All HMI panels are developed to satisfy the demands of human-machine communication. Built-in
functions such as displaying and controlling text, dynamic indication, time channels, alarm and
recipe handling are included. The HMI panel works primarily in an object-oriented way, making it
easy to understand and use. Configuration is carried out on a PC using iX Developer software. The
project can then be transferred and stored in the HMI panel itself. Various types of automation
equipment such as PLCs, servos or drives can be connected to the HMI panels. In this manual, the
term “the controller” refers to the connected equipment. This manual explains how to install the
HMI panel. Please refer to the iX Developer reference manual for further information.
Copyright © 2023 Beijer Electronics AB. All rights reserved.
The information in this document is subject to change without notice and is provided as availa-
ble at the time of printing. Beijer Electronics AB, including all its group companies, reserves
the right to change any information without updating this publication. Beijer Electronics AB, in-
cluding all its group companies, assumes no responsibility for any errors that may appear in this
document. Read the entire installation manual prior to installing and using this equipment. Only
qualified personnel may install, operate or repair this equipment. Beijer Electronics AB, includ-
ing all its group companies, are not responsible for modified, altered or renovated equipment.
Because the equipment has a wide range of applications, users must acquire the appropriate
knowledge to use the equipment properly in their specific applications. Persons responsible
for the application and the equipment must themselves ensure that each application is in
compliance with all relevant requirements, standards and legislation in respect to configuration
and safety. Only parts and accessories manufactured according to specifications set by Beijer
Electronics AB, including all its group companies, may be used.
BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES, SHALL NOT BE LIABLE TO
ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULT-
ING FROM THE INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT,
CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL BE THE REPAIR, REPLACEMENT, OR
REFUND OF PURCHASE PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL BE AT THE
SOLE DISCRETION OF BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES.
Head Office
Beijer Electronics AB
Box 426
201 24 Malmö, Sweden
www.beijerelectronics.com / +46 40 358600

Table of Contents
1. Safety Precautions ........................................................................................ 5
1.1. General ............................................................................................ 5
1.2. Hazardous Materials ............................................................................. 5
1.3. Disposal Requirements Under WEEE Regulations ............................................ 6
1.4. UL and cUL Installation .......................................................................... 6
1.5. During Installation ................................................................................ 6
1.6. During Use ......................................................................................... 7
1.7. Service and Maintenance ........................................................................ 7
1.7.1. Cleaning the Display .................................................................... 7
1.8. Dismantling and Scrapping ...................................................................... 8
1.9. Appearance of Air in Touch Screen ............................................................ 8
2. Naming Convention ....................................................................................... 9
3. Installation ................................................................................................ 10
3.1. Space Requirements ............................................................................ 10
3.2. Installation Process ............................................................................. 10
3.2.1. Connections to the Controller ........................................................ 12
3.2.2. Other Connections and Peripherals .................................................. 12
3.2.3. Open Ports ............................................................................... 13
4. Technical Data ............................................................................................ 14
5. Chemical Resistance ..................................................................................... 16
5.1. Touch Screen and Overlay Material ........................................................... 16
5.1.1. Protective Film ......................................................................... 16
5.1.2. Touch Screen Surface .................................................................. 16
5.1.3. Touch Screen Protector ................................................................ 17
6. HMI Panel Drawings ...................................................................................... 18
6.1. Connectors ....................................................................................... 18
6.2. HMI Panel Outline ............................................................................... 19
7. Additional Installation Tips ............................................................................. 21
7.1. Grounding the HMI Panel ....................................................................... 21
7.2. Ethernet Connection in the HMI Panel ....................................................... 22
7.3. To Achieve Better EMC Protection ............................................................ 23
7.4. Ambient Temperature .......................................................................... 24
7.5. Safety ............................................................................................. 25
7.6. Galvanic Isolation ............................................................................... 26
7.7. Cable and Bus Termination RS-485 ........................................................... 27
7.8. USB Flash Drive .................................................................................. 27
7.9. Image Sticking ................................................................................... 27
Beijer Electronics, MAEN333 3 2023-09

