Compur Statox 502 User manual

Manual
Statox 502
Control Module
Compur Monitors GmbH & Co. KG
Weissenseestrasse 101
D-81539 Münc en
P one: +49 (0) 89 62038 268
Fax: +49 (0) 89 62038 184
www.compur.com

Statox 502 Control Module
Page 2 of 40 Issue 1/2015
Content
Warning Signs ....................................................................................................................................... 3
Mounting .............................................................................................................................................. 5
Dismounting .......................................................................................................................................... 6
Connecting to power supply ................................................................................................................. 7
Start-up ................................................................................................................................................. 7
Controls ................................................................................................................................................. 9
LEDs ....................................................................................................................................................... 9
Display ................................................................................................................................................. 10
Communication bus ............................................................................................................................ 11
Electrical connections ......................................................................................................................... 11
Connecting t e external reset and analog output ................................................................... 13
Connecting t e internal relays ................................................................................................. 13
Password ............................................................................................................................................. 14
Main menu structure .......................................................................................................................... 15
Service Mode ...................................................................................................................................... 16
Selecting t e measuring program ....................................................................................................... 16
Calibration ........................................................................................................................................... 18
Reading t e bridge voltage ................................................................................................................. 20
Switc ing t e sensor power supply off............................................................................................... 21
Programming t e alarm relays ........................................................................................................... 22
Alarm relays configuration ................................................................................................................. 25
Functional test .................................................................................................................................... 26
Current output in Service Mode ......................................................................................................... 28
C anging t e operation mode – Control Module or Common Alarm Module .................................. 29
Status messages .................................................................................................................................. 32
Error messages.................................................................................................................................... 33
Control Module - Status diagram ....................................................................................................... 35
Common Alarm Module - Status diagram .......................................................................................... 35

Statox 502 Control Module
Issue 1/2015 Page 3 of 40
Safety notes
Read and observe t is manual prior to installation and start-up.
T e Statox 502 Control Module is only allowed to operate under t e given ambient conditions (see
Tec nical Data). In particular, it must not be operated in potentially explosive atmosp eres!
T e Statox 502 Control Module must be operated, maintained and repaired by trained and expert
personnel only. Use only Compur Monitors original parts for repair and maintenance.
Do not connect t e module directly to mains!
Do not modify t e product. Do not use if damaged or incomplete.
W en installing t is product observe all local standards and regulations.
Disregarding of t e above points represents a danger to people and property.
Warning Signs
Potential Danger
Note on an immediate danger to people and property.
Advice
Extra information for t e proper use of t e product.
!
!

Statox 502 Control Module
Page 4 of 40 Issue 1/2015
Product description
T e Statox 502 Control Module can be used in two different modes:
As a Control Module it supplies t e sensor eads for toxic or combustible gases wit energy and andles
t eir signal. It can be configured for different gases and measuring ranges. T e Statox 502 Control Module
displays t e concentration and converts it into a 4 – 20 mA signal at t e analog output. If one of t e
programmed alarm t res olds is exceeded, t e relevant LED goes on, t e relevant relay switc es and t e
relays status is communicated on t e communication bus. T e alarms can be set latc ing or non - latc ing.
Latc ing alarms can be reset by pus ing t e reset button or by an external contact.
Please note:
Sensor eads for toxic gases and oxygen (Statox 501/S and Statox 505) are protected in concept Ex i
(intrinsic safety) and must be connected via an intrinsically safe repeater, as far as t ey are intended
to be installed in a azardous area (Zone 1 or 2).
Sensor eads for combustible gases, CO
2
and VOC (Statox 501 HRC, ARE, LCIR, MCIR, Infratox, and
PID) are protected in concept Ex e (en anced safety) or Ex d (flameproof). T ey can be connected
directly to t e Control Module, even if t ey are intended to operate in Zone 1 or 2.
T e Statox 502 can also be operated as Common Alarm Module. It collects t e alarm signals (A1/A2/SF) of
up to 25 connected control modules and generates a common alarm on LEDs, relays and its analog output.
T is way you can set up a multi - c annel gas detection system. Prerequisite is t at all modules are connected
to eac ot er via bus adapter. An Error from t e Control Module or t e connected sensor eads will appear
on t e respective Control Module as well as on t e Common Alarm Module.
If power supply is provided via t e optional bus plugs, it is possible to replace t e modules during operation
wit out effort.

Statox 502 Control Module
Issue 1/2015 Page 5 of 40
Getting started
T e Statox 502 control modules are designed for mounting on DIN rail TS 35. Due to t e tilted
mounting/dismounting of t e modules t e span between t e outsides of t e rail and t e wall below and
above t e Statox 502 Module must be at least 80 mm (3.15 “). Furt ermore at least 120 mm (4.72 “) must
be remain free between two rail lines.
Mounting
T e Control Module can be operated wit out bus adapter, t ey will be mounted on t e
DIN rail as s own in Figure 2. In t is case eac module must be powered separately wit
24 VDC.
1. Plug t e bus adapters toget er and snap t em on t e DIN rail as s own in Figure 1.
2. Incline t e module and move it to t e lower part of t e DIN Rail. See Figure 2.
3. Now pus t e module forward to t e rail against t e resistance of t e spring lock, until you ear it
snapping in.
Set wit 2 bus adapters, obligatory
for eac module in bus operation,
Art.# 557002
Connection set for bus adapter
(Bus plug left and rig t),
optional, Art.# 557003
DIN rail TS 35
Figure
1
: Requirements for bus operation, sample installation
Control Module, Art.# 557000
Control Module, Art.# 557000, configured as Common Alarm Module
Power supply
24 VDC
!

