MFZ Ovitor CS 110 User manual

Operating Instructions for CS 110 Door Controls EN
CS 110 Door Controls / Rev. A 05 – 1

2 – CS 110 Door Controls / Rev. A 05
1. Contents
1. Contents 2
2. Information in this document 2
3. General safety instructions 3
4. Product overview 4
5. Initial operation 6
6. Initialisation 11
7. Changing the direction of rotation 11
8. Setting the travel limits 11
9. Programming using the LCD Monitor 13
10. Navigator (only with the LCD monitor) 14
11. Input mode (LCD monitor) 15
12. Error indication and elimination 16
13. Door cycle counter 17
14. Technical data 17
15. EC Declaration of Incorporation 18
Original Operating Instructions
−Protected by copyright.
−No part of this manual may be reproduced without our
prior approval.
−Subject to alterations in the interest of technical progress.
−All dimensions are given in millimetres.
−The illustrations are not true to scale.
Meaning of symbols
DANGER!
Safety notice indicating a danger that will directly result in
death or severe injury.
WARNING!
Safety notice indicating a danger that can result in death or
severe injury.
CAUTION!
Safety notice indicating a danger that can result in slight or
moderate injuries.
NOTICE
Safety notice indicating a danger that can result in damage
to property or in irreparable damage to the product
CHECK
Reference to a check that needs to be carried out
REFERENCE
Reference to separate documents that must be observed
Instruction requiring action
−List, itemisation
ÔReference to other sections of this document
2. Information in this document

EN
CS 110 Door Controls / Rev. A 05 – 3
3. General safety instructions
DANGER!
Failure to comply with the documentation could
result in life-threatening danger!
Be sure to follow all the safety instructions in this docu-
ment.
Warranty
The warranty with regard to function and safety is only valid
if the warnings and safety instructions in these operating
instructions are observed.
MFZ Antriebe GmbH + Co. KG accepts no liability for personal
injury or material damage arising from failure to observe the
warnings and safety instructions.
MFZ shall not provide a warranty and does not accept any
liability for damage arising from the use of non-approved
replacement parts or accessories.
Use for the intended purpose
The CS 110 control unit is intended exclusively for the
purpose of controlling door systems that have mechanical or
electronic (AVE) travel limit systems.
Keep remote control units out of the reach of children and
do not allow children to play with xed regulating or control
devices.
Target group
Only qualied and trained specialist tters are allowed to
install the door operator and carry out mechanical servicing
work.
Qualied and trained specialist tters must have the follow-
ing:
− - Knowledge of the general and specic safety and
accident-prevention regulations
−- Knowledge of all the relevant regulations
−Training in the use and care of appropriate safety equip-
ment
−The ability to recognise the risks associated with the instal-
lation work
Only qualied and trained electricians are allowed to connect
up the door operator to the power supply and to carry out
electrical servicing work.
Qualied and trained electricians must have the following:
− Knowledge of the general and specic safety and accident-
prevention regulations
−Knowledge of the relevant electrotechnical regulations
−Training in the use and care of appropriate safety equip-
ment
−The ability to recognise the risks associated with electricity
Instructions relating to installation and connection
−Before commencing electrical works, the system must be
disconnected from the power supply. Measures must be
taken to ensure that the power supply remains switched off
for the duration of the works.
−The local safety regulations must be observed.
−Power cables must be laid separately from control cables.
Regulations and test specications
The following regulations must be complied with when
connecting, programming or servicing the unit. (The list is not
exhaustive.)
Construction product standards
− EN 13241-1 (Products without re resistance or smoke
control characteristics)
−EN 12445 (Safety in use of power operated doors - Test
methods)
−EN 12453 (Safety in use of power operated doors - Requi-
rements)
−– EN 12635 (Garage doors and gates - Installation and
use)
−EN 12978 (Safety devices for power operated doors and
gates - Requirements and test methods)

