- Numerical
Over Current / Earth Fault
Protection Relay
Type : ADR141C / 241C

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 2/86
User Notice
Ashida Electronics (P) Ltd. Reserve all right to make improvements in the
products described in this manual at any time and without notice. All rights are
reserved. No part of this manual may be reproduce, copied, translated or
transmitted in any form or by any means without the prior written permission of
Ashida Electronics (p.) Ltd. Information in this manual is intended to be accurate
and reliable. However Ashida assumes no responsibility for its use; nor for any
infringements of rights of third parties, which may result from its use.

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 3/86
CONTENTS
1. Description 6
2. Protection Feature 7
3. Relay Design Feature 7
4. Main Function 7
4.1 Over current and EF Element 7
4.2 Inverse Time curve 8
4.3 Trip circuit supervision 10
4.4 Breaker failure detection 10
4.5 Cold Load Setting 11
5. Construction Detail 11
6. Self Check Feature 11
7. Technical Details 12
7.1 Technical Specification 12
7.2 Type Test Detail 14
7.3 Cabinet Drawing 16
7.4 Block Diagram 17
8 Front Panel and Control 18
8.1 User’s Interface 19
8.1.1 LCD Display 19
8.1.2 Touch Keys 19
8.1.3 LED’s 20
8.2 Password 20
8.2.1 Password Entry & Changing the Password 20
8.2.2 Clear Password 22
8.3 Menus 23
8.3.1 Default Display 23
8.3.2 Main Menu List 23
8.3.2.1 Main Menu List Details 24
8.3.3 Primary Current 27
8.3.3.1 To View – Primary Current 27
8.3.4 General Setting 28
8.3.4.1 To Set – General Setting 28
8.3.4.2 To View – General Setting 31

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 4/86
8.3.5 Relay Setting 32
8.3.5.1 To Set – Relay Setting 32
8.3.5.2 To View – Relay Setting 35
8.3.6 Cold Load Settings 36
8.3.6.1 To Set – Cold Load Setting 36
8.3.6.2 To View – Cold Load Setting 40
8.3.7 Relay/LED Configuration 41
8.3.7.1 Bit Definition for Relay/LED Configuration 41
8.3.7.2 To Set – Relay/LED Configuration 44
8.3.7.3 To View – Relay/LED Configuration 49
8.3.8 Trip Test 51
8.3.8.1 To View – Trip Test 51
8.3.9 Fault 1 52
8.3.9.1 To View – Fault 1 Data [Fault 2 to Fault 8] 52
8.3.10 Events Log 53
8.3.10.1 To View – Error Log 53
8.3.11 Error Log 53
8.3.11.1 To View – Error Log 53
8.3.12 Status 54
8.3.12.1 To View – Status 54
8.3.13 Date Time Setting 55
8.3.13.1 To Set – Date Time setting 55
8.3.13.2 To View – Date Time Setting 56
8.3.14 Secondary Current 57
8.3.14.1 To View – Secondary Current 57
9.0 Flow Chart 58
9.1 Flow Chart – To View Primary Current 58
9.2 Flow Chart – To Set / View General Settings 59
9.3 Flow Chart – To Set / View Relay Settings 60
9.4 Flow Chart – To Set / View Cold Load Settings 61
9.5 Flow Chart – To Set / View Relay/LEDs Settings 62
9.6 Flow Chart – To View Trip Test Settings 63
9.7 Flow Chart – To View Fault 1 (Fault 2 – Fault 8) 64
9.8 Flow Chart – To View Events Log Settings 64

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 5/86
9.9 Flow Chart – To View Error Log Settings 65
9.10 Flow Chart – To View Status Settings 65
9.11 Flow Chart – To Set / View Date/Time Settings 66
9.12 Flow Chart – To View Secondary Current 67
10 Communication –Only for ADR241C Relay 68
10.1 General 68
10.2 General Questions 69
10.3 Physical connection and link layer 70
10.4 Relay Talk System for downloading the data 71
10.5 ADR241C IED Main Screen 75
10.5.1 Parameter Display 76
10.5.2 IEDs Din Display 76
10.5.3 Control Operation 77
10.5.4 Private Setting 77
10.6 History Fault 78
10.7 Setting 79
10.7.1 General Setting 79
10.7.2 Bank Settings 80
10.8 Event List 81
11.0 Test Report Annexure – 1 83
11.1 Drawing for Test Setup. 85
12.0 Revision Note 86

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 6/86
1. Description:
•ADR141C / ADR241C are second generation Numerical 3OC + 1EF Over Current
Relay. [The ADR241C is communicable Relay having RS485 Port. All the other
features as per ADR141C Relay] It consist all the necessary protection and monitoring
functions required for Normal feeder. It consists of High Speed Digital DSP Controller.
•Analog Measuring Module.
•Power supply Module.
•Digital Input output module.
The High speed Digital Signal Controller continuously monitors phase, E/F current along with
different optical isolated status connections. The high-speed micro-controller samples these
current signals through a A/D converter. The Digital Signal performs powerful Numerical
Algorithms to find out RMS of fundamental & harmonic contents of the current then this
value is used for protection and metering function. All measurement is tuned to fundamental
frequency i.e. 50Hz, thus relay remain stable during distorted waveform generated
electronics loco-motive. All these measure values are then used for different protection
function such as IDMT/DMT Over current protection, Instantaneous Over current protection,
Earth Fault protection, etc. These measured values are also displayed on large 16 x 2 LCD
display for metering purpose. The DSC also monitors different digital input through optical
isolator and perform some monitoring function such trip circuit supervision, and control
potential free contact for control CB and generate ALARM and Tele-signalling.
The power supply module is basically DC – DC converted designed using modern PWM
based Switching mode technique to convert station battery supply to the 12V and 24Vdc low
voltage supply for relay electronics and control circuit. It also provides necessary isolation
from station battery. The power supply module is design using very advance PWM controller
which allow very wide input supply variation i.e 18V to 250VAC/DC covering 24Vdc, 30Vdc,
and 110Vdc and 220Vdc station battery requirement.
The relay is having total 4 nos of high intensity dual LED for easy identification of type of fault
for easy user interface. All LEDs and control output RL2 to RL4 are fully programmable via
keypad interface

