Philips Dynalite DUS704W User manual

Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia
t +61 8338 9899 f +61 2 8338 9333 dynalite.info@philips.com ABN 33 097 246 921 Philips.com/dynalite
DUS704W
Ceiling Mount Universal Sensor Installation Manual
The DUS704 series combine motion detection (PIR), infra red remote control reception (IR) and
ambient light level detection (PE) in the one device. In applications such as homes, lecture
theatres and office towers, DUS704 universal sensors can be utilised to detect motion and switch
on the lights.
When rooms are unoccupied, lights can be automatically dimmed or switched off to provide
energy savings. The same sensor provides IR remote control reception to give full control over
lights, audio-visual equipment and blinds. A range of hand held infra-red transmitters to
complement DUS704 series universal sensors.
In situations where it is critical to maintain precise lighting control for individual workspaces, such
as a flight control tower or office workstation, the DUS704 facilitates light compensation. The
DUS704 can be placed in an automatic “Daylight Harvesting” mode for energy savings.

installation steps
2DUS704W Installation Manual Rev G.doc
1. * WARNING * Do not touch the Pyro Sensor with your fingers. For indoor use only.
2. Select an appropriate indoor mounting location, as detailed in the location guidelines on the following
pages. Note that this product has three functions, and the optimum mounting location for each individual
function may conflict with each other, and may require the use of multiple sensors.
3. Remove the cover from the base unit by un-clipping the bottom of the cover and hinging it upwards.
4. Screw the base unit to the wall, ensuring the unit is mounted vertically. Pass the data cable through the
cable entry hole.
5. Terminate the data cable as shown below.
6. Use silicon sealant to seal any cable entry and screw holes to prevent air draughts, dust and insects from
entering the enclosure.
7. Replace the cover onto the base unit by locating it in the top clip position then hinging it downwards.
Remove the screw cap at the bottom of the housing, insert and loosely tighten the supplied screw, then
replace the screw cap.
internal view

connecting data cable
DUS704W Installation Manual Rev G.doc 3
motion detection mounting location
• Fix the sensor to a firm section of wall
• Position the sensor so it is between 1.1 and 3.1 metres from the floor. Optimum height for the sensor is 2.1
metres.
• Slide the circuit board up or down so the marker on the housing matches up with the installed height on the
scale provided on the right hand side of the circuit board.
• Position the sensor so it is at least 2 metres away from electrical lighting such as neon and fluorescent
lights.
• Position the sensor as to avoid exposing it to direct sunlight and heating / cooling sources.
• Keep data cables away from electrical wiring.
• Select a location where persons are more likely to walk across the detection “fingers” rather than into them
(see diagram below).
• For programming instructions refer to Dynalite Tech Note – Setting up Motion Detection functions.
motion detection lens pattern
INSTALLATI ON D ETAIL S
DIMTE K 11 0
INPUT: 23 0 V 5 0-6 0Hz 10 A
OUTPUT: 1 x230 V 10A
MOUNT V ERTIC ALLY
AGAINST WALL
ENSURE GOOD VENT ILAT ION
FOLLOW INSTALL AT ION
INSTRUCTIO NS
Unit6 -11 9 /13 3 M cE VOYS t.A lexand ri a
NSW 2015A USTRALIA
Manufactured by :
ISOLATEFROM
MAINSS UPPLYBEFO RE
REMOVINGTH ISC OVER
NOUS ERSE RVICEABLEPA RTS INSIDE
SERVICE BYQ UALIFIED PERSONNEL ONLY
INSTALLATI ON D ETAIL S
DIMTE K 11 0
INPUT: 23 0 V 5 0-6 0Hz 10 A
OUTPUT: 1 x230 V 10A
MOUNT V ERTIC ALLY
AGAINST WALL
ENSURE GOOD VENT ILAT ION
FOLLOW INSTALL AT ION
INSTRUCTIO NS
Unit6 -11 9 /13 3 M cE VOYS t.A lexand ri a
NSW 2015A USTRALIA
Manufactured by :
ISOLATEFROM
MAINSS UPPLYBEFO RE
REMOVINGTH ISC OVER
NOUS ERSE RVICEABLEPA RTS INSIDE
SERVICE BYQ UALIFIED PERSONNEL ONLY
Connect Data Cable in a "Daisy Chain"
serial cable permanent connectors
connect data cable in a “daisy chain”
Recommended Cable Colours
Green/White Pair paralleled for GND
Orange/White Pair paralleled for +VE
Blue/White Pair Blue for DATA
White for DATA-
Recommended Cable Types
Belden: 9503
Garland: MCP3S
Hartland: HCK603
M&M Cable: B2003CS
Dynalite: DYNET-STP-CABLE
Side view
Top view