4

1. Safety Precautions
Both the installer and users of the HMI panel must read and understand this manual.
1.1. General
• Read the safety precautions carefully.
• Check the delivery for transportation damage. If damage is found, notify the supplier as soon as
possible.
• Do not use the HMI panel in an environment with high explosive hazards.
• The supplier is not responsible for modified, altered, or reconstructed equipment.
• Use only parts and accessories manufactured according to specifications of the supplier.
• Read the installation and operating instructions carefully before installing, using or repairing the
HMI panel.
• Never allow fluids, metal filings or wiring debris to enter any openings in the HMI panel. This may
cause fire or electrical shock.
• Only qualified personnel may operate the HMI panel.
• Storing the HMI panel where the temperature is lower or higher than recommended in this manual
can cause the LCD display liquid to congeal and become isotropic.
• The LCD display liquid contains a powerful irritant. In case of skin contact, wash immediately with
plenty of water. In case of eye contact, hold the eye open, flush with plenty of water and get
medical attention.
• The figures in this manual serve an illustrative purpose. Because of the many variables associated
with any particular installation, the supplier cannot assume responsibility for actual use based on
the figures.
• The supplier neither guarantees that the HMI panel is suitable for your particular application, nor
assumes responsibility for your product design, installation or operation.
• It is recommended to turn on and shut down the HMI panel at least once before installing any
components or cards, or before connecting the HMI panel to external devices, for example serial
devices.
1.2. Hazardous Materials
Part description
零件描述
Toxic and hazardous materials or elements
有毒和有害的材料或元素
PCB and electronic components
PCB 和电子元件
Pb Hg Cd Cr6+ PBB PBDE
X O O O O O
O: Indicates that the concentration of the hazardous substance in all homogeneous materials in the
parts is below the relevant threshold of the GB/T 26572-2011 standard.
O: 表示该有害物质在该部件所有均质材料中的含量均在 GB/T 26572-2011 规定的限 量要求以下。
X: Indicates that the concentration of the hazardous substance of at least one of all homogeneous
materials in the parts is above the relevant threshold of the GB/T 26572-2011 standard. But still
complies with the EU RoHS Directive 2011/65/EU.
X: 表明该有害物质至少在部件的某一均质材料中的含量超出 GB/T 26572-2011 规定 的限量要求。但仍然
符合 EU RoHS 指令 2011/65/EU。
Safety Precautions
Beijer Electronics, MAEN333 5 2023-09

1.3. Disposal Requirements Under WEEE Regulations
For professional users in the European Union: If you wish to discard electrical and electronic
equipment (EEE), please contact your dealer or supplier for further information.
For disposal in countries outside of the European Union: If you wish to discard this product please
contact your local authorities or dealer and ask for the correct method of disposal.
1.4. UL and cUL Installation
Indoor use only. Altitude up to 2,000 m. Pollution Degree 2. Do not use in wet locations or in areas
where moisture or condensation can be expected.
WARNING
• The temperature resistance of the power cable used must be at least 55°C.
La tenue en température du câble d'alimentation utilisé doit être d'aumoins 55°C.
• Use copper conductors only.
Utilisez uniquement des conducteurs en cuivre.
• Power Port: Use cable type - AWG (American Wire Gauge) 12~28 and tighten
terminal screws with a torque value of 4.5 lb-in.
Port D'alimentation: Utilisez le type de câble - AWG (American Wire Gauge) 12 ~ 28
et serrez les vis des bornes avec une valeur de couple de 4.5 lb-in.
• COM C Port: Use cable type - AWG (American Wire Gauge) 16~28 and tighten
terminal screws with a torque value of 1.7 lb-in.
COM C Port: Utilisez le type de câble - AWG (American Wire Gauge) 16~28 et serrez
les vis des bornes avec une valeur de couple de 1.7 lb-in.
• If the equipment is used in a manner not specified, the protection provided by the
equipment may be impaired.
Si l'équipement est utilisé d'une manière non spécifiée, la protection fournie par
l'équipement peut être détérioré.
• The person responsible for installation safety for all systems covered by the
equipment is the person who installs the system.
La personne responsable de la sécurité de l'installation pour tous les systèmes
couverts par l'équipement, est la personne qui installe le système.
• Repairs may only be carried out by the manufacturer.
Les réparations ne peuvent être effectuées que par le fabricant.
• The manufacturer is not liable for damages resulting from failure to comply with
the manufacturer's instructions.
Le fabricant n'est pas responsable des dommages résultant du non-respect des
instructions du fabricant.
1.5. During Installation
• Install the HMI panel according to the accompanying installation instructions.
• Ground the HMI panel according to the accompanying installation instructions.
• Only qualified personnel may install the HMI panel.
Safety Precautions
2023-09 6 Beijer Electronics, MAEN333

