ETC Sensor+ SR+ Series User manual

Part Number: 7141M2300 Rev: C
Released: 2021-03
Sensor+
Enclosure (SR+/HSR+ Series)
CEM
+
to CEM3 Retrofit Manual

Introduction 1
Introduction
This manual is intended to guide ETC Service Technicians
through the process of upgrading existing Sensor+
enclosure installations to Sensor3 enclosures with a CEM3
control module. This manual covers SR+ or HSR+ 6, 12, 24
and 48 permanent installation enclosures.
If you purchased this retrofit kit as part of a power
package, see support.etcconnect.com/Source_Articles/
ETC/Power_Controls/General/ETC_Upgrades_Program or
scan the QR code to the right for more information.
Overview of this Manual
•
Preparation (page 5)
: Before you open the enclosure
•
Remove the Old CEM (page 6)
: Label and remove the existing equipment
•
Attach New Power Harness (page 7)
: Adapt and connect the power harness for the new
backplane
•
Install the New Backplane (page 9)
: Transfer the wiring and install new components
•
Change out the AF Cards (if present) (page 11)
: Remove the existing Advanced Feature cards and
install the new ones
•
Change out the Beacon PCB (page 11)
: Replace the existing beacon primary circuit board (PCB)
with the new one
•
Enclosure Door (page 12)
: Replace the beacon acrylic in the door and replace the enclosure label
•
Verify the Retrofit (page 12)
: Put the dimmers back in the enclosure and power up the enclosure
•
Configure the CEM3 (page 13)
: Program a configuration for the CEM3
•
Final Steps (page 13)
: Clean up waste and archive CEM3 configuration

2CEM3 Sensor+ Rack Retrofit Manual
Document Conventions
This document uses the following conventions to draw your attention to important
information.
All ETC documents are available for free download from our website: etcconnect.com.
Safety
Please note the following safety warnings before use:
• Disconnect power from the enclosures before all maintenance.
Note:
Notes are helpful hints and information that is supplemental to the main
text.
CAUTION:
A Caution statement indicates situations where there may be
undefined or unwanted consequences of an action, potential for
data loss or an equipment problem.
WARNING: A Warning statement indicates situations where damage may occur,
people may be harmed, or there are serious or dangerous
consequences of an action.
WARNING: RISK OF ELECTRIC SHOCK! This warning statement indicates
situations where there is a risk of electric shock.
WARNING:
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power
to the dimmer rack before working inside could result in serious
injury or death.
AVERTISSEMENT :
RISQUE DE MORT PAR ÉLECTROCUTION! Travailler à l’intérieur du
rack de gradation sans avoir déconnecté le courant peut entrainer
des blessures graves, voire mortelles.
De-energize main feed to the dimmer rack and follow appropriate
Lockout/Tagout procedures as mandated by NFPA 70E. It is
important to note that electrical equipment such as dimmer racks
can present an arc flash hazard if improperly serviced. This is due to
the high amounts of short-circuit current available on the electrical
supply to this equipment. Any work must comply with OSHA Safe
Working Practices.

Introduction 3
Help from ETC Technical Services
If you are having difficulties, and your problem is not addressed by this document, try the ETC
support website at support.etcconnect.com or the main ETC website at etcconnect.com. If
none of these resources are sufficient, contact ETC Technical Services directly at one of the
offices identified below. Emergency service is available from all ETC offices outside of normal
business hours.
When calling for help, take these steps first:
• Prepare a detailed description of the problem
• Go near the equipment for troubleshooting
• Find your notification number if you have called in previously
ETC, Inc.
Americas
Technical Services Department
3031 Pleasant View Road
Middleton, WI 53562
800-775-4382 (USA, toll-free)
+1-608 831-4116
ETC GmbH
Germany, Austria, Switzerland, Eastern
Europe, and Russia
Technical Services Department
Ohmstrasse 3
83607 Holzkirchen, Germany
+49 (80 24) 47 00-0
techserv-germany@etcconnect.com
ETC Austin
High End Systems Products
Technical Services Department
2105 Gracy Farms Lane
Austin, TX 78758 USA
800-890-8989 (USA, toll-free)
+1-512 836-2242
ETC France
France
Zone Urbaparc -
Bâtiment E
6 Boulevard de la Libération
Saint-Denis, 93200
+33 1 4243 3535
ETC Ltd
Europe, Middle East, and Africa
Technical Services Department
26-28 Victoria Industrial Estate
Victoria Road,
London W3 6UU England
+44 (0)20 8896 1000
ETC Asia
Asia
Technical Services Department
Room 1801, 18/F
Tower 1, Phase 1 Enterprise Square
9 Sheung Yuet Road
Kowloon Bay, Kowloon, Hong Kong
+852 2799 1220

