–4–
M‑3311A Transformer Protection Relay
STANDARD PROTECTIVE FUNCTIONS (cont.)
Device Setpoint
Number Function Ranges Increment Accuracy†
Instantaneous Residual Overcurrent
1-8
Pickup 1.0 to 100.0 A 0.1 A 0.1 A or 3%
(0.2 to 20.0 A) (0.02 A or 3%)
Time Delay 1 to 8160 Cycles 1 Cycle 2 Cycles or 1%
Current Selection Sum1, Sum2, W1, W2, W3, W4
Inverse Time Phase Overcurrent
1-4
Pickup 0.50 to 12.00 A 0.01 A 0.1 A or 3%
(0.10 to 2.40 A) (0.02 A or 3%)
Current Selection Sum1, Sum2, W1, W2, W3, W4
Characteristic Curve Beco Definite Time/Inverse/Very Inverse/Extremely Inverse
IEC Inverse/Very Inverse/Extremely Inverse/Long Time Inverse
IEEE Moderately Inverse/Very Inverse/Extremely Inverse
Time Dial Setting 0.5 to 11.0 0.1 3 Cycles or 3%
0.05 to 1.10 (IEC curves) 0.01
0.5 to 15.0 (IEEE curves) 0.1
Two or three of the windings may be summed together.
Inverse Time Ground Overcurrent
51GW2/51GW3/51GW4
Pickup 0.50 to 12.00 A 0.01 A 0.1 A or 3%
(0.10 to 2.40 A) (0.02 A or 3%)
Characteristic Curve Beco Definite Time/Inverse/Very Inverse/Extremely Inverse
IEC Inverse/Very Inverse/Extremely Inverse/Long Time Inverse
IEEE Moderately Inverse/Very Inverse/Extremely Inverse
Time Dial Setting 0.5 to 11.0 0.1 3 Cycles or 3%
0.05 to 1.10 (IEC curves) 0.01
0.5 to 15.0 (IEEE curves) 0.1
Inverse Time Residual Overcurrent
1-4
Pickup 0.50 to 6.00 A 0.01 A 0.1 A or 3%
(0.10 to 1.20 A) (0.02 A or 3%)
Characteristic Curve Beco Definite Time/Inverse/Very Inverse/Extremely Inverse
IEC Inverse/Very Inverse/Extremely Inverse/Long Time Inverse
IEEE Moderately Inverse/Very Inverse/Extremely Inverse
Time Dial Setting 0.5 to 11.0 0.1 3 Cycles or 5%
0.05 to 1.10 (IEC curves) 0.01
0.5 to 15.0 (IEEE curves) 0.1
Current Selection Sum1, Sum2, W1, W2, W3, W4
†Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
50N
51
51G
51N