WCS-PNG210
Product Description
2018-03
9
Rotary coding switches S4 and S5
The two switches control the operating modes. nsure that the two switches are at position 0
to enable the data exchange mode.
PROFINET State:
PROFINET Power:
The "PROFIN T Power" L D is green: The L D is connected directly to the electrically isolated
supply voltage of the PROFIN T side.
PROFINET Link/Activity P1:
The "Link/Activity" L D on port 1 is controlled directly by the PROFIN T processor and is
green if the thernet link pulses are found. When there is data traffic on the network, the L D
flashes green at the same speed as the sent/received data.
PROFINET Link/Activity P2:
The "Link/Activity" L D on port 2 is controlled directly by the PROFIN T processor and is
green if the thernet link pulses are found. When there is data traffic on the network, the L D
flashes green at the same speed as the sent/received data.
0 1 0 1 5 Script error
0 1 1 0 6 Reserved
0 1 1 1 7 Communication WCS reader, RS
send buffer overflow
1 0 0 0 8 Communication WCS reader, RS
receive buffer overflow
1 0 0 1 9 Communication WCS reader, RS
timeout
1 0 1 0 10 General fieldbus error
1 0 1 1 11 Parity or frame check error
1 1 0 0 12 Reserved
1 1 0 1 13 Fieldbus configuration error
1 1 1 0 14 Fieldbus data buffer overflow
1 1 1 1 15 Reserved
Table 2.2 Meaning of the error codes (four L Ds display " rror No/Select ID", if the "State" is
illuminated red and thus indicates an error or a warning)
L D "PROFIN T State" PROFIN T interface state
Lights up green Data exchange in progress
Flashes green PROFIN T is initialized, waiting for connection with IO controller
Lights up red rror with PROFIN T hardware
Flashes red rror during PROFIN T initialization
Table 2.3 "PROFIN T State" L D display
rrorNo/Select ID L D rror number rror description
L D8 L D4 L D2 L D1