Gemini Tinytag TGE-0003 User manual

Tinytag Energy Logger
Technical Manual

02

01 Contents 03
02 Warnings and PAT Testing Instructions 04
03 Introduction 06
04 In the Case 07
05 Controls and Connections 08
06 Logger Display 09
07 Logger Markings 10
08 Quick Start 12
Modes of Operation:
09 Single Phase Current 14
10 Three Phase Current 15
11 Single Phase Current and Voltage 16
12 Three Phase Current and Voltage 17
12.1 Positioning Coils 19
12.2 Screen Messages 22
12.3 Manual Conguration 24
13 Data Logging 27
14 Tinytag Explorer 28
15 What Does the Logger Record? 34
16 How the Energy Logger Works 36
17 Logging Specication 38
18 Measurement Specication 39
19 Physical Specication 40
20 Maintenance and Service Instructions 41
21 Battery Information 42
22 Approvals and Warranty 43
Contents
03

Important Safety Information. Read the following warnings
carefully before installing or operating the Energy Logger.
• The logger must only be used as intended and in accordance
with the instructions in this manual. Failure to do so may
impair the safety features of the logger.
• Never attempt to use the logger or accessories if they appear
to be damaged or malfunctioning. Disconnect the mains
supply and contact your supplier.
• The logger is for indoor use only. Do not use in damp or wet
environments.
• Installation of this logger may expose the operator to
hazardous voltages. If in doubt, refer to a qualied electrician.
• The mains input of the logger (see page 6) must only be
connected to an AC mains socket using the supplied lead. Do
not exceed the maximum rated input voltage for the logger.
• The current measurement inputs must only be connected
to approved exible coil current transducers, Gemini part
number ACS-002X. Any other type of connection may
damage the logger and expose the user to hazardous
voltages.
• An earthed mains connection is required for correct
operation, not for device safety.
• When changing batteries, make sure the mains lead is
removed from the logger.
• Only use 4 x Alkaline AA batteries, observing the correct
polarity.
• The logger must only be operated with the battery cover
tted.
• The logger contains no user-serviceable parts. Do not
open (except to remove the battery cover when replacing
batteries).
• The logger contains hazardous voltages and a lithium battery.
Servicing must be carried out by an authorised service centre
only. Please contact your supplier for further information.
02 Warnings & PAT Testing Instructions
04

• This equipment should be used within the temperature range
and other environmental conditions specied in this manual.
• Voltage Range 230V ±10%
• Mains Transient Overvoltage Category II, 2.5kV
• Measurement Category IEC61010: 2001 CAT II
• Operating Temperature 0 to +50°C
• Maximum RH 95% (non-condensing)
• Maximum Altitude 3000m
This logger is tted with a magnet.
• Keep away from pacemakers
• Keep away from iPods and hard drives
• Keep at least 10mm from credit cards
If the magnet is removed from the logger:
• There is a danger it will shatter if it makes a sudden contact
with a hard surface.
• Keep away from children, this magnet is not a toy.
Portable Appliance Testing - Flash Test
• Do not Flash Test this product at more than 3000v RMS.
• Due to EMC ltering components within the product, the
leakage current at the ash test voltage may be up to 10mA &
register as a fail on some PAT testers.
05

The Tinytag Energy logger combines the level of performance
required by experts with the level of simplicity required by those
that are new to energy management.
The logger is ideal for monitoring building energy supply,
sections within a building or individual pieces of equipment.
Data from the Tinytag Energy Logger can be used to identify
power-hungry or inecient equipment and peak load times,
and can highlight equipment that is left powered up or idling
unnecessarily.
The Tinytag Energy Logger provides visibility of energy usage so
that eective measures can be taken to reduce electricity bills,
lower carbon footprint and improve environmental performance.
• Simple to use
• High accuracy
• Non-invasive
• Small size/lightweight
• Reduce energy costs
• Reduce carbon foot print
• Can be used straight out of the box
• Track down inecient pieces of equipment
03 Introduction
06
Warning!
Text marked with this symbol is important
information, vital to the correct and safe
usage of this data logger. Please read these
warnings carefully.
Disclaimer
The information presented in this document has been carefully
checked for reliability; however, no responsibility is assumed
for inaccuracies. The information in this document is subject to
change without notice.

04 In the Case
07
The following items are supplied in the carry case:
• 1 x Tinytag Energy Logger
• 3 x Clip on coils
• 1 x Tinytag Explorer software
• 1 x UK mains lead
• 1 x EU mains lead
• 1 x USB cable
• 1 x User Manual

05 Controls and Connections
08
3
4
1
5
2
1. PC interface connection (USB “B” Socket)
2. Mains input
3. Display
4. Control buttons
5. Coil connections (for ACS-002X coils)
Buttons
Function: Allows you to step through the dierent
wiring congurations the logger supports
Record: Starts and stops the
data logger recording
Scroll: Allows you to scroll through current,
voltage and power readings from the logger

06 Logger Display
09
1
2
3
1. Wiring Conguration
This shows the dierent wiring congurations supported by the
logger. To step though them, press the Function button.
2. Prompts and Error Messages
When a wiring conguration is selected, the logger will show
prompts in this area of the display to tell the user what needs to
be plugged in next. This area of the display is also used to display
error messages.
3. Current Readings
Current, voltage, power and power factor information is displayed
here. To step through them, press the Scroll button.

07 Logger Markings
10
CE
This equipment meets the requirements of
the EMC Directive and Low Voltage Directive
of the European Union.
A Declaration of Conformance for this product
is available upon request, please contact your
supplier for further information.
WEEE
Data loggers, accessories and batteries should
be disposed of at organised facilities, where
available, in line with local regulations.
In accordance with the WEEE directive Gemini
Data Loggers (UK) Ltd. will take back and
dispose of any equipment purchased directly.
Equipment not purchased directly should be
returned to the point of sale for disposal.
WARNING!
Observe the text of any warning messages
associated with this symbol.
Table of contents
Other Gemini Test Equipment manuals