Pinter MINICOMB-EDS User manual

Operating Instructions
MINICOMB®-EDS
Electronic Pressure Switch
for Pressure and Vacuum

2
www.pinter-gmbh.com
Any given information and/or technical data in this document have been prepared very carefully and reect the state
of the art when printed. Information and/or technical data may change without prior notice.
All given information and/or technical data in this document are not binding and for information purposes only. Bin-
ding information and/or technical data can be obtained from our quotations and/or order conrmations.
Please understand that we cannot be held responsible for the correctness of any given information and/or technical
data in this document.
All mentioned product names, product designations, product descriptions and logos are trademarks and property of
their respective owners. MANOCOMB®, MINICOMB®, INTELLICOMB®, INDUSENS®, INDUSWITCH®und CHEM-
SEAL®are trademarks and/or registered trademarks of the PINTER Mess- und Regeltechnik GmbH and/or their
afliated companies in Germany, the European Union, Switzerland and/or other countries.
Reproduction and / or duplication of this manual or any portion of this manual is prohibited without permission.
Sample congurations are shown on the title page, hence the delivered product may differ from the depicted pro-
ducts.
This document was originally issued in German language.
Product Description
The product is an electronic pressure switch for measuring the pressure and / or vacuum in pressure lines of - de-
pending on model conguration - compressed air, neutral gases, corrosive gases and liquids. The pressure switch
has - depending on the version - 1 or 2 digital outputs (PNP) or 1 digital output and 1 analogue output (4-20 mA).
About these instructions
This instruction contains important information, in order to safely and properly install, operate and maintain the MINI-
COMB-EDS pressure switch and also information you on how to x simple failures youself.
Before working with the MINICOMB-EDS pressure switch, make sure that you have read and understand these
instructions completely.
Further documents
The MINICOMB-EDS pressure switch is a component. Please also read the instructions for the rest of your system.
This includes:
• system documentation of the manufacturer
Intended use
• Only use the product in industrial applications.
• Only use the product with media, that is - depending on model conguration - compatible with aluminium / Al2O3
/ FKM or stainless steel 1.4404 (AISI 316L) / Al2O3 / FKM.
• Only use the product within the specied operating conditions and performance limits.
• Please also note operating instructions of other system components, including the system documentation of
the manufacturer.
• Please also note generally applicable statutory and other binding regulations of the European and national
legislation and regulations in your country for accident prevention and environmental protection.
• Prevent mechanical loads on the device under any circumstances. Never use the device as a handle or shoul-
der. Do not place objects on it.
• You must not make alterations or modications to the device!
• All activities with the product may only be performed by a specialist or by a trained person under the supervi-
sion of a specialist. A specialist is someone who based on their technical training, knowledge and experience
and his knowledge of the relevant provisions of his assigned job is able to identify potential hazards and take
appropriate safety measures. A specialist must comply with the relevant subject-specic rules. Note that there
may be additional requirements in the country of use.
• Always turn off pressure and power of the relevant part of the facility before mounting the unit or unplug or
plug. Secure the part from re-powering or re-pressuring. During installation hang out warning signs that warn
from re-powering or re-pressuring.
The intended use also includes that you have read and understood these instructions.

www.pinter-gmbh.com
3
EN
Type Designation
Type / Part-No. E 0 0 x x x - x x - x D x
Model sub-base mounting 1
female thread 5
Material
Aluminium / Ceramics / FKM 1
Stainless Steel 1.4404 / Aluminium / Ceramics
/ FKM 2
Output
1x PNP A
2x PNP B
1x PNP + 4 - 20 mA C
Pressure relative 0
absolute 5
Pressure Range
-1...0 bar 0 06
-1...+1 bar 0 09
0 - 1 bar 20
0 - 1,6 bar 22
0 - 2,5 bar 23
0 - 4 bar 24
0 - 6 bar 25
0 - 10 bar 26
0 - 16 bar 27
0 - 25 bar 28
Process Connection sub base mounting standard P
1/4“ female thread 4
Further Options without further options O
cleaned for O2service A
Scope of delivery
The package includes:
• 1x MINICOMB-EDS Electronic Pressure Switch
• 2x mounting screw (only sub base mounting )
• 1x o-ring (only sub base mounting)
• 1x operating instructions

