Nibe S Series User guide

Installer manual
HRV unit
NIBE ERS 30-600
IHB EN 2306-1
731443

S-series
S1255
F-series

41 Important information
4Safety information
4Symbols
4Serial number
4Recovery
5Inspection of the installation
62 Delivery and handling
6Transport and storage
6Compatible products
6Removing the covers
7Assembly
83 Design of the HRV unit
9Pipe connections
9Sensors etc.
9Electrical components
9Ventilation
9Miscellaneous
104 Ventilation connections
10Condensation water drain
11General ventilation connections
11Ventilation flow
11Adjusting ventilation
11Ventilation connections
125 Electrical connection
12Overview accessory board (AA5)
12Supply
12Connecting to main product
146 Commissioning and adjusting
14Preparations
14Filling
14Start-up and inspection
157 Activating ERS 30
15Start guide
15Menu system
178 Disturbances in comfort
17Troubleshooting
189 Accessories
1910 Technical data
19Dimensions
20Technical specifications
21Energy labelling
22Electrical circuit diagram
43Contact information
3Chapter |NIBE ERS 30-600
S
Table of Contents
S-series

Safety information
This manual describes installation and service procedures
for implementation by specialists.
The manual must be left with the customer.
This appliance can be used by children
aged from 8 years and above and per-
sons with reduced physical, sensory or
mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning use
of the appliance in a safe way and under-
stand the hazards involved. Children shall
not play with the appliance. Cleaning and
user maintenance shall not be made by
children without supervision.
This is an original manual. It may not be
translated without the approval of NIBE.
Rights to make any design or technical
modifications are reserved.
©NIBE 2023.
If the supply cable is damaged, only NIBE,
its service representative or similar author-
ised person may replace it to prevent any
danger and damage.
Symbols
Explanation of symbols that may be present in this manual.
NOTE
This symbol indicates danger to person or machine.
Caution
This symbol indicates important information about
what you should consider when installing or servi-
cing the installation.
TIP
This symbol indicates tips on how to facilitate us-
ing the product.
Serial number
The serial number can be found at the top, to the left of the
ventilation connection for exhaust air.
UN
UN
Serial number
Caution
You need the product's serial number for servicing
and support.
Recovery
Leave the disposal of the packaging to the installer
who installed the product or to special waste sta-
tions.
When disposing of the product, its constituent ma-
terials and components, e.g. compressors, fans, circulation
pumps and circuit boards, must be disposed of at a special
waste station or dealer who provides this type of service.
To access the separate components, refer to the section
that shows the construction of the product. No special tools
are required for access.
Improper disposal of the product by the user results in ad-
ministrative penalties in accordance with current legislation.
NIBE ERS 30-600Chapter 1 | Important information4
S
Important information

Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be
carried out by a suitably qualified person. In addition, fill in the page for the installation data in the User Manual.
DateSignatureNotesDescription
✔
Electricity (page 12)
Connections
Main voltage
Fuses property
Earth circuit-breaker
5Chapter 1 | Important informationNIBE ERS 30-600
S

Transport and storage
ERS 30 should be transported and stored in the dry.
Compatible products
•SMO S40•VVM S320
•VVM S325
•S1155
•S1255
Removing the covers
1. Open the filter cover as illustrated.
2. Pull out the filters.
UN
3. Unscrew the screws as illustrated and pull out the front
panel.
UN
4. Unscrew both of the screws at the top and lift off the
top panel.
NIBE ERS 30-600Chapter 2 | Delivery and handling6
S
Delivery and handling

Assembly
ERS 30 must be placed on a stable surface to minimise the
risk of vibrations.
•Wherever the unit is located, any joists that back onto a
sound-sensitive room should be fitted with soundproofing.
•Condensation water comes from the HRV unit. A condens-
ation outlet with a water seal must be installed and routed
to an internal drain.
•The HRV unit’s installation area always has to have a
temperature of at least -25 °C and max. 50 °C.
INSTALLATION AREA
Leave a free space of 600 mm in front of the product.
600
NOTE
Ensure that there is sufficient space (300 mm) for
connecting ventilation ducts.
7Chapter 2 | Delivery and handlingNIBE ERS 30-600
S

UN
XL32
HQ11XL34
XL31
XL33GQ2 GQ3EP26
AA5
HQ10
XL40
BT23 BT20
BT21
BT22
PZ1
WM5 BL2
QN37
W101
W102
RF3
NIBE ERS 30-600Chapter 3 | Design of the HRV unit8
S
Design of the HRV unit

Pipe connections
Ventilation connection, exhaust airXL31
Ventilation connection, extract airXL32
Ventilation connection, supply airXL33
Ventilation connection, outdoor airXL34
Condensation water drainXL40
Sensors etc.
Level monitorBL2
Temperature sensor, exhaust airBT20
Temperature sensor, extract airBT21
Temperature sensor, supply airBT22
Temperature sensor, outdoor airBT23
Electrical components
Accessory cardAA5
EMC cardRF3
Cord with connection plugW101
Communication cableW102
Ventilation
Heat exchangerEP26
Exhaust air fanGQ2
Supply air fanGQ3
Exhaust air filterHQ10
Supply air filterHQ11
Bypass damperQN37
Miscellaneous
Type platePZ1
Condensation water troughWM5
Designations according to standard EN 81346-2.
9Chapter 3 | Design of the HRV unitNIBE ERS 30-600
S

Condensation water drain
ERS 30 can produce several litres of condensation water
per day. It is therefore important that the condensation
outlet is correctly executed and the HRV unit installed hori-
zontally.
Check that the water seal is airtight and firmly in position.
The connection must be made so that the user can check
and top up the water seal, without opening ERS 30.
The connection for the condensation outlet measures Ø15
mm.
If the HRV unit will be installed in a cold area, the condensa-
tion water drain pipe must be insulated so the condensation
water in the pipe does not freeze. It is also recommended
that the water seal is mounted in a warm area to guarantee
that the water in the water seal does not freeze. If it cannot
be guaranteed that insulation will protect the condensation
water drain pipe against frost, a thermostat-controlled
heating cable must be installed around the condensation
water drain pipe. The installation from the water seal to the
drain must be carried out with a requisite slope of at least
1 %.
CLEANINGTHECONDENSATIONWATERDRAIN
Condensation forms when ERS 30 is working. This condens-
ation is led off and collected in the condensation water drain.
Apart from water, a certain amount of dust and particles
also collect there.
Check regularly that the condensation water drain and any
floor drains are not blocked; water must be able to run
through freely. Clean, if necessary.
NOTE
During operation, negative pressure arises in the
HRV unit, which means that a water column of at
least 100 mm must be guaranteed in the water
seal.
100 mm
NIBE ERS 30-600Chapter 4 | Ventilation connections10
S
Ventilation connections
Other manuals for S Series
4
This manual suits for next models