Master cool 69000-220 User manual

OPERATING INSTRUCTIONS
REFRIGERANT RECOVERY SYSTEM
MODEL#: 69000 (110V/60Hz) / 69000-220 (220V/50-60Hz) / 69000-J (100V/50Hz) Japan

SAFETY INFORMATION! READ CAREFULLY BEFORE USING MASTERCOOL RECOVERY SYSTEM!
1. This equipment is designed to be used by qualified service personnel. The operator of this equipment
must be familiar with air conditioning and refrigeration systems. Do not attempt to operate this
equipment until all safety instructions and operating instructions are read and understood.
2. Always use eye protection (safety goggles) and hand protection (gloves) when working with refrigerants.
Other types of personal protective equipment should also be used.
3. All hoses used for interconnecting system should have shut off valves (manual or automatic) on both
ends. Treat all hoses and connections with caution. Hoses or connections will contain liquid refrigerant
or gas under pressure. Connect and disconnect fittings with caution.
4. Do not pressure test system with air. Some mixtures of air and refrigerant can be combustible or
explosive.
5. Recovery tank contains liquid refrigerant under high pressure. Never over fill recovery tank. Tanks
should be filled to a maximum of 80% of capacity only. Use scale only to continuously monitor the
recovery tank weight. Use only approved tanks for refrigerant recovery. An overfilled tank can explode
causing serious injury or death.
6. Do not breathe refrigerant vapors and/or lubricant vapor or mist. Breathing high concentrations of these
substances will cause severe health problems. Always use Recovery System in a well ventilated area.
7. Do not use this Recovery System in the vicinity of spilled or open containers of flammable substances
(gasoline, solvents, etc.).
8. If electrical extension cord is used, it must be 14 AWG or larger and 50 feet maximum length. If lower
amperage capacity extensions are used an over heat condition and fire hazard could occur.
9. Make sure system is electrically connected to a properly grounded power source. Always disconnect
system from power source when servicing system.
10. Some governmental agencies require licenses or certification to work with refrigerants and this
recovery equipment. Use this system only if operator has proper license or certification.
11. This recovery system is not to be used with any type flammable refrigerant or flammable gas.
12. The Recovery System includes a fine screen filter at the inlet port. Since many recovery operations
involve transferring contaminated refrigerants a filter should be used. It is recommended that an in line
suction filter be used on the inlet side of Recovery System. A recommended type is Sporlan “Catch-All”
series of proper size. Filter should be changed often.
DANGER! EXPLOSION RISK!!!
DO NOT RECOVER FLAMMABLE REFRIGERANTS
FOR DIRECT VAPOR OR LIQUID RECOVERY
(Refer to fig.1) Connect System per fig. 1 and following instructions
1. Make sure on-off switch is off, “O” pushed in. Connect system to grounded power connection.
If equipped, push “HPCO” reset button on front panel of system. This switch will “trip” (shut Recovery
System off) if Recovery System is pressurized above 38 bar (550 psi).
2. Turn INLET (blue color) valve to CLOSE position. Turn center valve (yellow color) to RECOVER position.
3. Turn OUTLET (red color) valve to OPEN position.
4. Connect the inlet and outlet hoses to the Recovery System (per fig. 1). The inlet hose should be
connected to the unit to be serviced. The outlet hose should be connected to vapor valve on recovery

tank. Recovery tank must be used on a scale that can be set to shut off refrigerant flow when tank
reaches 80% of capacity. Recovery tank must have a minimum pressure rating of 38 bar (550 psi).
5. Open the valve on the unit being serviced (feeding inlet hose).
6. Open the vapor valve on the recovery tank.
7. Turn INLET valve on Recovery System to OPEN.
8. Turn on Recovery System (push power switch “I”). If Recovery System fails to start, rotate center valve
to PURGE position. Rotate inlet valve to PURGE position. Wait about 10 seconds for pressure to equalize.
If circuit breaker has tripped, reset it. Start Recovery System.
9. Once Recovery System has started turn center valve to RECOVER position and INLET valve to OPEN
position.
10. Observe operation of system. In rare instances “slugging “ may be apparent (loud compressor noise or
high vibration). If this condition is apparent turn inlet valve to LIQUID position. System can be run with
this setting continuously. It is suggested that operator periodically turn inlet valve to OPEN position and
check for proper operation of system. Best operation of the system is with inlet valve OPEN and
automatic pressure regulating valve controlling flow conditions.
11. System has automatic vacuum shut down switch. After recovery is complete system will turn off when
inlet pressure reading is about 14 inches of mercury (-.4 bar) below atmospheric pressure. When
system shuts down automatically, turn inlet valve to CLOSE position and turn power switch off. Proceed
to “Recovery System Purge” section to purge Recovery System of remaining refrigerant.
RECOVERY SYSTEM PURGE
1. Turn off power switch. Turn inlet valve to PURGE position. Turn center valve to PURGE position. Make sure
outlet valve is in OPEN position. Start System. If system does not start due to pressure difference
between inlet and outlet, turn center valve slowly to recover position and slowly back to purge position.
The inlet and outlet pressure gauges should read the same pressure. Start system.
2. System will run until vacuum switch shuts System off automatically. Purge may take a few minutes as
some liquid refrigerant may be in the Recovery System. The liquid must become vapor, which may
require some time. System will shut-off automatically when proper vacuum level is reached.
3. Shut OFF Recovery System power switch. If system is to be used with the same refrigerant next
operation, shut outlet valve and disconnect outlet hose. If opening of Recovery System is required,
disconnect outlet hose to relieve residual pressure.
4. The inlet port has a fine screen filter. Remove inlet nut and clean or replace filter after every use. A clean
30
25
20
15
10
5
0
200
250
300
350
400
450
150
100
50
0
PSI
BAR
R134a
MC
40
60
50
70
80
30
20
10
0
190
180
170
160
150
140
130
120
110
100
90
80
70
60
40
20
0
34
0
100
90
80
70
60
50
40
30
20
10
110
130
120
140
150
350
PSI
BAR
R134a
MC
1
2
3
4
5
6
7
8
9
10
18
0
0
10
-10
-20
-30
20
30
40
10
20
-20
30
40
50
60
70
80
90
100
110
-40
F
In
Hg
VAC
10
20
30
30
25
20
15
10
5
0
0
200
250
300
350
400
450
150
100
100
90
80
70
60
50
40
30
20
10
110
130
120
140
150
350
50
0
PSI
PSI
BAR
BAR
R134a
MC
R134a
MC
40
60
50
70
80
30
20
10
0
190
180
170
160
150
140
130
120
110
100
90
80
70
60
40
20
0
34
1
2
3
4
5
6
7
8
9
10
18
0
0
10
-10
-20
-30
20
30
40
10
20
-20
30
40
50
60
70
80
90
100
110
-40
F
In
Hg
VAC
10
20
30
R

