24-15/16 x 29-1/8 x 29-1/8
33-3/16 x 29-1/8 x 29-1/8
2.2 Unit Dimensions
2. Unit Location Considerations
Table 2-1 Condensing unit dimensions
Units are packaged for shipment to avoid damage
during normal transit and handling. It is the receiving
party’s responsibility to inspect the equipment upon
arrival. Any obvious damage to the carton box should be
reported on the bill of lading and a claim should be filed
with the transportation company, and the factory
should be noticed.
All units should be stored in the factory shipping carton
with internal packaging in a dry place until installation.
Carefully remove the packaging and inspect for hidden
damage. Any hidden damage should be recorded and the
factory should be notified. The gauge port can be used to
check the refrigerant charge has been retained during
shipment.
2.1 Inspect Units
Fig 2-1 Check damage
Fig 2-2 External dimensions
Two models sharing the same chassis are suit for most
residential air conditioner and heat pump applications.
W
H
D
2.3 Location Restrictions
Exposure to a corrosive environment may shorten the life of the equipment, corrode metal parts, and/or
negatively affect unit performance. Corrosive elements include, but are not limited to: sodium chloride,
sodium hydroxide, sodium sulfate, and other compounds commonly found in ocean water, sulfur,
chlorine, fluorine, fertilizers, and various chemical contaminants from industry/manufacturing plants. If
installed in areas which may exposed to corrosive environments, special attention should be given to the
equipment placement and maintenance.
•Lawn sprinklers/waste water should not spray directly on the unit cabinet for prolonged periods.
•In coastal areas: The outdoor unit should be installed at a location that is at least 1000 feet away from
the coastal and on the side of the building that is farthest from the sea.