CIATControl OPC Server
OptimumcontrolforHysyssystemsolutionsforoffices,
hotelsandseniorcitizenresidences
Installationandoperating
instructions
Description:
•StandardOPCcommunicationsolution
•Centralisationofthesystem'svariousCIATControlsonanOPC‐compatibleBMS
•Largerangeoflicencesformonitoring:
o1CIATControl
o2to5CIATControls
oOver5CIATControls
•Quick,intuitiveinstallation
Includes:
•InstallationCD
•Dongle(licence)
•Installationandoperatinginstructions
Tobecarriedoutbytheintegrator:
•InstallationoftheOPCserverontheBMS
•CIATControlIPconfiguration
•CIATControldeclarationviatheOPCserverconfigurator
•SelectionofpointstobeindicatedontheBMS

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [2]
V05.2012
1. LISTOFEQUIPMENT
No.DescriptionQuantityComment
1InstallationCD1Minimumrequirements:
WindowsXP/7/Server2008compatible
Processor:1.6Ghz
RAM:1Gb
Diskspace:1Gb
CDplayer
1USBportavailable
.NetFrameworkversion2.0
2Dongle(licence)1TobeconnectedtotheUSBport
3Installationandoperatinginstructions1‐
2. INSTALLINGTHESOFTWARE
InserttheinstallationCDintheCDplayer.
Doubleclickontheicontolaunchtheinstallation.Thefollowingwindowappears.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [3]
V05.2012
Followtheinstallationinstructionsandclickon"Finish"afterselecting"Yes,Iwanttorestartmycomputernow".
Note:makesureyoucloseallyouropendocumentsbeforeclickingon"Finish".
Afterrestartingyourcomputer,theOPCserverwillbeoperational.
Connectthedongletoactivatethelicence.
3. CONFIGURINGTHESTATIONS
1/ConfiguringtheCIATControls
ConfigureeachCIATControlwithafixedIPaddress.
Todothis,identifyyourselfasa"User",clickon"Parameters"andselectthe"Ethernetconfiguration"tab.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [4]
V05.2012
ConnectanRJ45cabletooneofthe2EthernetportsontheCIATControl.
Note:eachCIATControlhasadefaultDHCPsetting.
OnceanaddresshasbeenassignedtotheCIATControl,theactiveboardisdisplayed.
Select"Static"andentertheinformationsuppliedbythenetworkadministrator(orthatassignedbytheDHCPserver):
‐IPaddress
‐Subnetmask
‐Gateway
Clickon"Send"toconfirmtheconfiguration.
Note:ifseveralCIATControlsarepresentonthenetwork,pleasemodifythecomputername(defaultname:
CIATCONTROL)toauniquenametoavoidconflicts.TheCIATControlwillneedtoberestartedafterthenamehasbeen
modified.
CarryoutthesameoperationoneachCIATControl,takingcaretoassigndifferentfixedIPaddressesforeach
CIATControl.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [5]
V05.2012
2/ConfiguringtheOPCserver
In"Start","Programs",clickon"OPCServerConfigurator".
Thefollowingwindowopens.
Clickon"NEW"toaddaCIATcontrol.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [6]
V05.2012
EnteranameforthisequipmentanditsfixedIPaddress,thenclickon"OK".
Clickon"PING"tocheckthecommunicationwiththeequipment.
Itsstatusswitchesto"Success".
RepeattheoperationforeachCIATControl.
WhenalltheCIATControlshavebeenconfigured,closetheapplicationbyclickingonthecrossinthetopright.
TheOPCserverisnowconfigured.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [7]
V05.2012
AnyOPCclientcanconnecttheOPCservertoaccessthevaluesforalltheCIATControlsavailableonthesystemand
declaredontheserver.
Notes:
OtheractionsarepossiblefromtheOPCserverconfigurator:
‐"MODIFY":usedtomodifythenameorIPaddressoftheequipment
‐"DELETE":usedtodeletetheequipment
‐"REFRESH":usedtostartapingforalltheequipmentonthelist
‐"SETTINGS":usedtoconfiguretheOPCserverparameters
The"SETTINGS"menuisusedtomodifythefollowingparameters:
‐Booleanvalueistrue:appliestoallOPCitemscreatedwiththebooltype;iftheboxischecked,thevalue
codedfortrueis1;iftheboxisnotchecked,itis‐1.
‐Reconnectevery:frequencyofreconnectiontoastationdeclaredabsentonthenetwork.Whenastationis
declaredabsentafteralossofcommunication,theOPCserverusesthisfrequencytocheckthatthestation
hasreturnedtothenetwork
‐Refreshtime:waitingtimeactivatedwitheacheventpriortostationupdate.Thisisused,forexample,when