4
www.pinter-gmbh.com
Technical Data
Technical Data Standard Options
Function electronic pressure switch with display; based on ceramics sensor
Life Cycle at least 100 mio. switch cycles
Pressure Ranges (relative or absolute) 0 - 1 bar; 0 - 1,6 bar; 0 - 2,5 bar; 0 - 4 bar;
0 - 6 bar; 0 - 10 bar; 0 - 16 bar; 0 - 25 bar
Vacuum Ranges (relative) -1...0 bar;
-1...+1 bar; -1...+5 bar; -1...+9 bar; -1...+15 bar; -1...+24 bar
Overpressure Safety (short time) > 2,5x FS on request
Burst Pressure > 3,0x FS on request
Vaccum Safety -1 bar
Material Enclosure Aluminium on request
Material Pressure Inlet (wetted)
Aluminium Stainless Steel 1.4404 (AISI
316L)
Material Sensor
(wetted)
Al2O3
Material Seal (wetted)
FKM
(NBR and FKM fro sub-base
mouting)
on request
Permissible Media Temperature -20...+85°C
Permissible Ambient Temperature -20...+85°C
Output Signals either 1x PNP, 2x PNP or 1x PNP with analogue output 4 - 20 mA
Switch Accuracy, Repeatability < 0,5% FS
Accuracy Analogue Output < 0,5% FS
Longterm Stability (DIN EN 60770) ± 0,5% FS
Switch Point / Reset Point adjustable > 0,5% FS - 100% FS / adjustable > 0,5% FS from
switch point
Switching Function adjustable, normally open, normally closed, hysteresis-mode,
window-mode
Response Time < 10ms
Switching Current DC max. 0,5 A
Max. Load Resistance 600 Ω
Display OLED
Switch State Indicator 1 LED per channel (yellow)
Menu Navigation oriented to VDMA standard sheet 24574-1 (with addition plain text
menu)
Menu Language adjustable - English, French, German, Italian, Spanish
Supply 24 VDC (15 - 32 VDC) on request
Power Consumption < 50 mA
Process Connection either sub-base mounting or 1/4“ female thread
Electrical Connection M12x1 plug (5-pin)
Weight approx. 0,3 kg
Protection (EN 60529) IP65 (with installed counter-plug)
Shock Resistance (XYZ-direction) 30g, xyz, DIN EN 60068-2-27 (11ms)
Vibration Resistance (XYZ-direction) 5g (10….150Hz), xyz DIN EN 60068-2-6
Electromagnetic Compatibility
EMC-Directive 2004/108/EC,
EN 61326-1:2013, EN 61326-2-3:2013;
EN 61000-6-2:2005; EN 61000-6-4:2007 + A1:2011
Further Functions
zero-point adjustment, adjustable switching and re-set delay,
changable units, adjustable display power off, rotatable display
indication, password protection
Further Options cleaned for O2service

www.pinter-gmbh.com
5
EN
Installation
• Let the product acclimatize for several hours before installation and commissioning, as otherwise condensation
water can form in the housing.
• Install and fasten the product according to the pictures.
• If the product is not properly fastened, other plant parts may be damaged by uncontrolled movements of the
product, as well as personal injuries may occur. Make sure that the product is securely fastened.
Dimensions
MINICOMB-EDS
version with female thread
S
Sealing Surface
R 2,4 µm
a
Torque
M = 12 Nm
A
+1
1/4" female thread ISO 228
A - coded
MINICOMB-EDS
version with sub-base mounting
S
O-Ring Seal 5x1,5 NBR∅
(within supply range)
A - coded
Cylinder Screw
M5x30 DIN EN ISO 4762
(within supply range)

6
www.pinter-gmbh.com
Electrical connection
• Route cables so that nobody can trip over them.
• Only use harmonized (color-coded or number) cables. Make sure of the correct connection of the cables!
• Connect the product accurding to the pictures.
• If the product is not properly connected electrically, the protection type can not be guaranteed. Make sure the
plug is securely connected.
Pin Assignment
Pin Description cable color (cable available as sep.acc.)
1+Ub brown
2 OUT2 (PNP) / 4 - 20 mA white
3 0 Volt blue
4 OUT1 (PNP) black
5 FE grey
1P
1 PNP - output
1PA
1 PNP - output + 1 analogue output 4 - 20 mA
2P
2 PNP - outputs
Circuit Diagrams

