Haes ESPRIT-G Guide

ESPRIT-G FIRE CONTROL
EXTINGUISHING PANEL
INSTALLATION,
COMMISSIONING &
OPERATING MANUAL
This manual covers the installation, programming and commissioning of the Esprit
Extinguishing Fire Alarm Control Panels for One and Two Flood Zones.

ESPRIT Gas Extinguishing User Manual INTRODUCTION
2
Approved Document Ref: UI-ESG-01 Issue 2.0
INTRODUCTION
2797
Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD
Model Number CPR Number
ESG-1001/1002/1003/1004 2797-CPR-720738
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fire detection and fire alarm systems for buildings.
Provided Options (with requirements):
Output to fire alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1998
Power supply equipment for fire detection and fire alarm systems for buildings.
European Standard EN12094-1 : 2003
Requirements and test methods for electrical automatic control and delay devices
Haes Technologies Ltd declare that the products identified below conform to the essential
requirements specified in the Construction Products Regulation CPR305/2011/EU.
In addition, the product complies with the following:
Low Voltage Directive 2014/35/EC,
EN60950-1: 2006 Safety of information technology equipment,
Electromagnetic Compatibility Directive 2014/30/EC,
EN61000-6-3:2007 + A1:2011 Emissions, Class B,
EN50130-4: 2011 +A1:2014 Immunity, Product Family Standard.
This product has been designed to comply with the requirement of the low voltage safety and the EMC
directives. Failure to follow the instructions may compromise its adherence to this standard.

ESPRIT Gas Extinguishing User Manual INTRODUCTION
3
Approved Document Ref: UI-ESG-01 Issue 2.0
List of optional functions with requirements:
EN 12094-1: 2003
- Electrical automatic control and delay device.
- Environmental class: A
- 1 Flooding Zone
- CO2 Low Pressure
- CO2 High Pressure
- Inert gas systems
Provided options:
- 4.17 Delay of extinguishing signal
- 4.18 Monitor Flow of Extinguishing Agent
- 4.19 Monitoring od status of components
- 4.20 Emergency Hold Device
- 4.21 Control of flooding time: (60 –1800) seconds
- 4.23 Manual Only Mode
- 4.26 Triggering Signals to Equipment outside the System
- 4.27 Emergency Abort Device
- 4.30 Activation of Alarm Devices with Different Signals
EN54-2: 1997 + A1
- Control and indicating equipment for fire detection and fire alarm systems for buildings
Provided options:
- 7.8 Outputs to Fire Alarm Devices
- 7.9 Fire alarm routing
- 7.11 Delays to outputs
- 7.13 Alarm Counter
- 8.9 Fault warning routing equipment
- 10 Test Condition
EN54-4: 1998
- Power supply equipment for fire detection and fire alarm systems for buildings. Non-standard
Provided Options:
- Manual Extraction Control
- Charge during alarm
- Earth fault monitoring
- UPS Mode
- Changeable password for Level 2
- Adjustable Date & Time

ESPRIT Gas Extinguishing User Manual INTRODUCTION
4
Approved Document Ref: UI-ESG-01 Issue 2.0
Panels Model No.
Model No
Model Name
Standby
Current
Alarm
Current
ESG-1001
Esprit Ext Control Panel, Single Flood Zone, 1.2A PSU
205mA
300mA
ESG-1002
Esprit Ext Control Panel, Single Flood Zone, 3.4A PSU
205mA
300mA
ESG-1003
Esprit Ext Control Panel, Dual Flood Zone, 3.4A PSU,
Large Cabinet
207mA
365mA
ESG-1004
Esprit Ext Control Panel, Single Flood Zone, 3.4A PSU,
Large Cabinet
205mA
300mA

ESPRIT Gas Extinguishing User Manual INTRODUCTION
5
Approved Document Ref: UI-ESG-01 Issue 2.0
Contents
INTRODUCTION.....................................................................................................................................2
PRODUCT OVERVIEW..........................................................................................................................7
General Description of the Equipment ................................................................................................7
Cabinet for Single Flood Zone.........................................................................................................8
Cabinet for Two Flood Zones ..........................................................................................................8
Circuit Boards ..................................................................................................................................9
Circuit Description/Function...........................................................................................................11
Technical Specification .........................................................................................................................13
INSTALLATION CONSIDERATION .....................................................................................................17
Safety.................................................................................................................................................17
Warnings........................................................................................................................................17
Cautions.........................................................................................................................................17
ESD Precaution .............................................................................................................................18
Installing the System .........................................................................................................................18
Environment...................................................................................................................................18
Mounting the Cabinet.....................................................................................................................18
Mains Connections ........................................................................................................................19
Connecting the Batteries ...............................................................................................................19
Battery Charging Voltage Checks..................................................................................................20
Detection Zone Inputs....................................................................................................................20
Sounders / Monitored Output Circuits............................................................................................22
Relay Outputs ................................................................................................................................23
Inputs - Class Change and Pulse ..................................................................................................24
Monitored Input Wiring...................................................................................................................25
Extinguishing Actuator Output Wiring............................................................................................25
Igniting Actuators ...........................................................................................................................25
Solenoid Actuators.........................................................................................................................26
Remote Status Unit (RSU) Wiring .................................................................................................27
OPERATING INSTRUCTIONS.............................................................................................................28
Panel Control and Indicators.............................................................................................................28
Control Panel .................................................................................................................................28
User Controls.....................................................................................................................................32
General User Controls ...................................................................................................................32
Authorized User Controls...............................................................................................................33
Engineer Controls ..........................................................................................................................34
Panel Alarm Conditions.....................................................................................................................36
Fire Alarm Condition ......................................................................................................................36
Activated/Released Condition........................................................................................................36
Hold Condition ...............................................................................................................................39
Abort Condition..............................................................................................................................39