addingitemstothestationformonitoring:itisusedtosendthelistofitemstobemonitoredonceallthe
itemshavebeendeclared,ratherthanupdatingthestationeachtimeanitemisadded/deleted.Inparticular,
thissavestimewheninitialisingtheOPCserver
‐Disconnectiontime:waitingtimepriortodisconnectionofthelinkbetweentheOPCserverandthestationfor
whichnoitemsarereadbytheOPCserver
‐Dataservertestfrequency:cyclicaltesttocheckforthepresenceofthestation(useofthepingcommand)
‐TCPtimeout:configurationofthetimeoutperiodontheTCPcontrolwhencheckingforthepresenceofthe
stationonthenetwork
‐Nativetypeisstring:appliestoOPCitemsforwhichthetypeisdefinedasstringiftheboxischecked.
Otherwisethetypeisundefined
‐Addressseparator:characterusedtoseparatethedifferentfieldsoftheOPCaddress(devicefield,network
field,variablefield,etc.)
4. USE
TheOPCserverlaunchesautomaticallywhenanOPCclientattemptstocommunicatewiththeCIAT.CIATControlOPC
Server.DAserver.
AnyOPCclientcannowselecttheitemshewishestomonitor(seesections7to10fortheitemsavailableforeachtype
ofequipment).
TheOPCserverhasthefollowingbuttons:
‐Stations…:usedtocheckthestationsinterrogatedbytheOPCclient;itispossibletorefreshtheconnections
orattempttoreconnectifthereisalossofcommunicationwithoneofthestations.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [8]
V05.2012
‐Exit:usedtoclosetheOPCserver.Ifequipmentisaddedtotheserver,itisrecommendedtoshutdownthe
serverbeforeconfiguring,otherwiseanymodificationswillonlybetakenintoaccountoncetheOPCserveris
restarted.
‐Group:usedtoindicatetheitemsreadbytheOPCclient.Thefulladdressisindicated,aswellastherefresh
timeandvalue.
‐Badaddresses:usedtoindicateincorrectaddressesread/writtenbytheOPCclient.Iftheseaddressesdonot
exist,theywillbedirectlyplacedinthismenu.
‐Groupdetails:givesageneraloverviewoftheOPCserveraswellasthevalueoftheparameterssetintheOPC
serverconfigurator.
‐Filter:usedtoapplyafiltertotheitemslistedinthetable.Simplyenterthecharacterspresentintheaddress
ofeachitem.Thefilterrefreshesautomatically.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [9]
V05.2012
ImportantnotesfortheinstallationprocedureviaOPC:
‐Thevalueswrittenintheequipmentparametersarenotstoredinthedatabase.Whenreplacingthe
modules(inoperativemodule),theparametervaluesshouldbechangedagain.Onlythevaluessetviathe
CIATControlscreenarestoredinthedatabase.
‐TakecarewhenwritingtheparametervaluesforV3000typemodules.Whenaparameterismodified,the
V3000restartsautomatically.Itthenlosesthecontextinwhichitwasswitchedto"Auto"mode.Itwillnot
switchbacktothemoderequestedbythetimeschedulewhenthemodenextswitches.Topreventthis,the
OPCclientmustsendthecommandtotheV3000inordertomakeitswitchbacktothemodeitwasin
beforetherestart.
‐TheitemsavailableforeachpieceofequipmentaredisplayedinFrenchonly.
5. UNINSTALLING
Touninstallthesoftware,theOPCservermustbeshutdown,whichrequiresalltheOPCclientstobeclosed.
Doubleclickonthe"CIAT"iconinthebottomrightofthetaskbar.
Thefollowingwindowopens.Clickon"Exit"andconfirmthattheapplicationhasclosed.

NA 12.46 A
©2012CIAT
NA 12.46 A installation instructions [10]
V05.2012
In"Configurationpanel",clickon"ProgramandFunctions"(Win7)or"Add/Removeprograms"(WinXP/Win
Server2003/2007).
Select"CIATControlOPCServer"andclickonuninstall.Thefollowingwindowopens.Followtheinstructions.
Table of contents
Other CIAT Control Unit manuals
Popular Control Unit manuals by other brands

Festo
Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation
JS Automation MPC3034A user manual

JAUDT
JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum
Spektrum Air Module System manual

BOC Edwards
BOC Edwards Q Series instruction manual

KHADAS
KHADAS BT Magic quick start

Etherma
Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations
PMFoundations Attenuverter Assembly guide

GEA
GEA VARIVENT Operating instruction

Walther Systemtechnik
Walther Systemtechnik VMS-05 Assembly instructions

Altronix
Altronix LINQ8PD Installation and programming manual