filter is very important for the proper operation of the System. See “Routine Maintenance” section.
PUSH – PULL LIQUID RECOVERY METHOD (Refer to fig. 2)
The push –pull liquid recovery technique permits recovery of large volumes of liquid refrigerant from HVAC
or refrigeration systems. The Recovery System pulls vapor from the recovery cylinder and produces high
pressure vapor that is discharged into vapor service port of system being evacuated. The liquid service port
is connected to liquid inlet on recovery tank.
Note: Recovery tank must be used with a scale that shuts of refrigerant flow when tank reaches 80% of
its capacity. When the Recovery System is started vapor from the recovery tank is compressed and sent,
at high pressure, to HVAC or refrigeration system. As pressure builds, the liquid is “pushed” out of unit into
recovery tank. Vapor from recovery tank is “pulled” out of recovery tank, compressed, and then pressurizes
unit.
Note: Some systems may not have liquid service port. This prevents the push-pull technique from being
used.
Procedure for Push-Pull technique (Connect system per fig. 2 and following instructions).
1. Connect outlet port of Recovery System to vapor port of unit to be serviced. Use hoses with automatic or
manual valves on both ends to prevent refrigerant release when disconnecting.
2. Connect liquid port on unit to be serviced to liquid port on recovery tank. Recovery tank should be on a
scale that stops flow when 80% tank capacity is reached. This connection should be made with a
manifold gauge set with sight glass to verify liquid flow. Recovery tank must have a minimum pressure
rating of 38 bar (550 psi).
3. Connect vapor port of recovery tank to inlet port of Recovery System. Use hose with automatic or manual
valve on both ends.
4. Open valves on unit to be evacuated. Open valves on recovery tank.
5. On Recovery System, rotate outlet valve to “OPEN” position. Rotate center valve to “RECOVER” position.
Rotate inlet valve to “OPEN” position.
6. Start Recovery System.
7. Check the sight glass for the presence of liquid flow. When liquid stops flowing, rotate inlet valve on
Recovery System to “CLOSED” position. When Recovery system shuts down due to vacuum, turn OFF
the power switch. Reconnect system for direct vapor recovery following instructions listed under
“Operating Guide for Direct Vapor or Liquid Recovery”.
30
25
20
15
10
5
0
0
200
250
300
350
400
450
150
100
100
90
80
70
60
50
40
30
20
10
110
130
120
140
150
350
50
0
PSI
PSI
BAR
BAR
R134a
MC
R134a
MC
40
60
50
70
80
30
20
10
0
190
180
170
160
150
140
130
120
110
100
90
80
70
60
40
20
0
34
1
2
3
4
5
6
7
8
9
10
18
0
0
10
-10
-20
-30
20
30
40
10
20
-20
30
40
50
60
70
80
90
100
110
-40
F
R
E
T
A
R
D
In
Hg
VAC
10
20
30
Liquid
Vapor
L IQ U ID
S U C T IO N P R E S S U R E D IS C H A R G E P R E S S U R E
P U R G E
P U R G E (S TA R T )IN L E T
P O W E R
CIRCUT
BREAKER
O U T L E T
C L O S E
30
25
20
15
10
5
0
200
250
300
350
400
450
150
100
50
0
PSI
BAR
R134a
MC
40
60
50
70
80
30
20
10
0
190
180
170
160
150
140
130
120
110
100
90
80
70
60
40
20
0
34
0
100
90
80
70
60
50
40
30
20
10
110
130
120
140
150
350
PSI
BAR
R134a
MC
1
2
3
4
5
6
7
8
9
10
18
0
0
10
-10
-20
-30
20
30
40
10
20
-20
30
40
50
60
70
80
90
100
110
-40
F
R
E
T
A
R
D
In
Hg
VAC
10
20
30
R
Air Conditioning
or
Refrigeration System
Recovery
System
Approved
Recovery
Tank
Use Sight Glass
or
Manifold W/Sight Glass
FIGURE 2
This manual suits for next models
2
Table of contents
Other Master cool Test Equipment manuals

Master cool
Master cool TwinTurbo 69300 User manual

Master cool
Master cool COMMANDER4000 User manual

Master cool
Master cool Black 55745 User manual

Master cool
Master cool COMMANDER1000 User manual

Master cool
Master cool 69200-220 User manual

Master cool
Master cool COMMANDER1000 User manual

Master cool
Master cool 69400-CON User manual

Master cool
Master cool 69789-220 User manual

Master cool
Master cool 43707 User manual

Master cool
Master cool COMMANDER1100 User manual