4CEM3 Sensor+ Rack Retrofit Manual
Unpack and Organize
The table below lists the parts and components needed to retrofit a Sensor+ rack (SR+ or HSR+ 6, 12,
24, or 48) to become a Sensor3 rack with a CEM3.
Bag Parts/Components
ETC Part Number
SR+Enclosure
7141K1101
HSR+ Enclosure
7141K1004
1
CEM+ to CEM3 Backplane Power Adapter
Harness
7141B7007
11
Cable tie 4" Hi-temp Black
HW7121 88
Tie-mount (sticky-back)
HW741 44
Sensor3 Beacon Door Acrylic
7141A4050 11
2
Screw 6-32 X 3/8 Ph PH MS CP W/Patch
HW222 3 3
Screw 8-32 X 3/8 Ph PH MS CP W/Patch
HW377 3 3
CEM3 Backplane 1/8” #8 screw spacer
HW9343 3 3
3CEM3 Beacon Assembly
7140B5620 11
-
Sensor3 ESR/HSR Install Enclosure Backplane
Assembly
7144A2100-CFG
- 1
-Sensor3 SR Install Enclosure Backplane Assembly
7141A2103-CFG 1 -
-Sensor3 Installation Rack Door Label
7141A4049 1 1
Additional Items
Sensor3 AF Card (Optional)
7150B5623 up to 4*
CEM3
7140A1000 1
Required Tools
#1 Phillips screwdriver
#2 Phillips screwdriver
1/4” flat head screwdriver
Diagonal wire cutter
Permanent marker
Wire strippers

The Retrofit 5
The Retrofit
Preparation
1: Use the Sensor+ Connect web interface to download and save the current configuration out of
the CEM+ for later reference. Instructions on saving your configuration from this interface can
be found in any CEM+ Software Release Note or any CEM+ Configuration Manual available for
download at etcconnect.com.
2: Turn off main power to the enclosures.
3: Remove the eight dimmer modules above the CEM+ (if retrofitting an SR+48 rack, remove the
eight modules below the CEM+ as well). Note and document the modules’ order/positioning in
the enclosure for proper insertion and configuration later.
4: Use a digital voltmeter and VERIFY that power is off by checking voltages for all combinations
between the phase bars, neutral and ground.
5: Remove the CEM+ from the rack.
WARNING:
RISK OF DEATH BY ELECTRIC SHOCK! Power down the rack before
removing the CEM3. Only remove modules with the rack powered off,
following these instructions or as instructed by ETC Technical Services.
AVERTISSEMENT :
RISQUE DE MORT PAR ÉLECTROCUTION! Mettez le rack de gradation
hors tension avant de retirer le CEM3. Ne retirez les modules de
gradation ou de contrôle que lorsque le rack est éteint, en suivant ces
instructions ou selon les instructions des services techniques ETC.
Removing modules exposes the phase bars inside of the rack. When the
rack is powered on, phase voltages inside the rack can cause injury or
death. When the rack is powered on, modules should only be removed
by qualified installers or electricians.
WARNING:
RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to
the dimmer rack before working inside could result in serious injury or
death.
AVERTISSEMENT :
RISQUE DE MORT PAR ÉLECTROCUTION! Travailler à l’intérieur du rack
de gradation sans avoir déconnecté le courant peut entrainer des
blessures graves, voire mortelles.
De-energize main feed to the dimmer rack and follow appropriate
Lockout/Tagout procedures as mandated by NFPA 70E. It is important to
note that electrical equipment such as dimmer racks can present an arc
flash hazard if improperly serviced. This is due to the high amounts of
short-circuit current available on the electrical supply to this equipment.
Any work must comply with OSHA Safe Working Practices.

