1 Mount the power supply in the desired location using the 4 mounting holes.
NOTE: For use in Indoor Protected Area with Controlled Environment only.
Do not Install Power Supply on Exterior Doors.
2 With the Mains power disconnected, connect the leads to the AC Input Terminal
Block, respecting the wiring phase and polarity :
Ground/Earth=Green/Yellow, Neutral = Blue (White), Live =Black (Brown). This
equipment must be connected to the 120-240 Volt Mains via a readily dedicated accessible
external disconnect device with maximum 15 Amp branch protection. Select the operating
3Do not connect the battery at this time.
4 Switch ON the AC. Green LED will come ON indicating AC is present and the AC
Fault Relay will be energized “ON” (closed). When the AC is off the AC Fault Relay
will drop open within 60 seconds (Factory set) activating the CMOS output
contact “AC Fail”. Connect this output to relevant monitoring devices.
5 Verify the DC output voltage is correct = 13.20VDC or 26.40VDC max. Blue DC LED
will be ON to indicate DC output is OK.
6 Yellow LED will be on and the BAT FAULT CMOS relay open indicating the Battery is
not present or connected with reversed polarity.
.
7 Connect the Battery or Batteries respecting the polarity. Battery shall not be connected
if AC is not present first.
8 If the battery is connected with the correct polarities the Yellow LED will turn OFF
(See Fault Conditions and Indications Table). Within one minute the Battery Fault Relay
will restore and the Yellow LED will flash once every 2 seconds.
9 If the battery is connected reverse polarity, the Yellow LED will be ON. (See the Table Fault).
The CMOS relay will open indicating Battery Fault. Connect this output to relevant monitoring
Installation Instructions
This power supply should be installed in compliance with National Electrical Code,
NFPA70 as well NFPA72 National Fire Alarm Code, CSA C22.1, Safety Standard
for Electrical Installations, Canadian Electrical Code, Part I, CAN/ULC-S524,
and all applicable Local Codes. Installation to be performed by suitably qualified
personnel. The power supply shall not be installed in the fail secure mode unless
permitted by the local authority having jurisdiction, and shall not interfere with the
operation of Listed panic hardware.
SW1 ON=12VDC, SW1 OFF=24VDC.
5
output DC voltage 12/24 with the jumper SW1.
devices.
10 Connect the devices to be powered to the output terminals marked “Vo- Vo+”.
11 See below for installation of PD4ECB, PD8ECB, MOM8ECB and ACM4ECB
need 2 EOLR Resistors(2K2) provided. See Fig 1 & Fig 2.
12 If Tamper Switch is required use part # TSW1-02 or TWS2-02, see Fig 3.
13 Use 2K2 EOLR (end of line resistor) Part #EORL-PWX2K2
14 Connect the fault relays to FACP or ACP for trouble indication.
15 Secure the enclosure with the screw or with the Key Lock if provided.