ESPRIT Gas Extinguishing User Manual INTRODUCTION
6
Approved Document Ref: UI-ESG-01 Issue 2.0
Fault Condition...............................................................................................................................39
CONFIGURING THE SYSTEM.............................................................................................................41
Accessing the Menu Structure...........................................................................................................41
Learn System ....................................................................................................................................42
Set Common Output for HOLD & ABORT.........................................................................................44
User Menu.........................................................................................................................................46
User Menu: AUTO/MANUAL MODE Menu ...................................................................................46
User Menu: DISABLE....................................................................................................................47
User Menu: Time & Date ...............................................................................................................48
User Menu: LAMP TEST ...............................................................................................................49
User Menu: Contrast......................................................................................................................49
User Menu: BUZZER.....................................................................................................................50
User Menu/sub-menu Breakdown .................................................................................................51
CONFIG Menu...................................................................................................................................53
CONFIG Menu: PANEL.................................................................................................................54
CONFIG Menu: GAS CARD..........................................................................................................57
CONFIG Menu: DEVICES.............................................................................................................58
CONFIG Menu: P-BUS..................................................................................................................61
CONFIG Menu: PSU......................................................................................................................61
CONFIG Menu/sub-menu Breakdown...........................................................................................62
CONTROL Menu...............................................................................................................................68
Control Menu: EXTRACT ..............................................................................................................68
Control Menu: FLOODING ............................................................................................................69
Control Menu: DELAYS.................................................................................................................69
CONTROL Menu/sub-menu Breakdown.......................................................................................70
Report Menu......................................................................................................................................71
Report Menu: ALARM....................................................................................................................71
Report Menu: FAULT.....................................................................................................................72
Report Menu: DISABLE.................................................................................................................73
Report Menu: OTHER....................................................................................................................74
Report Menu: HISTORY................................................................................................................75
Report Menu: Versions..................................................................................................................76
Report Menu: COUNTER ..............................................................................................................76
Report Menu: Gas Card.................................................................................................................77
Report Menu: PSU Card................................................................................................................77
Report Menu: BATTERY................................................................................................................77
Report Menu/sub-menu Breakdown..............................................................................................79
ENG Menu.........................................................................................................................................83
ENG Menu: TEST..........................................................................................................................83
ENG Menu: MISC..........................................................................................................................85
ENG Menu/sub-menu Breakdown.................................................................................................86
SERVICE & MAINTENANCE................................................................................................................87

ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW
7
Approved Document Ref: UI-ESG-01 Issue 2.0
PRODUCT OVERVIEW
General Description of the Equipment
The ESPRiT-G extinguishing gas panel acts as both a conventional fire alarm panel and an automatic
extinguisher control panel and was designed from the ground up to be intuitive and flexible for the
engineer. The panel is easy to install and programme and incorporates a large 240 x 64-pixel graphical
LCD display, with an easy-to-navigate menu system, which contains simple discernible icons in each
section.
In-built safety features ensure the client’s employees and assets are protected to the highest degree
with the minimum risk.
The panels are available in One Flood Zone (three Conventional Detection Circuits), and Two Flood
Zones(six conventional detection circuits), and hence will be presented in two different enclosure sizes.
The Gas panel can be powered by either; 35W, 1.2 Amps (for 1 Flooding Area), or 100W, 3.4 Amps
(for 2 Flooding Areas), switch mode PSU’s, rated at 230VAC, 50/60Hz.
The panel also offers optional Output Expansion Relay Board providing additional volt-free relay
outputs.
The panel supports connections for up to Sixteen Remote Status Units (RSU), or up to Sixteen
Economy Remote Status Units (EcoRSU).
This product has been designed and manufactured in the United Kingdom.

ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW
8
Approved Document Ref: UI-ESG-01 Issue 2.0
Cabinet for Single Flood Zone
Cabinet for Two Flood Zones

ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW
9
Approved Document Ref: UI-ESG-01 Issue 2.0
Circuit Boards
2827-206 DISPLAY CARD & 2972-206 EXTENSION LEDs CARD (2nd Flood Zone)

ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW
10
Approved Document Ref: UI-ESG-01 Issue 2.0
2879-206 PSU CARD & 2883-206 GAS CARD
Table of contents
Other Haes Control Panel manuals

Haes
Haes ESENTO MARINE Guide

Haes
Haes ELAN HS-5100 User manual

Haes
Haes ESG-2001 Guide

Haes
Haes AOV Series Guide

Haes
Haes MZAOV-1001 Guide

Haes
Haes AlarmSense Guide

Haes
Haes Excel-32 Series Guide

Haes
Haes AlarmSense PLUS User manual

Haes
Haes ELAN HS-5000 Series User manual

Haes
Haes FUSION 0832-CPD-1431 User manual