Digital Outputs
from a PLC,
Controller, etc.
TW-DA Connection Examples.
Common '0V' Input. Common '+V' Input.
TW-DA Specifications.
Digital Inputs 6 Opto-Isolated Inputs with LED Indication for each Input.
Note: All Inputs have one common that can be connected to '0V' or '+V'.
Input Voltage 6~30Vdc.
Threshold Voltage 5.5V Typical.
Load @ 6V 1mA per Channel Typical.
@ 12V 4mA per Channel Typical.
@ 20V 8mA per Channel Typical.
@ 24V 9mA per Channel Typical.
Code Binary. N.O. Contact = '0', N.C. Contact = '1'.
Analogue Outputs
- Voltage Ranges 0~10V,2~10V.
- Output Drive 5mA Maximum. (2k@ 10V.)
- MilliAmp Ranges 0~20mA, 4~20mA
- Output Drive 10V Maximum. (500@ 20mA.)
Resolution From 2 to 6 bits. (4 to 64 steps.)
PowerSupply 24Vdc±6Vdc. LED Indication of Power Supply.
Current Usage - 20mA O/P 40mA Typical at 24Vdc P/S. (No allowance for Digital Inputs.)
- 10V O/P 22mA Typical at 24Vdc P/S. (No allowance for Digital Inputs.)
Accurate to Selected Resolution <±1% FSO Typical.
Linearity&Repeatability <±1% FSO Typical.
Ambient Drift <±0.02%/C FSO Typical.
EMC Compliances Emissions EN 55022-A. Immunity EN 50082-1, <1% Effect FSO Typical.
Isolation Test Voltages Digital Inputs to Analogue Input/Outputs: 1600Vdc for 1min.
Operating Temperature 0~70C.
Storage Temperature -20~80C.
OperatingHumidity 5~85%RH Max. Non-Condensing.
Construction DIN & EN Rail Mount Enclosure.
Dimensions L=90mm, W=78mm, H=45mm.
Weight 180g (Includes Packaging).
Product Liability. This information describes our products. It does not constitute guaranteed properties and is not intended to affirm the suitability
ofaproductforaparticularapplication.Duetoongoingresearchanddevelopment,designs,specifications,anddocumentationaresubjecttochange
without notification. Regrettably, omissions and exceptions cannot be completely ruled out. No liability will be accepted for errors, omissions or
amendments to this specification. Technical data are always specified by their average values and are based on Standard Calibration Units at 25C,
unless otherwise specified. Each product is subject to the ‘Conditions of Sale’.
Warning:Theseproductsarenotdesigned for use in,andshouldnotbeusedforpatientconnectedapplications.Inanycriticalinstallation
an independant fail-safe back-up system must always be implemented.
13.07-2
0V
OUT
24V
B1 (LSB)
B2
B4
B8
B16
B32 (MSB)
COM
TW-DA
10
9
8
7
6
5
4
3
2
1
6~30Vdc
Power Supply
24Vdc
Power Supply Indicator,
PLC, etc.
0V
OUT
24V
B1 (LSB)
B2
B4
B8
B16
B32 (MSB)
COM
TW-DA
10
9
8
7
6
5
4
3
2
1
6~30Vdc
Power Supply
24Vdc
Power Supply Indicator,
PLC, etc.
Note 1. N.O. Contact is '0'
N.C. Contact is '1'
Note 2. The COM of the inputs can connected to the +ve or the -ve of the input power supply.
Note 3. Solid state outputs are recommended for powering the digital inputs. If electro-mechanical relays are used
contact bounce may cause momentary false outputs.
Note 4. The same power supply can be used to power up both the input and output of the TW-DA. Note that this will
however void the isolation between input and output.
}Code is Binary.
Digital Outputs
from a PLC,
Controller, etc.
Intech
INSTRUMENTS LTD
www.intech.co.nz