6CEM3 Sensor+ Rack Retrofit Manual
Remove the Old CEM
1: Disconnect the multi-colored DMX ribbon cable and Cat5 cable from the backplane.
2: Disconnect the power cable from the rear of the CEM+ backplane.
3: Disconnect the dimmer output ribbon cables from the backplane. As you remove the ribbon
cables, mark them with a permanent marker to indicate the proper order for reattachment
(Dimmers 1–24, 25–48, and so on). There may be stickers on the ribbon cables already, however
these may refer to cable length and not dimmer outputs. They should not be used as a reference
to these instructions.
4: Unscrew the backplane metal from the enclosure. (One screw in each side upper-corner - two
screws total.) Discard these screws. Replacement screws with thread locker are provided
(ETC Part# HW377) and will be used later.
5: Push the backplane towards the back of the enclosure to free the backplane side tabs.
6: Bend the sides in towards the center (out of the sides of the enclosure).
7: Pull one side forward to angle the backplane then remove the backplane metalwork from the
enclosure. Discard the old backplane.
6
88
9
7
Remove the
backplane screws

The Retrofit 7
Attach New Power Harness
1: Connect the old power connector to the new power harness adapter found in the kit. The
connectors are keyed - the power connectors only fit one way.
2: Run the green ground wire from the power harness adapter between the bus bar and the
enclosure wall avoiding any interference with other wires in the enclosure.
3: Carefully route the ground wire to any open terminal in a grounding strip inside the enclosure.
Grounding terminal screws can be loosened or tightened with a flat-blade or square drive
screwdriver.
4: Use a wire tie to secure the ground wire to the wires that travel from the mated power harness
connectors.
New Power Harness
Run Ground behind bus bar Secure Ground in rack
ground terminal

8CEM3 Sensor+ Rack Retrofit Manual
Backplane Settings
Upgrade kit backplanes ship from the factory with all DIP switches in the off (down) position. You will
have to set the DIP switches on the new backplane to match your rack. You will also have to verify the
termination switch settings.
1: Set the DMX termination switches for each port to "Off" unless the port is the last position in
the DMX chain.
• If there are both DMX In and Thru connections to the port, the enclosure is not last in the
chain. DMX Thru connections can be made either using two pairs of wires in one terminal
block, or using the DMX Thru connector.
• If there is only one set of DMX wires in the connector and the DMX Thru is not used, the
enclosure is the last in the chain.
• If there is no DMX wire connected, leave the termination switches off.
2: Using a precision screwdriver, set the DIP switches to match your enclosure type according to:
• number of modules (6, 12, 24, or 48)
• whether the enclosure has Advanced Features (AF)
Use the following chart to determine your required DIP switch settings:
“On” position = switch pushed to the top
DIP switch Number
EnclosureModel 12345678
SR3-6 On On
SR3-6AF On On On
SR3-12 On
SR3-12 AF On On
SR3-24 On
SR3-24 AF On On
SR3-48
SR3-48 AF On
Set termination to “Off”
(middle position) Set DIP switches
This manual suits for next models
9
Table of contents
Other ETC Enclosure manuals

ETC
ETC OneTrack Backbone I-coupler Housing User manual

ETC
ETC OneTrack Backbone End Feed Housing User manual

ETC
ETC 7180A1018 User manual

ETC
ETC OneTrack Backbone T-coupler Housing User manual

ETC
ETC 7180A1018 User manual

ETC
ETC DRd6-12-120 User manual

ETC
ETC Unison AX Series User manual

ETC
ETC Unison ERn2-W User manual