10 -60
HHP - Reversible air-water heat pump
Installation, use and maintenance manual
HF61GJ0181C
- Before performing any work on the unit, each operator must be perfectly aware of how the
unit and its controls work and must have read and understood all the technical information
in this manual.
- It is forbidden to use the unit in conditions or for purposes other than those stipulated in this manual and THE
MANUFACTURER cannot be liable for faults, issues or accidents due to non-compliance with this prohibition.
- Do not repair the high pressure pipes by welding them.
- It is prohibited to tamper with, alter or modify, even partially, the systems or equipment referred to in the
instructions manual, particularly the guards and symbols regarding personal safety.
- It is also prohibited to disregard the instructions or the required safety operations.
- Safety guidelines, together with general information provided in this manual, are particularly important.
WARNING
Each unit is distinguished by an identication label on the
frame, which bears all the data required for installation,
maintenance and unit traceability. Take note of the model,
serial number, the denitive refrigerant charge and the
reference drawings of the unit enclosed with this manual,
in order to be easily retrieved in the event the data plate
deteriorates and maintenance is required.
1.5 IDENTIFICATION OF THE UNIT
Modello - Model HHP0XXH
Matricola - Serial number HFXXXXXXXXXX
Codice ID - Code ID
Data di produzione - Date of production 22/08/17
Categoria PED/ 2014/68/EU Category II
Procedura di valutazione conformità - Conformity module D
Max pressione ammissibile PS - Max allowable pressure PS[bar-r] 41,5
"Max pressione esercizio lato bassa pressione PS
Max allowable pressure low pressure side PS [bar-r]"
41,5
Max/Min temp. di stoccaggio - Max-Min storage temperature [°C] +42 / -20
Max/Min.temp.amb. di funzionamento-Max/Min amb.working
temp.[°C]
+42 / -20
Potenza frigorifera* - Cooling Capacity* [ kW ]
EER*
Potenza termica* - Heating Capacity* [ kW ]
COP*
Refrigerante - Refrigerant [Ashrae 15/1992] / GWP R410A/2088
Carica refrigerante - Refrigerant charge [kg] C1 C2 C3 C4
(1*) - - -
Refrigerante aggiunto - Refrigerant added [kg] C1 C2 C3 C4
(2*) - - -
Carica totale - Total Charge [kg] (2*)
"Tonnellate di CO2 equivalenti
Tonnes of CO2 equivalent"
Taratura press. lato ALTA - HIGH pressure Switch Set [bar-r] 41,5
Taratura press. lato BASSA - LOW pressure Switch Set [bar-r] -
"Taratura valvola sicurezza refrigerante
Safety valve refrigerant Set [bar-r]"
-
"Massima pressione esercizio circuito acqua
Max working pressure water circuit [bar-r]"
5
"Taratura valvola sicurezza acqua
Safety valve water side Set [bar-r]"
-
Alimentazione Elettrica- Power supply 400V/3ph+N/50Hz
Potenza massima assorbita - Max. absorbed power [kW] 15,6
Corrente massima - Full load ampere FLA [A] 32
Corrente di spunto - Starting Current LRA [A] /
Schema elettrico - Wiring diagram HF620Axxxx
Schema frigorifero - Refrigeration diagram HF630Axxxx
Peso a vuoto - Empty weight [kg] 260
"* EN14511-2
Contiene gas uorurati ad eetto serra disciplinati dal protocollo di Kyoto
Contains uorinated greenhouse gases governed by the Kyoto protocol
Ermeticamente sigillato/Hermetically sealed"