Procedure de reglage LR180-a - 27/10/2009
Page 5a
LR180 E :
Electrical lock (24 / 48 V ac) with positive safety – tecnicals characteristics
Anomalies
If, cabin on the oor, nothing occurs ;
that the door s' do not open and that the
receiver is lit :
If, cabine on the oor, the receiver
is not lit :
Checks if the alimentation arrives at the lock.
If yes : replace the lock
If no : checks if the alimentation leale the RIR180 modul
If yes : to check the connection of the lock
If no : to check if alimentation goes good in the RIR modul
If yes : replace the RIR modul
If no : to control the line power supply of the locks and
RIR180 modules
to check that transmitter is well lit and centered about well
opposite with the receiver.
If transmitter is well lit; be-with-to say that l' infra-red is HS
(out service).
Therefore, to replace transmitter
if transmitter is extinct : - to check the polarity of connection
- to check the alimentation tension
- to check the presence of
alimentation of transmitter.
Verications
Device RCD180
Principle of operation of piloting d' an electric lock by the transmit-
ting EM150 and receiving RCD180 device.
Transmitter installed on the cabin has a distance approximately 30 cm,
send its infra-red signal to the receiver of stage concerned.
So that transmitter sends its coded signal, it is necessary that alimenta-
tion passes by a called dry contact “info of came”; contact normally used
to control the mobile cam and coming from cupboard of manouevre.
When it’s fed, a green indicator (led) s' light on transmitter.
When the receiver receives its coded signal, the green led s' also light on
this one once the decoded signal.
The DIR180 receiver orders the change d' then; state of the relays of the
RIR180 so d' to supply the electrical lock.