BPC 5000VA User manual

PowerPrem
Line-interactive UPS
User’s Manual
5000VA
5K-02
0

IMPORTANT SAFETY INSTRUCTIONS
●When replacing the batteries, use the same number and the same type of batteries.
●Do not dispose of batteries in a fire; the battery may explode.
●Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin
and eyes.
●A battery can present a risk of electric shock and high short circuit current. The following
precaution should be observed when working on batteries.
* Remove watches, rings or other metal objects.
* Use tools with insulated handles.
●To prevent an overbalance of this unit, with the installation the additional stabilizer are to
mount at the bottom side.
●This unit should be installed by service personnel.
●The equipment can be operated by any individuals with no previous experience.
●“The socket-outlet shall be installed near the equipment and easily accessible.”
●“With the installation of this equipment it should be prevented, that the sum of the leakage
current of the UPS at the connected consumer does not exceed 3.5mA.”
●Attention: hazardous through electric shock. Also, with disconnection of this unit from the
main, hazardous voltage still may be accessible through supply of battery.
●The battery supply should be therefore disconnected in the plus and minus pole through or
from the outer enclosure accessible battery fuses when maintenance or service work
inside the UPS is considered.
●The lead acid battery may cause chemical hazard.
●The battery presents a risk of electric shock and energy hazard.
●Batteries will be disposed by the manufacturer or importer. Customers need to send
them back with no charge for disposal.
1

CAUTION:
● The UPS connection instructions and operation described in the manual must be followed in the
indicated order.
● UPS must be connected to a near by wall outlet that is easily accessible. The UPS can be
disconnected from the AC-power source by removing the power cord.
● Check that the indications on the rating plate correspond to your AC-power system and to the
actual electrical consumption of all the equipment to be connected to the UPS.
● Never install the UPS near liquids or in an excessively damp environment.
● Never let a foreign body penetrate inside the UPS.
● Never block the ventilation grates of the UPS.
● Never expose the UPS to direct sunlight or source of heat.
● If the UPS must be stored prior to installation, storage must be in a dry place.
● The admissible storage temperature range is -15℃to +55℃.
● All handling operations will require at least two people (unpacking, installation in rack systems).
● Once installed and connected to the AC power source for the first time, the battery will start to
charge. Full charging to obtain the rated battery backup time requires at least 8 hours.
● Before and after the installation, if the UPS remains de-energized for a long period, the UPS must
be energized for a period of 24 hours, at least once every 6 months (for a normal storage
temperature less than 25℃. This charges the battery, thus avoiding possible irreversible damage.
During the replacement of the battery module, it is imperative to use the same type and number of
element previously mounted in the UPS, in order to maintain an identical level of performance and
safety. In case of doubt, don’t hesitate to contact our after sales department.
● Never apply the UPS as an Inverter.
3

Special Symbols
The following are examples of symbols used on the UPS to alert you the important information.
RISK OF ELECTRIC SHOCK -
Indicates that a risk of electric shock is present and the associated warning
should be observed
CAUTION; REFER TO OPERATOR’S MANUAL -
Refer to your operator’s manual for additional information, such as important
operating and maintenance.
SAFETY EARTHING TERMINAL -
Indicates the primary safety ground.
RJ-45 RECEPTACLE -
For 230V units only, this receptacle provides network interface connections.
Do not plug telephone or telecommunications equipment into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS
batteries in the trash. The UPS may contain sealed, lead-acid batteries.
Batteries must be recycled.
4

TABLE of CONTENTS
1. Over view and Features ----------------------------------------- Page 6
2. Presentation -------------------------------------------------------- Page 7
2.1 LCD display models
2.2 Rear Panels ---------------------------------------------------------- Page 8
3. Installation ----------------------------------------------------------- Page 9
4. Operation ------------------------------------------------------------- Page 12
5. Indication and Control ------------------------------------------- Page 15
5.1 LCD Display Control
5.2 LCD Screen Description
5.3 Audible alarm -------------------------------------------------------- Page 16
5.4 Auto self-test Function -------------------------------------------- Page 17
5.5 Remote Control
5.6 Reset the UPS
5.7 DIP Switch Settings
6. Communication interface -------------------------------------- Page 18
7. Trouble shooting -------------------------------------------------- Page 19
8. Specifications ------------------------------------------------------ Page 20
5

