naturally or mechanically. They
open to evacuate smoke in emergency situations whilst maintaining fire resistant integrity in standby position.
5simple operating tests through remote opening and resetting
5optimal free air passage and minimal pressure loss
∎tested according to EN 1366-10
∎compliant with EN 12101-8
∎approved for installation in calcium-silicate, ‘Staff’, Tecniver and
Glasroc shafts
∎maintenance-free
∎for indoor use
1. 1 shutter (1V)
2. aluminium frame
3. lock + key
4. blocking mechanism + automatic locking at 90°
5. product identification
6. resetting motor
4
3
6
1
2
5
Range and dimensions AVANTAGE DP 1V60/1V120
1. Refractory material
2. Sealing if mounting frame
3. KAP mounting frame (optional)
4. Nominal dimensions shutter Wn x Hn
5. Built-in dimensions without KAP mounting frame (Wn+10) x (Hn+10)mm
6. Built-in dimensions with KAP mounting frame (Wn+20) x (Hn+20)mm
7. Overall (outside) dimensions of the shutter (Wn+54) x (Hn+54)mm
≥
105mm
10mm
92mm
2
1
3
4
5
6
7
(1V) Wn+ 52mm
(2V) Wn/2 + 66mm
≥ ≤
(W x H) mm 350x385 700x1075

5
Evolution - kits
Evolution - kits
KITS VD24-VA Natural magnet 24 V DC
KITS FDC-VA Volt free switches for remote signalling of open and closed damper
position.
KITS ME AVANDP Motor DP 24V
Options - at the time of order
BLACK Damper painted black with non decorated dust coat to provide vision
shading behind a fitted finishing grille

6Storage and handling
Storage and handling
As this product is a safety element, it should be stored and handled with care.
Avoid:
• any kind of impact or damage
• contact with water
• deformation of the casing
It is recommended:
• to unload in a dry area
• not to flip or roll the product to move it
• not to use the damper as a scaffold, working table, etc.
• not to store smaller dampers inside larger ones
Installation
General points
∎The installation must comply with the classification report and the installation manual delivered with the product.
∎The installation of the shaft must comply with the classification report delivered by the manufacturer.
∎Axis orientation: see the declaration of performance.
∎Avoid obstruction of adjoining ducts.
∎Verify if the blade can move freely.
∎Rf-t smoke dampers may be applied to ducts that have been tested according to EN 1366-8 and EN 1366-9 as appropriate, con-
structed from similar materials with a fire resistance, thickness and density equal or superior to these of the tested materials.
Caution: when fitting, the product should be handled with care and remain protected from any sealing products.
Caution: before putting the installation into operation, clean off all the dust and dirt.
Caution: bear in mind the blade's clearance inside the smoke evacuation duct.
Warning
Extreme care must be taken in the installation of Smoke Control Dampers and regard should be given to health and safety pro-
visions. The Installation should only be carried out by suitably trained and qualified personnel. Installers, users and maintainers
are reminded of their duties under the U.K. Health and Safety at Work Act, the European Community Workplace Directives and
other National Legislation and Guidelines on Safety.
Do not attempt to lift, support or move the damper by the drive linkage transom. If the transom is bent in any way it will cause
damage to the motor drive shaft and gearbox. Do not attempt to operate the damper if the transom bar is damaged.

7
Installation
Operation: manual opening
20°
20°
Unlocking 1V
Turn the key 20° anti clockwise and the damper will push open
without releasing the magnetic latch. Turn the key past 20
degrees and the latch will disengage and the damper will also
push open. To re-arm the latch insert key and turn clockwise.
Operation: manual closing
20°
Resetting 1V
Insert the key and turn 35° clockwise. Press the drive linkage
bar to release from the stand-open position and pull the dam-
per door slowly closed until the latch locates with the strike
plate.
Electrical connection
The DP drive motor is a 24 volt DC 0.8 amp rated motor that requires a 24 volt ± 5% fully smooth and rectified supply.
The damper operates on a 2 wire reverse polarity connection. Terminate cables in a site supplied junction box with screw terminals.
The 24 volt DC motor connections are polarity sensitive. Be sure positive (+) and Negative (-) are connected correctly.
Wire colours: brown = 24 V DC (+); blue = 24 V DC (-); white = not used (programming).
Operation: brown + and blue -: opening; brown - and blue +: closing.
It is recommended that only control systems conforming to standards BS ISO 21927-9, pr BS EN12101-9 and BS EN 12101-10 are used to
operate the smoke control dampers.

8Installation
The Avantage DP is a 24 volt DC drive open, drive closed unit in-
corporating a 24 volt DC pulse active locking latch. It is supplied
with double insulated trailing lead cables for onsite connection
in accordance with these instructions. Mechanisms need to be
visually inspected prior to installation to check any physical
damage to actuators or cables.
The trailing lead cable exit position can be any of the 4 corners
of the damper.
Drill a hole in the refractory material at the chosen corner(s).
The galvanised part at the inside of the shutter is already
indented.
Caution: after passing and fixing the cables, it is necessary to
caulk around the electrical cables with fire resistant adhesive
sealant (BCM f.e.).
1
1
2
It is recommended that once the holes have been drilled at the
cable exit position, the cables are laid and clipped in position
around the inside perimeter of the damper framing and each
cable “Fed and Drawn” through these holes to the outside of
the damper spigot. At all times take care not to damage the
cable insulation.
Lead the cables through the opening. Use the fixation clips
(1) and the plastic cable clamp (2) to attach the cables to the
frame.

9
Installation
Position in the shaft
The shutter is affixed to the smoke evacuation shaft through a
sleeve. That sleeve can be indifferently installed: in the shaft, in
the axis of the shaft or outside the shaft (or shaft extension).
Maintenance
∎No specific maintenance required.
∎Schedule at least two running checks each year.
∎Remove dust and all other particles before start-up.
∎Follow the local maintenance regulations (i.e. BS9999 Annex V; NF S 61-933) and EN13306.

10 Operation and mechanisms
Operation and mechanisms
Operation: general points
∎See under 'Installation' (manual opening and closing).
Caution : please note dampers must be fully open before starting supply and/or extract fans.
VA DP MEC for motorised unlocking and resetting.
Mechanism for the motorised unlocking and resetting of the Smoke Control Damper Avantage DP.
1. Motor and housing
2. Motor mounting bracket
3. Drive arm guide pin
4. Motor drive arm
5. Cable connectors
4
2
1
3
5
Unlocking
∎manual unlocking: manual release with the damper key
∎remote unlocking: remote by connection of 24 V DC
Resetting
∎manual resetting: rearm magnetic latch with key and pull damper closed
∎motorised resetting: remote resetting by inverting the voltage connection
Electrical connection
VA DP MEC
DCU
NONCC
FCU
NONCC
DP
-+
24 VDC
BLUE
BLACK
GREY
BLUE
BLACK
GREY
BROWN
BLUE
MEC Nominal voltage
motor
Nominal voltage
magnet
Power consumption
(stand-by)
Power consumption
(operating) standard switches Protection
class
VA DP MEC 24 V DC N/A N/A Pnom 15VA 1mA...6A, DC 5V...AC 250V IP 32
This manual suits for next models
2
Table of contents
Popular Fan manuals by other brands

ELTA FANS
ELTA FANS H03VV-F installation guide

Hunter
Hunter 20714 Owner's guide and installation manual

Emerson
Emerson CARRERA VERANDA CF542ORB00 owner's manual

Hunter
Hunter Caraway Owner's guide and installation manual

Panasonic
Panasonic FV-15NLFS1 Service manual

Kompernass
Kompernass KH 1150 operating instructions