Fbt LIGHT User manual

VAIE 5500
FBT ELETTRONICA S.p.A. - Via Paolo Soprani, 1 - ZONA IND. SQUARTABUE - 62019 RECANATI (MC) - ITALY
INSTRUCTIONS FOR USE
VAIE 5502 500W / 2 ZONES
“LIGHT” Wall-mounted
voice evacuation system


3
VAIE 5500 EN
TABLE OF CONTENTS
1. WARNINGS 4
1.1. Power supply and earthing 4
1.2. Safety notes 4
2. INTRODUCTION 5
2.1. Overview of the system 5
2.2. Functional features 5
3. GENERAL DESCRIPTION 6
3.1. Front panel 6
3.2. Inside view 7
4. INSTALLATION AND CONNECTIONS 8
4.1. Wall mounting 8
4.2. Connections 9
4.2.1 Connection of emergency units 10
4.2.2 Connection of music input 10
4.2.3 Connection of input contacts 11
4.2.4 Connection of relay output 11
4.2.5 Connection of loudspeaker lines 12
4.2.6 Connection of standby amplifier 12
4.2.7 Connection of power supplies 13
5. OPERATIONAL CONDITIONS AND TERMINOLOGY 14
5.1. Signalling of operating conditions 14
6. DEFINITIONS 14
7. MENU STRUCTURE 15
8. USING THE SYSTEM 16
8.1. Configuration of the system 17
8.2. < MUSIC > Menu 20
8.3. < AUDIO SETTING > Menu 21
8.4. < INSPECTION > Menu 23
8.5. < OPERATOR > Menu 26
8.6. < CONFIGURATION > Menu 29
8.7. MANUAL emergency – < EMERGENCY > Menu 37
8.8. AUTOMATIC emergency (alarm status activated by an external peripheral unit) 39
9. FAILURE STATUS 40
9.1. System operation and signalling in a generic failure condition 40
9.2. System operation and signalling with a fault on a loudspeaker line 40
10. TECHNICAL SPECIFICATIONS 41

4
VAIE 5500
EN
1. WARNINGS
1.1 POWER SUPPLY AND EARTHING
These items of equipment are intended to work on a 230 VAC +10% / -15%, 50/60 Hz mains voltage and a 24 VDC supply from
the internal batteries.
! N.B. – FEATURES OF THE WIRING SYSTEM
The mains AC power MUST be supplied through a two-pole differential thermal-magnetic circuit breaker with a current
of 10 to 16A dedicated SOLELY to the equipment.
!N.B.
These devices have been designed to be connected to an earthed power supply.
Make sure that the equipment is always connected to earth in accordance with legal regulations.
1.2 SAFETY NOTES
All FBT equipment is made according to the strictest international standards and complies with European Union requisites.
For correct and effective use of the equipment it is important to be aware of all the characteristics by reading carefully these
instructions and warnings. While the equipment is in use, it is necessary to ensure adequate ventilation, above all leaving the slits
for providing air for the cooling fans free.
REFER TO THE ‘INSTALLATION AND CONNECTIONS’ SECTION FOR THE RELEVANT PROCEDURES, TO BE CARRIED
OUT BY TRAINED SPECIALISED PERSONNEL ONLY.
Important information for correct disposal of the product in accordance with EC Directive 2002/96/EC
his product must not be disposed of as urban waste at the end of its working life. It must be taken to a special waste
collection centre licensed by the local authorities or to a dealer providing this service. Separate disposal of electric
and/or electronic equipment (WEEE) will avoid possible negative consequences for the environment and for health
resulting from inappropriate disposal, and will enable the constituent materials to be recovered, with significant savings
in energy and resources. As a reminder of the need to dispose of this equipment separately, the product is marked
with a crossed-out wheeled dustbin.
This product is in keeping with the relevant European Community Directives.

5
VAIE 5500 EN
2. INTRODUCTION
2.1 OVERVIEW OF THE SYSTEM
The VAIE 5500 range includes “light” voice evacuation systems for emergency facilities, designed specifically for wall-mounting
and equipped with control units, certified in compliance with EN 54-16:2008 / EN 54-4 standards. The VAIE 5502 model is
capable of managing 2 zones, each driven by a single amplifier, as well as remote microphone stations and controlled inputs to
be connected to a central fire-fighting system.
2.2 FUNCTIONAL FEATURES
•
Rated audio output: 500 W overall, distributable freely among the 2 zones with a maximum limit of 250 W per single zone.
•
Backlit 4.3” display with touch screen for selecting the alert and evacuation zones and enabling navigation for adjusting
volume levels, configuring the equipment and viewing failures.
•
Handheld fireman’s paging microphone.
•
Sending out of pre-recorded EVACUATION and ALERT messages.
•
7 off controlled input contacts, configurable for playing the evacuation and/or alert messages to the programmed zones or
for resetting the messages.
•
One off music input for sound sources.
• One
off configurable relay outputs.
•
Double A+B output for each zone.
•
Protected local button for placing the system in an emergency state, equipped with its own LED.
•
Local button for resetting the fault acoustic signal and stopping playing out of alarm messages.
•
Background music and calls of a general nature can be played through microphone stations.
•
Up to 4 FMD remote emergency units can be connected.

