Carrier RW Manual

Translation of the original document
EVAPORATIVE HUMIDIFIER
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS


3
The illustrations in this document are for illustrative purposes only and not part of any offer for sale or contract. The manufacturer
reserves the right to change the design at any time without notice.
1 - TECHNICAL RECOMMENDATIONS/WARRANTY.......................................................................................................................4
2 - OPERATING PRINCIPLE .............................................................................................................................................................4
3 - DESCRIPTION...............................................................................................................................................................................5
3.1 - General description of the humidier.........................................................................................................................................5
3.2 - General recommendations........................................................................................................................................................6
4 - TECHNICAL CHARACTERISTICS ...............................................................................................................................................7
4.1 - General characteristics of the humidier...................................................................................................................................7
4.2 - Characteristics of the components............................................................................................................................................8
5 - INSTALLATION/START-UP/MAINTENANCE .............................................................................................................................17
5.1 - Installation ...............................................................................................................................................................................17
5.2 - Start-up....................................................................................................................................................................................17
5.3 - Maintenance............................................................................................................................................................................17
5.4 - Disposal of the product and efuent generated ......................................................................................................................17
5.5 - Cleaning and disinfection ........................................................................................................................................................17
5.6 - Removing the media ...............................................................................................................................................................18
6 - RELATED DOCUMENTS ............................................................................................................................................................ 22
6.1 - CCB control box wiring diagram (option 12)............................................................................................................................22
7 - MCCB MANUAL - HUMIDIFIER CONTROL BOX ......................................................................................................................23
7.1 - General description.................................................................................................................................................................23
7.2 - Installation ...............................................................................................................................................................................24
7.3 - Description of hardware ..........................................................................................................................................................25
7.4 - Connections ............................................................................................................................................................................31
7.5 - Monitoring................................................................................................................................................................................33
7.6 - Conguration...........................................................................................................................................................................34
7.7 - Settings ..................................................................................................................................................................................36
7.8 - Calibration ...............................................................................................................................................................................37
7.9 - Launch.....................................................................................................................................................................................37
7.10 - List of alarms.........................................................................................................................................................................38
8 - AL-UW SUBMERSIBLE UVC LAMP...........................................................................................................................................39
8.1 - Safety ......................................................................................................................................................................................39
8.2 - Operating data and description of the device..........................................................................................................................40
8.3 - Assembly and connection of the unit.......................................................................................................................................41
8.4 - Unit operation..........................................................................................................................................................................42
8.5 - Faults and troubleshooting......................................................................................................................................................42
8.6 - Maintenance and spare parts..................................................................................................................................................43
8.7 - Disposal...................................................................................................................................................................................43
CONTENTS

4
1 - TECHNICAL RECOMMENDATIONS/WARRANTY
For all technical recommendations relating to the humidier, please see paragraphs 1-GENERAL, 2-SAFETY GUIDELINES,
3-REGULATIONS of Instruction Manual FR 7486825 for the Unit, supplied with the product.
Regarding the warranty, please see paragraph 1-GENERAL of Instruction Manual FR 7486825 for the Unit, supplied with the product.
CAUTION : All specic recommendations relating to the humidier are described below in paragraphs 3-DESCRIPTION,
4-TECHNICAL CHARACTERISTICS and 5-INSTALLATION/START-UP//MAINTENANCE.
CAUTION :
RESPONSIBILITIES
All personnel operating a humidier are responsible for:
-their personal safety, the safety of other people and the prevention of damage to the humidier
-the correct operation of the humidier
-electrical wiring must be installed in accordance with national standards, by qualied personnel..
These instructions explain how the humidier must be used.
These instructions are recommendations only, and do not replace the responsibilities set out above.
2 - OPERATING PRINCIPLE
Increasing the relative humidity by passing air through a matrix moistened with water is a simple, safe method of humidication, with
the benet of the adiabatic cooling generated and low operating costs.
100%
0
Outlet
conditions
Relative humidity (%RH)
Temp. (°C)
Inlet conditions
10 20 30 40 50 60
50% 20%
The dry air passes through an absorbent cellulose bre or breglass matrix and collects the water vapour located on the moist surface.
The water is distributed from the top of the matrix by a solid stainless steel nozzle bar and distribution cassettes located at the top of
each vertical row of matrices ensure even humidication.
20°C
32°C
32°C
Warm
dry
air
Damp
fresh air
without
aerosols
Water inlet

5
3 - DESCRIPTION
3.1 - General description of the humidier
Recirculated water model - RW
P
M
B
L
ED
K
B
I
C
B
J
F
H
O
J
Direct water model - DW
B
J
G

