S-FLP Series
The Tubular Parallel Form Structure
Surge Protective Devices
Website: http://www.anpe.cn
Service Tel: +86(25)-84459479
Address: New Power industrial Park, Luhe Economic Development Zone, Nanjing, China
Postcode: 211500
Nanjing New Power Electric Co., Ltd.
604100503000303
XX X X X X .X
Explosion proof:blank:Non explosion proof type
Types FL: :lightning protection
Ex:Explosion proof type
Protected mode:blank:floating
G:grounding
Voltage:5:5 V DC; 24:24 V DC
Input channel:2:2-wire; 3:3-wire
4:4-wire; 2D:dual channel
4P:4-wire parallel
2S:2-wire series; 3S:3-wire series
2P:2-wire parallel; 3P:3-wire parallel
Structure:T:12.4 mm module insert
S:7.4 mm; P :field installation
Series S: :S series SPD
Field Control room
Field
devices
(transmitter)
S series
surge
protective
devices
Equipotential connection drawing
Connection diagram
S series
surge
protective
devices
Control
room
devices
(DCS or
PLC)
èApplications
S-FLP series Form structure SPD is used to protect signals
and control equipments, preventing interference caused by
lightning or high voltage switch. In a short surge impact, by
discharging the transient current to the ground to clamp the
voltage in a safe level and ensure the transmission. It
guarantees the safety for industrial automation equipment.
This product is a 304 stainless steel shell, hybrid circuit
design with the advantages of strong surge shock resistance.
Moreover, it is easy to use and install, can be used with the
transmitter, flowmeter, etc.
èGrounding
It is necessary to ground the SPD correctly. Each SPD
should be grounding by DIN rail.
èExplosion protection parameters
Parameters certified by China National Quality Supervision
and Test Centre for Explosion Protected Electrical Products
(CQST):
Explosive-proof grade: Ex ia ⅡC T6 Ga
Explosion proof parameters: (please see the explosion-
proof certificate for details)
Type
Parameter
V Un
Max.continuous voltage Uc (AC)
oltage
Max.continuous voltage Uc (DC)
Impulse current limp(10/350 μs
Total discharge current C2
Discharge current per path In(8/20 μs, C2)
)
In(8/20 μs, )
Voltage protection Up(8/20 μs, C2)
Bandwidth fG(100 Ω resistance)
Intrinsically safe circuit certification
Response time Ta
Temperature
Thread size(match)
Installation
Grounding mode
Output wire size
Material
Protection degree
S-FLP-2P-24.Ex S-FLP-3P-24.Ex S-FLP-4P-24.Ex
24 V
32 V
22.5 V
2 kA
20 kA
10 kA
24 V
32 V
22.5 V
2 kA
20 kA
10 kA
24 V
32 V
22.5 V
2 kA
20 kA
10 kA
L-L ≤ 60 V/L-PE ≤ 650 V
10 MHz
L-L ≤ 60 V/L-PE ≤ 650 V
10 MHz
L-L ≤ 60 V/L-PE ≤ 650 V
10 MHz
Ex d ia IIC T6 Ga
<1ns
-40 ℃~80
M20×1.5, 1/2" NPT, 3/4" NPT etc. (Pin thread)
parallel form structure
connecting lead
2
1.5 mm , length 250 mm, Multiple lines to soft or hard, wear-resistance
304 stainless steel
IP67
IIC Gb, Ex
℃
RD
S-FLP-2P-24.Ex
S-FLP-3P-24.Ex
S-FLP-4P-24.Ex
BK
GNYE
RD
BK
BU
GNYE
RD
BK
BU
BN
GNYE
GND
EX cable gland
transmitter
èStandards
IEC 61643-21/GB 18802.21; IEC 60079-4/GB 3836.4
IEC 62305-1~IEC 62305-5; IEC 61508-1~IEC 61508-7
èModel description
èFeatures
m2-wire, 3-wire, 4-wire;
mMultiple protection circuit, strong resistance to surge;
mM20 × 1.5 etc (match);
mField parallel install module;
m304 stainless steel shell;
mApply to 0 ~ 24 V measurement and control system.
èParameters
èWiring diagram