JAMA M8 User guide

Installer manual
LEK
LEK
LEK
JÄMÄ Inverter
M8, M12, M16
Air/water heat pump


Table of Contents
1 Important information 2
Safety information 2
2 Delivery and handling 6
6
6
8
9
9
Transport and storage
Assembly
Supplied components
Removing the covers
Removing the front panel
Removing the side panel 10
3 The heat pump design 11
11
General
Electrical connection 16
4 Pipe connections 19
19
19
General
Pipe coupling heating medium circuit
Docking alternatives 21
5 Electrical connections 22
General 22
Connections 24
6 Commissioning and adjusting 30
30
30
30
31
32
Preparations
Filling and venting the heating medium sys-
tem
Compressor heater
Start-up and inspection
Readjusting, heating medium side
Adjustment, charge flow 33
7 Disturbances in comfort 34
Troubleshooting 34
8 Accessories 38
9 Technical data 40
40
42
43
Dimensions and setting-out
coordinates Sound pressure levels
Technical specifications Electrical
circuit diagram 46
Item register 52
1Table of Contents |

Safety information
This manual describes installation and service proced-ures
for implementation by specialists.
This appliance can be used by children
aged from 8 years and above and per-sons
with reduced physical, sensory or mental
capabilities or lack of experience and
knowledge if they have been given
supervision or instruction concerning use
of the appliance in a safe way and
understand the hazards involved. Chil-
dren shall not play with the appliance.
Cleaning and user maintenance shall not
be made by children without super-vision.
Rights to make any design or technical
modifications are reserved.
Symbols
NOTE
This symbol indicates danger to machine or
person.
Caution
This symbol indicates important information
about what you should observe when main-
taining your installation.
TIP
This symbol indicates tips on how to facilitate
using the product.
Marking
Tee C- marksng means that Kaukora OY ensures that the
pro8uct meets all regulaticns that are placed on it based
on relevant Et dsrectives. Tee C- mark is oAlimat-cry fcr
most pro8ucts sold in the Et, regardless weere they are
made.
Serial number
The serial number for JAMA Inverter can be found on the
side of the foot.
JAMA Inverter M8
LEK
DATA
Serial number
JAMA Inverter M12
LEK
D ATA
Serial number
Chapter 1 | Important information2
1 Important information

JAMA Inverter M16
LEK
DATA
Serial number
Caution
Always give the product's serial number when
reporting a fault.
Country specific information
Installer manual
This installer manual must be left with the customer.
3Chapter 1 | Important information

Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be carried
out by a suitably qualified person. Fill in the page for information about installation data in the User manual.
DateSignatureNotesDescription
✔
System flushed
System vented
Particle filter
Shut-off and drain valve
Charge flow set
Fuses property
Safety breaker
Communication cable connected
JAMA Inverter addressed (only when
cascade connection)
Miscellaneous
Chapter 1 | Important information4

Contact information
5Chapter 1 | Important information
Kaukora Oy
PL 21, Tuotekatu 11
21200 Raisio
Puh. 02 4374 600
E-mail kaukora@kaukora.
www.kaukora.

Transport and storage
JAMA Inverter must be transported and stored vertically.
Assembly
႑ Place JAMA Inverter outdoors on a solid level base that can
take the weight, preferably a concrete foundation. If
concrete slabs are used they must rest on asphalt or
shingle.
႑ The concrete foundation or slabs must be posi-
tioned so that the lower edge of the evaporator is at
the level of the average local snow depth, al-though a
minimum of 300 mm.
႑ The JAMA Inverter should not be positioned next to sensit-
ive walls, for example, next to a bedroom.
႑ Also ensure that the placement does not inconveni-
ence the neighbours.
႑ JAMA Inverter must not be placed so that recirculation of
the outdoor air can occur. This causes lower output and
impaired efficiency.
႑ The evaporator should be sheltered from direct
wind. Place JAMA Inverter protected from wind against
the evaporator.
႑ Large amounts of condensation water as well as
melt water from defrosting can be produced. Con-
densation water must be led off to a drain or similar (see
page 7).
႑ Care must be exercised so that the heat pump is
not scratched during installation.
LEK
LEK
PLQ PP
0LQ PP
Do not place JAMA Inverter directly on the lawn or other
non solid surface.
If there is a risk of snow slip from roof, a protective roof or
cover must be erected to protect the heat pump, pipes
and wiring.
Chapter 2 | Delivery and handling
6
2 Delivery and handling