4 – CS 110 Door Controls / Rev. A 05
EMC
−EN 55014-1 (Electromagnetic compatibility - Requirements
for household appliances)
−EN 61000-3-2 (Limits for harmonic current emissions)
− EN 61000-3-3 (Limitation of voltage changes, voltage uc-
tuations and icker in public low-voltage supply systems)
−EN 61000-6-2 (Electromagnetic compatibility (EMC) - Part
6-2: Generic standards - Immunity for industrial environ-
ments)
−EN 61000-6-3 (Electromagnetic compatibility (EMC) - Part
6-3: Generic standards - Emission standard for residential,
commercial and light-industrial environments)
Machinery standards
−EN 60204-1 (Safety of machinery - Electrical equipment of
machines, Part 1: General requirements)
−EN 12100-1 (Safety of machinery - Basic concepts, general
principles for design, Part 1: Basic terminology, methodo-
logy)
Low-voltage electricity
−EN 60335-1 (Household and similar electrical appliances -
Safety)
−EN 60335-2-103 (Particular requirements for drives for
gates, doors and windows)
Committee for Workplaces (Ausschuss für Arbeitsstätten -
ASTA)
−ASR A1.7 (Technical Regulations for workplaces - Doors
and gates)
4. Product overview
4.1 Models available
The following models of the CS 110 control unit can be
supplied:
−CS 110 control unit integrated in the operator
−CS 110 control unit in CS Mini housing
−CS 110 control unit in CS Standard housing -
All of these models can be tted with a plug-in radio receiver.
The following housing models can be supplied:
−Housing unit with 3-button input unit CS
−Housing unit with 3-button input unit KDT
−Housing with ON/OFF key switch
−Housing with mains switch
−Housing with emergency stop button
The operating instructions describe the connection options
and programming procedures for the following models:
−CS 110 control unit with CSI buttons
−CS 110 control unit with LCD display board CS 250 / 110
General safety instructions

EN
CS 110 Door Controls / Rev. A 05 – 5
4.2 Main circuit board of the CS 110
L1
F1 = 250 mA
400V
230V
PE
- + P
F1
X16X15
X21
X18 X19
X17
X14
X1
X2
L2 L3 L1
U V WX2
X3
X13
K1
X11
X10
X9X8X7X6
X5X4
K3
X12
Key:
PE: Protective earth terminal block
X1: Mains power supply terminal
block
X2: Motor terminal block
X3: Network selection terminal block
X5: Relay terminal block
X8: Emergency stop terminal block
X9: 3-button input unit terminal
block
X11: Mechanical limit switch terminal
block
X12: Connector for RS485 devices
X14: Operating mode terminal block
X15/X16: Circuit card terminal block
X17: Radio terminal block
X18: Terminal block for buttons on
housing
X19: Terminal block for additional
shut-off system
X21: AVE RS485
K1: Relay
K3: Reversing contactor
F1: 250 mA fuse

6 – CS 110 Door Controls / Rev. A 05
5.1 General
WARNING!
To ensure that the system functions properly, the following
conditions must apply:
−The door is installed and functions properly.
−The MFZ geared motor is installed and ready for opera-
tion.
−The command and safety devices are installed and
function properly.
−The control unit housing with the CS 110 control unit is
installed.
NOTICE
The door, the MFZ geared motor and the command and
safety devices must be installed in accordance with the
relevant manufacturer’s instructions.
WARNING!
To ensure that the control unit functions properly, the
following conditions must apply:
−The supply voltage must correspond to the voltage
shown on the type plate.
−The supply voltage must correspond to the voltage of the
door operator.
−With a three-phase current supply, a clockwise rotating
eld must be ensured.
−If a permanent connection is to be made, an all-pole
mains switch must be installed.
−With a three-phase current supply, only three-pole circuit
breakers (10 A) may be used.
WARNING!
Before switching on the control unit for the rst time,
check to ensure that the cabling works are complete and
that all the motor connections are secure at both the
motor and the control unit. All control voltage inputs are
separated galvanically from the mains power supply.
5. Initial operation
5.2 Connection to the mains power supply
Detailed circuit diagram showing mains power connec-
tion (400 V / 230 V / 3-phase)
X3
230 V
X3
400 V
L3
L2
L1
400V 3~/PE
230V 3~/PE
PE
PE
PE
X1
Detailed circuit diagram showing mains power con-
nection (230 V / 1-phase)
L2
L3
L1
230V 1~/N/PE
PE
PE
PE
X1
X3
230 V
L
N
NOTICE
If the bridge is placed in the wrong position at X3, perma-
nent damage to the controls may be caused!
REFERENCE
See page 17 for technical data.