6
Component DW humidier
(without pump)
RW humidier
(with pump)
1. Water supply connection Std Std
2. Float ll valve Std Std
3. High and low water level sensor NA Std
4. Recirculation pump NA Std
5. 2-way valve
a. Manual NA Std
b. 24 VAC motorised - Two control points NA Option
6. Motorised 3-way valve Option NA
7. Supply solenoid valve NA Option
8. Medium cassette
a. 100 mm cellulose bre - 65% efcient Option Option
b. 200 mm cellulose bre - 85% efcient Option Option
c. 75 mm cellulose bre - 65% efcient Option Option
d. 150 mm cellulose bre - 85% efcient Option Option
9. Ø32 PVC pipe drain connector Std Std
10. Mineral salt deconcentration by
a. Deconcentration manifold NA Std
b. Conductivity sensor NA Option
(component 12 mandatory)
11. Flow balancing valve Std Std
12. Humidier control only with CCB box NA
Option
(including components 5b and
7)
13. Droplet separator
Std if:
- V>3 m/s cellulose
- V>3.5 m/s breglass
Std if:
- V>3 m/s cellulose
- V>3.5 m/s breglass
14. Submersible UV lamp Option Option
15. AHU control NA
Option
(including components 5b, 7
and 12)
WARNING : The humidier is pre-wired when option 15 (AHU control) has been selected. Otherwise, the installer is responsible
for wiring.
3.2 - General recommendations
■Recommendations for optimised operation
The air passing through the module must be ltered at least to ltration standards F7 and ePM1 50% in order to prevent fouling of the
humidier cassettes. Finer ltration may also be necessary in hospitals, food processing and electronics settings. We recommend that
a water lter be installed on the supply.
If the supply water for the humidier has a calcium content above the recommended level (see "drinking water network analytical
parameters" after component 9), we recommend that the water be demineralised.
When the humidier is the last component of the Unit, we recommend that an expansion valve be positioned 1,000 mm downstream
of the humidier.
■Recommendations for use in accordance with hygiene standard VDI6022
This adiabatic evaporative humidier option is certied in accordance with VDI6022 subject to certain restrictions and operating
conditions:
-The standard relates to RW and DW humidiers equipped with an inorganic breglass medium
-DW humidiers must be equipped with 3-way valves
-RW humidiers must be equipped with CCB control boxes (the option includes the supply and drainage solenoid valves)
-These humidiers and their control boxes are designed so that they ensure complete drainage of the water from the tank and the
supply and drainage pipes during one-off or permanent shutdowns of the humidication system for more than 48 hrs.
-Whenever the humidier is shut down, the Unit controller must ensure that the humidier media are dried completely.
-The water supply pipes must be equipped with a device preventing any water from returning to the drinking water column.
3 - DESCRIPTION

7
4 - TECHNICAL CHARACTERISTICS
4.1 - General characteristics of the humidier
■Permissible air ow in m3/hr, for DW and RW humidiers:
Size of the Air Handling Units 10 15 20 25 35 45 60 70
Without separator - cellulose bre 2927 4007 6167 8143 10336 12539 19559 21298
Without separator - breglass 3415 4675 7195 9500 12058 14629 22819 24847
With separator - cellulose bre + breglass 4878 6678 10278 13572 17226 20898 32598 35496
■Indicative water consumption (depending on air conditions)
• recirculated water (RW) dehumidier:
Evaporated water ow rate in l/hr with pump (pH neutral, medium TH), T°=30°C and 10% RH
Type of humidier medium Flow rate in l/hour for 1,000 m3/hr of air
Fibreglass or cellulose bre - 65% efcient 5.6 l/hr
Fibreglass or cellulose bre - 85% efcient 7.1 l/hr
Example: AHU025- humidier 85% -8,000 m3 /hr =8 x 7.1 = 56.8 l/hr
Deconcentration ow rate (to limit mineral salt concentration in the tank):
Deconcentration ow rate = see the "technical recommendations" paragraph in "mineral salt deconcentration by a. Deconcentration
manifold"
Water consumption = evaporation ow rate + deconcentration ow rate
• direct water (DW) humidier:
Evaporation module with continuous water supply.
Direct water supply in l/hr:
Air handling unit 10 15 20 25 35 45 60 70
Fibreglass or cellulose bre - 65% efcient 240 360 480 480 480 600 720 1080
Fibreglass or cellulose bre - 85% efcient 300 450 600 600 600 750 900 1440
Module casing
304 stainless steel
Max. inlet water pressure
6 bar
Max. inlet water temperature
15°C
Drain dimension
32 mm PVC piping
Min./max. air temperature on the humidier
5°C/40°C