• Separate the high voltage, signal, and supply cables.
• Make sure that the voltage and polarity of the power source is correct before connecting the HMI
panel to the power outlet.
• Peripheral equipment must be appropriate for the application and location.
1.6. During Use
• Keep the HMI panel clean.
• Emergency stop and other safety functions may not be controlled from the HMI panel.
• Do not use excessive force or sharp objects when operating the touch screen.
1.7. Service and Maintenance
• Only qualified personnel should carry out repairs.
• The agreed warranty applies.
• Before carrying out any cleaning or maintenance operations, disconnect the equipment from the
electrical supply.
• Clean the display and surrounding front cover with a soft cloth and mild detergent.
• The battery must be replaced by an authorized Beijer Electronics service center.
1.7.1. Cleaning the Display
We recommend using a dry, clean cloth to wipe off dust regularly. Use alcohol or ammonia-based
cleaning agent for cleaning only when necessary. When other solvents or cleaning agents are used,
be sure to follow manufacturers’ instructions. The agent should be applied to a clean cloth and
should not be sprayed directly onto the panel surface. After cleaning the agent should be removed.
Ammonia-based glass cleaners (typically 5-10% ammonia) or 75% alcohol can be used to clean the
surface of PCAP and resistive touch panels. When you clean the surface of your touch panel, please
follow these steps:
1. Apply cleaning agent (alcohol, bleach, or glass cleaner) to a clean cloth.
Make sure the cloth is well saturated.
2. Wipe the touch panel surface in a “Z” motion (see illustration below).
3. Dry the panel thoroughly with a dry cloth, removing as much of the cleaning solution as possible.
4. Do not mix bleach and ammonia because this will produce a dangerous chemical reaction.
5. Please do not spray cleaning solution directly onto the touch panel surface.
Safety Precautions
Beijer Electronics, MAEN333 7 2023-09

NOTE
• Cleaning solutions containing bleach, alcohol, and ammonia are corrosive to touch
panel surface coatings and ITO film. Do not leave the solution on the touch panel
surface for more than 2 minutes. Make sure to remove all residue when finished
cleaning.
• Do not use sharp tools to clean the surface of the touch screen.
• Do not use air guns, water jets, or steam, to clean the surface of the touch screen
as they may damage touch screen functionality.
• If condiments, food, or drinks are spilled on the surface of the touchscreen, please
remove it immediately.
• Ensure moisture does not seep through the cable connection area from the edges
during cleaning.
1.8. Dismantling and Scrapping
• Recycle the HMI panel and parts of it according to local regulations.
• The following components contain substances that might be hazardous to health and the
environment: lithium battery, electrolytic capacitor, and display.
1.9. Appearance of Air in Touch Screen
The layer structure of the touch screen contains air. In rare cases, the appearance of bubbles can
arise. This is purely cosmetic and does not affect the functionality of the HMI panel. The appearance
can occur under certain environmental conditions such as changes in temperature, humidity, or
atmospheric pressure.
Safety Precautions
2023-09 8 Beijer Electronics, MAEN333

2. Naming Convention
The name of each panel is based on its properties according to the table below.
Naming Convention
X2 family Size (inches) Generation/Version Variant
base
pro
marine (= with BL)
control (= with SC)
motion (= with SM)
extreme
4
5
7
10
12
15
21
v2 SC
SM
HB
HP
BL
12V
SL
RO
CO
web
Soft Control
Soft Motion
High Brightness
High Performance
Black
12 Volt
Sealed
Rugged Only
Certification Only
Web
Examples:
• X2 base 5 v2
• X2 pro 7
• X2 control 10
• X2 marine 12 SC
• X2 marine 15 HB SC
• X2 extreme 7 12V*
• X2 extreme 12 HP SC*
• X2 extreme 7 SL HP*
• X2 extreme 12 SL HP SC*
• X2 extreme 7 CO*
• X2 extreme 12 SL HP RO
NOTE
Not all combinations are available.
NOTE
* indicates variants including IECEx\ATEX and C1D2 accreditation.
Naming Convention
Beijer Electronics, MAEN333 9 2023-09

3. Installation
3.1. Space Requirements
• Maximum installation plate thickness: 5 mm.
The following drawings show the space requirements in millimeters when installing the HMI panel.
The drawings are only illustrative and may be out of proportion.
100,00
100,00
50,00 50,00
100,00
3.2. Installation Process
The following is needed:
• A Phillips/slot screwdriver
Do the following:
1. Unpack and check the delivery. If damage is found, notify the supplier.
NOTE
Place the on a stable surface during installation. Dropping the HMI panel or
letting it fall may cause damage.
Installation
2023-09 10 Beijer Electronics, MAEN333
Other manuals for X2 base 15 v2 HP
1
Table of contents
Other Beijer Electronics Touch Terminal manuals

Beijer Electronics
Beijer Electronics X2 extreme 7 12V CO User manual

Beijer Electronics
Beijer Electronics CIMREX 5 User manual

Beijer Electronics
Beijer Electronics X2 control User manual

Beijer Electronics
Beijer Electronics X2 control 21 - B2 User manual

Beijer Electronics
Beijer Electronics X2 control User manual

Beijer Electronics
Beijer Electronics X2 pro 7 - B2 2eth User manual

Beijer Electronics
Beijer Electronics VICPAS EXTER Series Installation and user guide

Beijer Electronics
Beijer Electronics X2 pro 10 - B2 User manual

Beijer Electronics
Beijer Electronics X2 control 10 - B2 User manual

Beijer Electronics
Beijer Electronics QTERM-G70 User manual