EN
CS 110 Door Controls / Rev. A 05 – 7
NOTICE
Changing the direction of rotation:
After the door operator has been connected, press the
OPEN and CLOSE buttons to check that the direction of
rotation is correct.
If the movement of the door does not correspond to the
buttons pressed, the connections at terminals U and V (or
OPEN/CLOSE) must be swapped over.
NOTICE
Safety switches of the door operator:
If the AVE Standard electronic limit switch is used, the
safety switches of the operator will be connected via the
AVE connector, which means that a bridge must be inserted
at X2:1/2.
5.3 Connection of the door operator
3-phase operator
1-phase operator
M
PE
PE
U
V
W
1
2
ab
a = Thermo switch
b = Emergency release / emergency hand chain /
emergency hand crank
X2
M
PE
PE
N
OPEN
CLOSE
1
2
ab
X2
a = Thermo switch
b = Emergency release / emergency hand chain /
emergency hand crank

8 – CS 110 Door Controls / Rev. A 05
Initial operation
5.4 Connection of limit switches
NOTICE
The limit switch settings are programmed automatically
during initial operation.
The type of limit switch used can be entered in the Input
menu.
a) Mechanical limit switches
X11
1 = Limit switch,
OPEN
2 = Limit switch,
CLOSE
3 = Pre-limit switch,
CLOSE
b) Electronic limit switch RS485
CS 110 in housing
X21
The numbers on the connector are
also the numbers of the leads:
4: Safety circuit input
5: RS 485 B
6: GROUND
7: RS 485 A
8: Safety circuit output
9: 12VDC
NOTICE
If no limit switch is connected at RS885, then the
safety circuit (4/8) must be bridged.
c) Electronic limit switches
CS 110 control unit integrated in the operator
X22 (on the plug-in circuit board)
The numbers on the connector are
also the numbers of the leads:
1: 5VDC
2: Signal 1
3: Signal 2
4: GROUND
5.5 Connection of safety devices
X8
1: Emergency stop
or door safety circuit
NOTICE
If no emergency stop is connected, the input must be
bridged.

EN
CS 110 Door Controls / Rev. A 05 – 9
3-button input unit - external button (KDT)
X9
External key switch
X9
NOTICE
If no stop system is connected at X9, then the input must be
bridged.
5.7 Connection for relay output
X5
STOP
OPEN
CLOSE
STOP
OPEN
CLOSE
5.6 Connection of command devices
CSI 3-button input unit
X12
4: Safety circuit input
5: RS 485 B
6: GROUND
7: RS 485 A
8: Safety circuit output
9: 12VDC
NOTICE
If no CSI button input unit is connected, then the
safety circuit (4/8) must be bridged.
CS 3-button input unit
X18
STOP
OPEN
CLOSE

10 – CS 110 Door Controls / Rev. A 05
Initial operation
5.8 Plug-in module
X15
X16
LED 1
LED 2
X15 X16
X22
LED 2 LED 1
NOTICE
Operation is not possible without the plug-in module.
5.9 Operating mode selector switch
X14
J1 Mode of operation for closing
direction:
Open: deadman mode
Closed: press-and-release
J2 Mode of operation for opening
direction:
Open: deadman mode
Closed: press-and-release
NOTICE
Operation with the press-and-release mode is allowed only
if the safety devices required by the regulations are in place.
5.10 Options
5.10.1 Radio receiver - CS plug-in radio system
X17
Program the transmission code:
1. Give the programming button of the receiver a short
press (holding for less than 1.6 seconds). The
programming mode will be activated. The LED of the
receiver ashes.
2. Press the channel button of your transmitter. When
the radio control system has saved the transmission
code, the LED of the receiver will light up and remain
lit for approximately 4 seconds.
5.10.2 Module - additional shut-off system
X19
Table of contents
Popular Door Opening System manuals by other brands

Normstahl
Normstahl IDO7 installation manual

Häfele
Häfele Finetta T 70 VF manual

AGS
AGS D-PL Instructions for fitting, operating and maintenance

Stanley
Stanley MA900ñ Installation and owner's manual

WITTUR
WITTUR Hydra Plus UD300 Instruction handbook

Alutech
Alutech TR-3019-230E-ICU Assembly and operation manual