8
4.2 - Characteristics of the components
1. Water supply connection
Technical characteristics
1/2" BSP-M stainless steel pipe
Technical recommendations
Connect the mains water to the 1/2” BSP male connector oat valve with a shut-off valve. Apply sealant
before connecting. Ensure that the supply pipes can be uncoupled from the humidier downstream of the
shut-off valve, so that the humidier and the front panel can be removed completely in the event of heavy
maintenance.
2. Float ll valve
Technical characteristics
304 stainless steel
Technical recommendations
The oat valve can be adjusted by 25 mm vertically using a 20 mm spanner, to adjust the tank water levels
(image 1). When the tank is full, the water level must be 3 cm below the overow. During operation, the
level must never drop below the foot of the pump, as this can damage the pump irrevocably (image 2).
The water level in the tank can also be adjusted by altering the rotation (max. 110°) of the oat, using a 10
mm spanner (image 3).
Images
1).
(*) 25 mm
2).
70 mm
3).
110°
4 - TECHNICAL CHARACTERISTICS

9
3. High and low water level sensor
Technical characteristics
304 stainless steel
Technical recommendations
CAUTION: Remove the protective net from the oat before system start-up.
Low level: This connection is mandatory to protect the operation of the recirculation pump, as it activates
and deactivates the pump when it detects a minimum water level in the tank (if the humidier control option
has been selected connector J17 on the SEF-028 card in the Control Box - NO contact).
High level: The maximum level is used as a safety system if the water supply oat valve fails. It must not be
used to control the water supply. If the equipment has a supply solenoid valve, connect it here so that it is
shut off by the safety system (if the humidier control option has been selected connector J16 on the
SEF-028 card in the control box - NC contact).
Images
BOTOM VIEW
S2
HIGH
LEVEL
S1
LOW
LEVEL
Pin assignment M12 socket, 8-pos., A-coded, view female side
N.C.= normally closed /
normalement fermé
N.A.= normally open / normalement
ouvert
C = Common / Commun
S1 (J17) LOW LEVEL - S1 niveau
bas
S2 (J16) HIGH LEVEL - S2 niveau
haut
S2
S2
(Vmax = 110 VAC)
Max.
level
Max.
level Filling
solenoid valve
Min. level
Pump
4 - TECHNICAL CHARACTERISTICS

10
4. Recirculation pump
Technical characteristics
Stainless steep pump body + plastic accessories
Rated power 60 W (0.13 A) or 125 W (0.36 A) depending on size, medium and efciency.
400 V/3~+PE/50 Hz connection
Connection box: PG9 packing box, max. cable Ø = 8 mm. IP 54
Technical recommendations
Connect the power supply line to the terminal connection box on the water irrigation pump.
Unless the control option has been selected (humidier only or AHU), the protection and power supply of
the pump must be determined by the system project designer. When option 12 - humidier control - has not
been selected, we recommend a thermal-magnetic circuit breaker with a rated current of:
0.1…0.16 A for the 60 W pump or 0.25…0.4 A for the 125 W pump.
Images
STAR CONNECTION
(400 V/III/50 Hz)
THREE-PHASE PUMP
WIRING DIAGRAM
Name Description
L1 Disconnecting switch for electrical isolation
SEL 1-2 3-4 5-6
1
0
X0 External housing
X1 Pump connection box (IP55)
Included if
there is a
control box
(humidier
control option)
Included on
the humidier
5. 2-way valve
Technical characteristics
Valve connection: 1/2” G
Servomotor (motorised valve):
Power consumption 5 VA/3.5 W.
Supply voltage 24 VAC - 2 control points.
Cable cross-section 0.75 mm², length 0.9 m
Rated torque: 7 Nm.
IP54.
Technical recommendations
Caution: In the event of a power failure, the motorised valve remains in the closed position. To drain
the humidier, the valve must be forced open on the servomotor (see image below).
See below
4 - TECHNICAL CHARACTERISTICS
This manual suits for next models
1
Table of contents
Other Carrier Humidifier manuals

Carrier
Carrier HUMXXSFP1012 User manual

Carrier
Carrier HUMCCLFP1025-A Series Planning guide

Carrier
Carrier HUMXXSFP1012 User manual

Carrier
Carrier HUMCCSBP2218 User manual

Carrier
Carrier HUMXXSTM3034 Installation and operating instructions

Carrier
Carrier CAC User manual

Carrier
Carrier HUMCCSBP2017-A Series Operation manual

Carrier
Carrier 49FH User manual

Carrier
Carrier Humidifier User manual

Carrier
Carrier HUMXXSTM3034 User manual