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 7/86
2. Protection Features:
94 Element (3 Phase + EF) Non Directional Over current IDMT/DMT.
9Selection of Curve: Five selectable curve (Normal Inverse1 (C1), Normal Inverse2, (C2)
Very inverse (C3), Extremely inverse (C4), Long time inverse (C5)) and Define Time (C6)
9Instantaneous Over-Current Protection with adjustable timer.
9Breaker Failure detection.
9In-built CB Trip Circuit Supervision function during pre closing and post closing of CB.
9On site CT Secondary selection 1A or 5A.
9Internal calculation of zero seq. current (3Io) for Earth fault.
9Wide range Power supply input 18V to 250V AC/DC.
9Cold Load Pickup.
9RS485 communication Port with IEC 60870-5-103 protocol. [Only in ADR241C]
3. Relay Design Features:
916 x 2 LCD Backlit display for Parameter and setting display.
9Online display of CB status and other digital and logical status.
9Continuous monitoring of module’s internal hardware and alarm generation in case of
failure of any critical components.
94 Digital Output contacts for local alarm as Trip.
92 dedicated status input for Trip Circuit Monitoring.
98 nos of Fault data stored with keypad interface and time stamping.
916 Nos. of Event Log provided.
4. Main Functions:
The ADR141C are having following protection functions.
1. Non Directional phase Over current element. (Ip>, and Ip>> )
2. Non Directional 3Io (Internally derived EF) (3Io> and 3Io>>).
3. Trip Circuit Super vision.
4. Breaker Failure Detection.
5. Monitoring Functions.
Each of these functions are independently programmable and can be enable or disable by
user depending upon requirement.
4.1 Over Current & EF Element:
The ADR141C is member of Ashida Numerical Relay family design for protection general
feeder. The relay has one stage of IDMT/DMT setting and one stage of instantaneous setting.
(Ip>, IP>>, 3Io>, 3Io>>). All major international IDMT curves are available. Range for first
stage is 10% to 250% and 50% to 3000% for instantaneous stage for phase and 3Io.
Although the curves tend towards infinite when the current approaches Is (general threshold),

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 8/86
the minimum guaranteed value of the operating current for all the curves with the inverse time
characteristic is 1.1Is (with a tolerance of ± 0.05Is).
4.2 Inverse Time Curves :-
The each stage thresholds for phase (earth) over current can be selected with an Inverse
Definite Minimum Time (IDMT) characteristic. The time delay is calculated with a
mathematical formula
where
t = operation time
a = constant
I = Input current
Iref = Current threshold setting
b = Constant
K = Time multiplier setting or Time dial Setting
Curve Type Description a b
C1 Standard Inverse_1 0.14 0.02
C2 Standard Inverse_2 0.06 0.02
C3 Very Inverse 13.5 1
C4 Extremely inverse 80 2
C5 Long Time Inverse 120 1
C6 Define Time Inst 99.9 Sec
K * a
I b
Iref
[ ] - 1
t =

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 9/86

NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 10/86
4.3 Trip circuit Supervision:-
The ADR141C is having 2 separate digital opto-coupler status input which can be used to
continuously monitor continuity of trip-circuit. The general scheme is as shown in fig. 4.
Relay monitor Trip coil continuity through CB NO during close condition and through CB NC
during Trip condition. If any discontinuity observed it generate Alarm signal.
The output can be assigned to any of 4 relay RL1 to RL4, The Trip circuit supervision logic
set reset PROTH (Protection healthy) bit, it normally ON and become OFF at following
condition
9When DC supply is not sufficient (DC fail)
9When CB NO and CB NC both active or both inactive. CB NO as well as CB NC are both
close or open.
9Relay detects any internal hard ware Error.
B+
B-
TC
CB NO
CB NC
To Relay CPU
To Relay CPU
TCCOM
B+
B-
TC
CB NO
CB NC
Trip Circuit Logic
-
CB NO
-
1
2
1
2
6
6
B+
B-
TC
CB NO
CB NC
To Relay CPU
To Relay CPU
TCCOM
B+
B-
TC
CB NO
CB NC
Trip Circuit Logic
-
CB NO
-
1
2
1
2
6
6
4.4 Breaker Failure Detection:-
Normally after tripping current should become Zero within 100 – 200ms time depend upon
type of fault and breaker mechanism. After Fault ADR141C trigger internal timer (settable
from 50ms to 800ms) if fault is not cleared during this time then relay declare as Breaker fail
(LBB function) and set BF bit. This bit can be assigned to any of the output relay.
Breaker Fail Logic
OPERATION
BF
&&
DELAY
50ms to 800ms
TRIP
GENERAL
BF ENABLE
Breaker Fail Logic
OPERATION
BF
&&
DELAY
50ms to 800ms
TRIP
GENERAL
BF ENABLE