1.0 INTRODUCTION
The Model 360 has been designed to detect Carbon Dioxide in Air and to signal an alarm
event above the level defined on the calibration certificate (normally 0.5% by volume in Air).
The Model 360 utilizes a highly sensitive solid electrolyte sensor which is operated and
monitored by microprocessor. The unit is constructed from high quality electronic
components which ensure trouble free operation during its expected life time.
2.0 APPLICATIONS
The detector has been designed to protect people from the risk of C02 build up. This
can be caused by leaks from cylinders, supply lines, industrial, vehicle emissions and
biological sources.
Beer cellars are generally classed as a confined space and therefore covered by the
Confined Spaces Regulations 1997. This means that an employer or manager is
responsible for the health and safely of their employees and must take into account
the risk of:
the loss of consciousness or asphyxiation of any person at work arising from gas,
fumes,vapour or the lack of oxygen.
This is a legal requirement.
3.0 SITING THE DETECTOR
First site the detector, Carbon Dioxide is a constituent of Air, however in
isolation is heavier than air (by a factor of 1.5). therefore the unit should be
sited not more than 4 metres from the potential leak source and 0.5 metres
from ground level.
Site the unit where it can be easily seen and heard.
PANTHERGASDIRECT LTD, PO BOX 2507. CLARENCE PLACE,READING RG1 5XF

4.0 INSTALLATION
The detector should be wall mounted by first fixing the mounting bracket to the wall with the
screws and rawl plugs provided.
The unit is fixed to the bracket by locating the holes in the back of the case onto the lugs
ofthe bracket and sliding downwards to secure.
We recommend that the power cable supplied with the detector is fitted to an un-switched
3amp fused spur.
WIRING:
240V circuit. LNE: Brown
NEUTRAL: Blue
SWITCHING CIRCUIT: Black/Grey
5.0 THE DETECTOR OPERATION
When the unit is first powered up the green LED will flash for up to two hours, while the unit
is stabilising.
Once the green LED has stopped flashing and is constantly lit, the detector is operational.
The detector will alarm as the level of Carbon Dioxide rises above the alarm set point
(calibrated at the factory).
The red LED will light, the internal sounder will operate and the alarm relay will change
state(if fitted).
If a repeater unit is supplied it will start to flash and the sounder will operate while the detec-
tor is in an alarm condition and resets with the detector.
In gas-free conditions the detector can be set to auto reset or push button. Once reset the
red LED will extinguish, the sounder will stop operating the relay and repeater(if fitted) will
change back to their original state.
Note: The detector will not reset when in alarm condition.
6.0 SPECIFICATION -Model 360
- Carbon Dioxide Detector
Power Supply Mains driven or DC
AC version: 230V or 11OVDC version: 12V or 24V
Power 6 Watts quiescent
Alarm relay (volt free SPCO) IOAmp 250V ac 10 Amp 30V dc
Sensor Solid electrolyte controlled by microprocessor -( expected life span 5 years)
Alarm level Standard calibrated to alarm above 0.5%
Volume- (if a different alarm level required please state when ordering)
Operating temperature: -10º C - + 40ºC
Sound level: -100 C to +400 85 decibels (dB) at 3m
Alarm indicators Unit stabilizing -Green LED flashingUnit operating correctly –Green LED
Light Unit in Alarm –Red LED
Dimensions (mm) 110 x 110 x 57
Detector 1 year warranty (expected life 10 years)
GUARANTEE
We guarantee your new gas detector for one year from the date of
purchase by the purchaser, to be free from defects in materials and workmanship under
normal use and service. We will, at our discretion, repair, replace or refund the price of
any part of the detector which is found to be defective in either materials or
workmanship under normal use and service during the guarantee period. We shall be
under no obligation to repair, replace or refunded the price of units which are found to
be defective in any way due to damage, neglect, unreasonable use or have been
dismantled.
PANTHERGASDIRECTLTD, PO BOX2507 , CLARENCE PLACE, READINGRG1 5XF
TEL 0118 960 4321 FAX: 0118 9604333 EMAIL:enquiries @panthergas.co.uk

PANTHERGAS DIRECT LTD, PO BOX 2507, CLARENCE PLACE, READING RG1 5XF
Table of contents