1. OVER VIEW AND FEATURES
The series UPS is an advanced Line-Interactive Uninterruptible Power System which produces pure
sine wave power to your equipment; unlike the traditional off-line UPS, the series provides very short
transference when blackouts happen, and zero transference from AC mode to battery mode and vice
versa. The voltage regulation of the series is similar to an On-line UPS; however, the series
provides efficiency over 96% under normal power condition. Two charge modes, quick charge and
trickle charge, are provided to maintain the batteries in the best condition.
With outstanding performance and reliability, the unique benefits of the UPS include the following:
* Pure sine wave output.
* Microprocessor based design with true Line-Interactive structure.
* Adjustable voltage sensitivity, charging voltage, & voltage-transfer points.
* Remaining Estimated Backup Time indication (EBT system on LCD version).
* Smart battery management with intelligent double stages of charging control.
* Real time auto-detection for battery condition.
* Automatic restart of load after UPS shutdown.
* Smart AVR function (Two buck / boost modes).
* Zero Transference.
* Generator compatible.
* “Green Power” design with auto on/off function & adjustable level.
* Hot-swappable batteries.
* Network manageable (SNMP slot included).
* RS-232 interface for communication, compatible with all major O.S., including Windows, Linux,
SCO UNIX, & DOS.
* Protection for overload, short circuit, & over heat.
6

2. PRESENTATION
2.1 Front Panel
Tower Type Rack Mount Type
LCD Display
Main control button.
LCD screen.
Selection button for mode & value.
1
2
3
7

2.2 Rear Panels
B-2
B-3
A. Inlet (screw type).
B. Outlets (3 choices)
B-1. IEC 5 sockets x 2 + German type (Schuko) x 1, or
B-2. IEC 5 sockets x 3, or
B-3. Universal sockets 2 x 2 + screw terminal x 1
C. Re-settable fuses for output.
D. Re-settable fuse for input.
E. SNMP slot.
F. Cooling fan.
G. Communication port (USB, optional).
H. RJ-11 port.
I. DIP switch.
J. Communication port (RS-232).
K Handles.
8

3. INSTALLATION
3.1 Inspecting the packing carton for damage that may have occurred while in transit. Immediately
notify the carrier and place of purchase if any damage is found. Retain the package for future use.
3.2 The packing of the UPS is separated into 3 units, main unit weight 39kgs, & 2 units of battery set
weight 18kgs of each. Each battery set contains 6pcs of 12V battery. To move these units, main
unit needs 2-3 persons; while each battery set can be moved by one person.
3.3 To install the UPS, please fix the main unit first; then, put on the battery set one by one, and finish
the connection (Ref. 3.6); finally make connection for input and output of the UPS.
3.4 The UPS can be used as a rack-mount unit, or a tower one. Please follow the steps to make it
as a rack-mount unit or a tower one as below:
3.4.1 Tower type ---
To screw on the rubber pad (6pcs, as enclosed) at the
bottom side of the unit; or put on 4 wheels (optional).
Bottom side (with pads,
or wheels/optional)
3.4.2 Rack mount type ---
To screw on the handling ears as a regular rack mount
unit, put it on the rack, and fix it.
3.5 Adjust the display panel between tower & rack mount types, you can make it easily simply by
screwing on/off the 4 screws around the display panel with 90° turning on the panel.
9

3.6 Battery Installation / Replacement
3.6.1 This is a hot-swappable designed UPS, which means that when you are replacing battery set, the
UPS doesn’t need to be turned off.
3.6.2 To install or replace batteries, please screw off the 4 screws of front panel, disconnect the cable
connection to the LCD display module; then please disconnect and pull out one of the two battery sets,
and keep the other set in connection so that your equipment can be still protected during the period of
time for battery replacement.
DWG. 3.6.2
Inside view when front panel is removed
3.6.3 Please screw off the top cover of the battery set to be replaced, change the batteries inside with
the same spec & number, and make it in series connection.
DWG. 3.6.3 Inside view of battery pack
when top cover is removed.
3.6.4 Put back the battery set in the main unit, finish the connection with the UPS, and proceed the
same steps for replacing the other battery set.
3.6.5 Once the battery replacement has been finished, please put back the cable connection to the LCD
module, and tightly screw on the front panel.
3.6.6 The warranty will be void if to replace battery without the same spec or number. The battery type
is 12V 7Ah, 6pcs for each pack, and 12pcs in total