Condensation run off
Condensation water trough
The condensation water trough is used to collect and lead
away condensation water from the heat pump.
NOTE
It is important to the heat pump function that
condensation water is led away and that the
drain for the condensation water run off is not
positioned so that it can cause damage to the
house.
NOTE
Pipe with heating cable for draining the con-
densation water trough are not included.
NOTE
To ensure this function the accessory KVR 10
should be used.
NOTE
The electrical installation and wiring must be
carried out under the supervision of an author-ised
electrician.
NOTE
Self regulating heating cables must not be
connected.
Caution
If none of the recommended alternatives is
used good lead off of condensation water must
be assured.
႑ The condensation water (up to 50 litres/day) collec-
ted in the trough should be routed by pipe to an
appropriate drain, it is recommended that the
shortest outdoor stretch possible is used.
႑ The section of the pipe that can be affected by frost
must be heated by the heating cable to prevent
freezing.
႑ Route the pipe downward fromJAMA Inverter.
႑ The outlet of the condensation water pipe must be
at a depth that is frost free or alternatively indoors
(with reservation for local ordinances and regula-
tions).
႑ Use a water trap for installations where air circula-tion
may occur in the condensation water pipe.
႑ The insulation must be tight against the bottom of
the condensation water trough.
Drain pan heater, control
The drain pan heater is supplied with power when one of
the following conditions is met:
1. Operating mode "Heating" or "Hot water" is activ-
ated.
2. The compressor has been in operation for at least 30
minutes after last start.
3. The ambient temperature is lower than 1 C.
Recommended alternatives Stone
caisson
LEK
FrFrostfritost prt oof depth
If the house has a cellar the stone caisson must be po-
sitioned so that condensation water does not affect the
house. Otherwise the stone caisson can be posi-tioned
directly under the heat pump.
The outlet of the condensation water pipe must be at frost
free depth.
7
Chapter 2 | Delivery and handling

Drain indoors
Water seal
The condensation water is lead to an indoor drain
(subject to local rules and regulations).
Route the pipe downward from JAMA Inverter.
The condensation water pipe must have a water seal to
prevent air circulation in the pipe.
Gutter drainage
Frostfritt
djup
LEK
Frost proof depth
Water seal
The outlet of the condensation water pipe must be at frost
free depth.
Route the pipe downward from JAMA Inverter.
The condensation water pipe must have a water seal to
prevent air circulation in the pipe.
Installation area
The distance between JAMA Inverter and the house wall
must be at least 150 mm. Clearance in front of JAMA
Inverter should be at least one metre.
3000 mm
400 mm
Minimalt
fritt utrymme
Minimalt
fritt utrymme
Fritt utrymme
framför
150 mm
Fritt
utrymme
bakom
600mm
Minimum
free space
Minimum
free space
Free
space
behind
400 mm 600 mm
150 mm
3000 mm
Free space
in front
Supplied components
LEK
Particle filter R25 (HQ1).
2 flexible hoses (R25) with 4
seals
Chapter 2 | Delivery and handling
8
This manual suits for next models
2
Table of contents
Popular Heat Pump manuals by other brands

Mitsubishi Electric
Mitsubishi Electric PUZ-SWM60VAA Service manual

Dimplex
Dimplex LI 16I-TUR Installation and operating instruction

Carrier
Carrier WSHP Open v3 Integration guide

TGM
TGM CTV14CN018A Technical manual

Carrier
Carrier 38MGQ Series installation instructions

Kokido
Kokido K2O K880BX/EU Owner's manual & installation guide

Viessmann
Viessmann VITOCAL 300-G PRO Type BW 2150 Installation and service instructions

Carrier
Carrier 48EZN installation instructions

Viessmann
Viessmann KWT Vitocal 350-G Pro Series Installation and service instructions for contractors

Ariston
Ariston NIMBUS user manual

Weishaupt
Weishaupt WWP L 7 Installation and operating instruction

GE
GE Zoneline AZ85H09EAC datasheet