www.pinter-gmbh.com
7
EN

8
www.pinter-gmbh.com
Commissioning, Parameter Setup
• Before starting make sure that all gaskets and seals and screwed connections are installed correctly.
• Set the desired parameters.
• Set parameters can be reviewed in the individual menu items.
• Most important parameters can be reviewed on the status-display quickly.
• Parameters can be set during operation.
• Please note that a change in the parameters during operation can affect the reliability of the system!
Parameters Description Values Factory Defaults
SP1 / FH1 set point 1 or
upper window value 1 OFF; >= 0,5% FS up to 100% FS 75% FS
RP1 / FL1 (1) re-set point 1 or
lower window value 1 0% FS up to SP -0,5% FS (+0,5% FS if SP < 0) 74,5% FS
SP2 / FH2 (2) set point 2 or
upper window value 2 OFF; >= 0,5% FS up to 100% FS 25% FS
RP2 / FL2 (1,2) re-set point 2 or
lower window value 2 0% FS up to SP -0,5% FS (+0,5% FS if SP < 0) 24,5% FS
DS1 switch delay 1 OFF; 0,2 up to 50 s OFF
DR1 re-set switch delay 1 OFF; 0,2 up to 50 s OFF
DS2 (2) switch delay 2 OFF; 0,2 up to 50 s OFF
DR2 (2) re-set switch delay 2 OFF; 0,2 up to 50 s OFF
OU1 switching function 1
HNO (hystersis function, normally open)
HNC (hystersis function, normally closed)
FNO (hystersis function, normally open)
FNC (hystersis function, normally closed)
HNO
OU2 (2) switching function 2
HNO (hystersis function, normally open)
HNC (hystersis function, normally closed)
FNO (hystersis function, normally open)
FNC (hystersis function, normally closed)
HNO
OUA (3) conguration
analogue output
I (4 - 20 mA = 0 - 100% FS)
I INV (4 - 20 mA = 100 - 0% FS) I
UNI pressure unit bar; mbar; MPa; kPa; psi; % bar
DISP autom. display shut-off OFF; 1 - 60 min OFF
DISR display rotation NO (standard display)
YES (display rotated by 180°) NO
ZERO zero correction NO; 1% FS (4) NO
PASS password protection NO; 0000 - 9999 NO
LANG language for text menu DE; EN; ES; FR; IT; OFF DE
(1) menu item not available, when corresponding output is turned OFF
(2) only 2P
(3) only 1PA
(4) for pressure ranges < 4 bar max zero correction +/- 50 mbar
Parameters, Description, Values, Factory Defaults

www.pinter-gmbh.com
9
EN
Switching Function
Hysteresis-Mode Window-Mode
In Hysteresis-Mode both switching point SP and
reset point RP can be adjusted freely. The switch
switches back when the RP is reached.
This allows, for example, a simple 2-point control.
With the Window-Mode dened areas can be
monitored. If the process pressure is within the
dened range the output is either closed or open.
Setpoint
It is not possible to adjust RPx > SPx or FLx > FHx.
In general SPx or FHx is leading:
if SPx/FHx > 0 bar, RPx/FLx = 0% FS up to SP -0,5% FS
if SPx/FHx < 0 bar, RPx/FLx = SP +0,5% FS up to 100% FS
Switch Delay
By adjusting switch delay and re-set
switch delay you can change the time
between the detection of a pressure
signal and the switch-over of the digital
output(s).
Note that a delayed signal transmissi-
on might possibly have an impact on
plant safety.

10
www.pinter-gmbh.com
Standard-Display
Standard view with information about output conguration, pressure unit and pressure value.
exemplary view of a 2P-version with output 1 congured HNC and output 2 congured FNO.
row 1 output conguration(s)
row 2 pressure unit
row 3 pressure value
Display
row 1 output conguration(s)
row 2 zero correction value and pressure unit
row 3 pressure value
row 1 description of error
row 2 description of error
row 3 Error Code
Standard view with information about output conguration and pressure value with activated zero correction.
exemplary view of a 2P-version with output 1 congured HNC and output 2 congured FNO.
Standard view in case of an error
1. LED for Switch Output 1
2. LED for Switch Output 2
3. Display (Pressure Indicator, Operating Modes, Menu)
4. Menu Key / Menu Item Selection / Parameter Conrmation
5. Keys for Menu Navigation/ Parameter Change
Display and 3-button control panel