optional motion detector lens
4DUS704W Installation Manual Rev G.doc
In addition to the supplied Wide Angle lens, An option for a long range lens is available for corridor
applications:
• DUS704W Long Range – Useful for monitoring a long thin space such as a corridor.
Contact your local supplier for more details
infrared receiver mounting location
• Position the sensor so it is within 6 meters of the intended operating positions of the infrared transmitter
• Position the sensor so it is not directly exposed to light, especially incandescent and sunlight, both of which
can substantially reduce IR range
• Keep data cables away from electrical wiring
photo electric cell mounting location
• Position the sensor so it “sees” a combination of artificial light and natural
light
• Position the sensor so it is not directly exposed to artificial light or sunlight
• Keep data cables away from electrical wiring
• For programming instructions refer to Dynalite Tech Note - Setting up PE
functions
6.0 Meters Max
Optional Lens –DUS704W Long Range

specifications
DUS704W Installation Manual Rev G.doc 5
warranty policy
Dynalite warrant to the original purchaser for a period of twenty four (24) months from the date of
shipment ex-factory of the equipment that should the equipment prove defective by reason of improper
workmanship or material, Dynalite will repair or replace the same without charge provided the equipment
has not been improperly installed, operated, repaired, damaged or abused. The warranty granted herein
is limited to repair or replacement only. Dynalite has the right to substitute any warranty item not on the
current price/equipment list. As far as the law permits, Dynalite shall not be liable for any loss or damage
caused to property or persons arising from any cause whatsoever. This warranty is subject to the return of
the equipment to Dynalite, or the Dynalite authorised distributor who supplied the equipment (the
„Supplier‟), by prepaid freight within the twenty four (24) month warranty period. Where Dynalite, or the
Supplier, agree to a site visit during the warranty period and it is found to be an operational problem, and
not subject to warranty in that event, then a field service call out charge will apply. Contact Dynalite or the
Supplier for details.
Motion Detector
Wide Angle Wall Mount PIR Detector
Range 12m x 90O (standard lens)
Mounting height: 1.1m to 3.1m
LED activation indicator
Adjustable Pulse Count & Sensitivity
Detection zones: 20 dual element zones
Sensor: Dual element pyro-electric
R.F.I. Immunity: >15V/m @ 10- 1000MHz
Optional lens:
* 30m x 30O Long Range
PE Cell
Dynamic range < 5 lux to > 5000 lux
Automatic “Daylight Harvesting” mode
Can be used for light measurement
Installation Position
Wall mount, indoor use only
Infra Red Remote Control Receiver
Range > 6m
LED activation indicator
Can be used with DTK500 series
Infra Red remotes or other learning
IR Remote controls
Dimensions
H 85mm x W 66mm x D 45mm
Control IO
Serial Port –RS485 DyNet
DyNet DC Load
20mA
Setup
All functions remotely
programmable
Weight
0.1Kg Packed

notes
6DUS704W Installation Manual Rev G.doc
DUS704W Instruction Manual Rev F.doc. Specifications and design subject to change without notice.
Philips Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921). Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail: dynalite.info@philips.com Web: Philips.com/dynalite
Table of contents
Other Philips Security Sensor manuals

Philips
Philips HP8115 User manual

Philips
Philips EcoSet SEG101 User manual

Philips
Philips EasyAir SNS300 User manual

Philips
Philips EasySense SNS200CMP User manual

Philips
Philips EasyAir SNS212 MC User manual

Philips
Philips OccuSwitch LRM1771 User manual

Philips
Philips LRM226500 User manual

Philips
Philips DUS804C User manual

Philips
Philips CHLORIDE COMPAC CXX Series User manual

Philips
Philips 17266xx16 Series User manual