6
VAIE 5500
EN
3. GENERAL DESCRIPTION
3.1 FRONT PANEL
1) Backlit 4.3” display with touchscreen for selecting the Alert/Evacuation zones and for navigation for adjusting volume levels,
configuring the equipment and viewing failures.
2) Integrated loudspeaker for playing back the output signals from the zones or the signals of the input sources and for
replaying the acoustic signal indicating that a failure has been detected (beep). The signalling tone will be automatically
muted if the conditions of failure end. Furthermore, in accordance with the regulations, the beep is muted by the system
while the Emergency Microphone is being used.
3) Handheld fireman’s paging microphone.
4) RESET button.
5) EMERGENCY button.
6) Status LEDs.

7
VAIE 5500 EN
7) 7 off controlled input contacts.
8) 1 off relay output contact.
9) Input for emergency microphone stations (max. 4).
10) Input terminal strip for music sources.
11) Connection to 230 VAC power supply.
12) Connection to 24 VDC battery power.
13) Connection of loudspeaker (zone 1).
14) Connection of standby amplifier.
15) Connection of loudspeaker (zone 2).
3.2 INSIDE VIEW

8
VAIE 5500
EN
4. INSTALLATION AND CONNECTIONS
!N.B.
Please remind that the operations illustrated in this part of the manual must be carried out by specialised personnel
ONLY, trained and qualified in the equipment installation and maintenance. When the VAIE 5500 is opened, parts entailing
a high risk of electric shocks become accessible.
It is advisable to install the equipment in a closed and sheltered place, protected against possible sources of damage (rain,
moisture, high temperatures, etc.).
Depending on requirements, the cables can be inserted by eliminating either the plugs sealing the holes in the top or the rear door
(in both cases use a flat screwdriver or a cutter to lift them and remove them).
!It is important to keep the power cables separate from those dedicated to the other connections.
4.1 WALL MOUNTING
Take the cardboard template included in the package and position it
at a suitable height so that it is accessible to the user. Ideally, the front
display should be at eye level.
Having decided on the position, mark the five points on the wall, drill
the holes and fit Fischer wall plugs (min. Ø 9 mm) equipped with bolts
into them.
Using the wall plugs as reference pins, lift the equipment and hook it to
the wall. It is advisable for this activity to be carried out by two people.
Tighten the bolts.

9
VAIE 5500 EN
4.2 CONNECTIONS
!N.B.
Check that the main thermal-magnetic circuit breaker is switched OFF.
If it is not, switch it OFF before carrying out any other activities in the cabinet as there is a danger of electric shocks.
Proceed with connection of the various devices, referring to the appropriate points of the manual:
CPU circuit
A) Point 4.2.1 Connection of emergency units (page 10)
B) Point 4.2.2 Connection of music input (page 10)
C) Point 4.2.3 Connection of input contacts (page 11)
D) Point 4.2.4 Connection of relay output (page 11)
AMPLIFIER circuit
E) Point 4.2.5 Connection of the loudspeaker lines (page 12)
F) Point 4.2.6 Connection of the standby amplifier (page 12)
Once the basic connections have been made, it is possible to go on to connect the power supplies:
G/H) Point 4.2.7 Connection of power supplies (page 13)
!N.B.: It is essential to follow the correct sequence for powering up the equipment, failing which it could be
damaged.

10
VAIE 5500
EN
4.2.1 CONNECTION OF EMERGENCY UNITS ΊCPU CIRCUIT
Use a CAT. 5e SF/UTP cable for connecting the EMG. DESK socket (9) to the ‘IN/OUT’ sockets of the remote emergency units
FMD range (max 4).
4.2.2 CONNECTION OF MUSIC INPUT ΊCPU CIRCUIT
The MUSIC terminals (10) are available for connecting outside music sources (CD player, tuner etc.).
This manual suits for next models
1
Table of contents
Popular Safety Equipment manuals by other brands

Innova
Innova Xtirpa Instruction and safety manual

bolle SAFETY
bolle SAFETY B810 quick start guide

SHENZHEN FANHAI SANJIANG ELECTRONICS
SHENZHEN FANHAI SANJIANG ELECTRONICS A9060T instruction manual

Hiltron security
Hiltron security POWER8E Installation and use manual

Hatco
Hatco B-950P installation guide

Sitec
Sitec TX MATIC operating manual