Statox 502 Control Module
Page 6 of 40 Issue 1/2015
You can combine modules of t e Statox 502 series in any sequence. Adding or removing one module as no
impact on t e ot ers. You can save wiring effort starting wit t e power supply on t e outside and connecting
it to t e bus. Alternatively t e first module in a row can be connected to 24 ± 2 VDC, t e ot ers will be
supplied via bus. T e power rail is rated for 30 modules max. in one row. You can interconnect multiple rows
wit t e optional bus plugs (Connection set Art.# 557003, 1 set per rail is needed). For furt er information
see Accessories list chapter 12.
Dismounting
Pull t e spring lock wit a screw driver and incline t e module simultaneously, see Figure 3. T is can be done
under operating conditions.
1
2
Figure
3
:
ismounting from IN rail
Figure
2
:
Mounting to
IN rail

Statox 502 Control Module
Issue 1/2015 Page 7 of 40
Connecting to power supply
Do not connect t e module directly to mains! Do not s ort circuit terminals! Bot can
destroy t e module!
T ere are two options connecting t e 24 V C power supply, see Figure 4.
a) Via bus plug to t e communication bus
b) Directly to t e relevant Statox 502 Control Module terminal
In bot cases all subsequent modules are automatically connected to t e power supply via bus. T e terminals
are rated to take a max. diameter of 2,5 mm
2
. T e module starts operating as soon as it is connected to
power.
Start-up
In any case make sure to select t e appropriate program prior to connecting t e sensor
ead. Ot erwise t e sensor can be damaged.
Ex works t e Statox 502 is configurated to operate as Control Module. After connection to power, it performs
a self-test. It displays t e firmware version, t en for 5 seconds t e actual measuring program, t en “PLEASE
WAIT”. T e module remains in t e system fail mode until t e measuring mode as successfully been
activated. During t is process t e red LED “S” is on.
If no sensor ead is connected, an error message is generated (ERROR 2 or ERROR 5, depending on measuring
program). In t is case activate t e appropriate program as described in chapter 6.1. T en connect t e sensor
ead as described in chapter 9.
!
13
14
1
5
16
+24 V C
0 V
17
18
19
20
a)
Bus plug (left)
b) Terminal block
5
4
3
2
1
0 V
+24 V C
Figure
4
: Connecting the power supply
!

Statox 502 Control Module
Page 8 of 40 Issue 1/2015
If a sensor ead as been connected and t e appropriate program as been selected, t e measuring mode
will start.
Sensor eads for combustible gases, type HRC, ARE, LC IR, MC IR and PID must be
calibrated after being connected.
Exception: A line calibration as been done by Compur.
!
Power ON
Actual firmware version is displayed 3 s.
Actual operation program is displayed 5 s.
During t is time an access to t e main menu is possible.
Figure
5
:
Start
-
up
sequence

Statox 502 Control Module
Issue 1/2015 Page 9 of 40
Product c aracteristics
Controls
T e Statox 502 as four pus buttons.
Button Function
Enter Enter.
Reset Deletes wrong entries, resets t e alarm relays, goes one step back in t e menu.
Left
*)
Navigates left in t e menu, reduces a programmed figure, c anges t e first
display line w en in t e measuring mode.
Rig t
*)
Navigates rig t in t e menu
,
increases a programmed figure, c anges t e firs
t
display line w en in t e measuring mode.
*)
In some menus a continuous pus activates t e fast mode
LEDs
T e Statox 502 as 4 status LEDs. T e function of t e individual LEDs is subsequently explained.
escription LE Function
ON Green
Power supply
:
„ON“ Power ON
„OFF“ Power voltage off or too low
A1
Yellow
Relays
1: Alarm t res old exceeded
A2
Yellow
Relays
2: Alarm t res old exceeded
S Red
Failure or service request
:
„Flas ing“ Service Mode
„ON“ System Failure
„OFF“ Measuring mode

Statox 502 Control Module
Page 10 of 40 Issue 1/2015
Display
In t e measuring mode t e display s ows t e target gas, t e actual measured value and t e unit.
Example 1 (Combustible gas)
E x p l . G
a s
1 0 0 %
L E L
Example 2 (Toxic gas)
S O
2
1 . 3 4 p p m
In case of an over range exposure, t e full scale value is going to flas .
T e ►- or◄-Button c ange t e content of t e upper line to display t e actual program and t e end of range
value. After 20 seconds t e display goes back to t e standard content – t e target gas.
Gas
Program
End of range value
◄
E
x
p
l . G
a
s
►◄
P
r o
g
. x
x
►◄
1
0
0
%
L
E
L
►
2
0
%
L
E
L
2
0
%
L
E
L
2
0
%
L
E
L
Gas
Measured value
Unit in % LEL (Lower Explosion Level)
Measured value
Unit in ppm (parts per million)
Gas
Table of contents
Other Compur Control Unit manuals
Popular Control Unit manuals by other brands

Festo
Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation
JS Automation MPC3034A user manual

JAUDT
JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum
Spektrum Air Module System manual

BOC Edwards
BOC Edwards Q Series instruction manual

KHADAS
KHADAS BT Magic quick start

Etherma
Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations
PMFoundations Attenuverter Assembly guide

GEA
GEA VARIVENT Operating instruction

Walther Systemtechnik
Walther Systemtechnik VMS-05 Assembly instructions

Altronix
Altronix LINQ8PD Installation and programming manual