Technical Manual: ST-H2-AS (Changes are subject to DCRN)
Ref No: NISM/ST-H2-AS/02 Date: 03.02.20 Issue: 02
• sensortec • ST-H2-AS • analogue addressable heat sensor instruction manual
Section 4 - INSTALLATION
In normal use, the ST-H2-AS sensor will be installed at ceiling level.
Pass the field wiring through the cable hole in the centre and from
the rear of the base. Offer up and affix the base to the ceiling or
conduit fitting with screws via the base mounting holes. Connect
the field wiring to the base terminals, as detailed on page 8 making
sure the wiring does not obstruct fitting of the sensor head. Fit the
sensor head by inserting it into the base and turning clockwise until
the notch in the sensor’s rim aligns with base locking screw. The
OMNIVIEWTM 360°LED alarm indicator permits visibility from any
angle.
Note: The address must be set before the sensor is fitted into place.
Fit the plastic dust cover supplied over the sensor to keep out
dust etc, until the system is commissioned. If the dust cover is not
fitted and the environment is slightly dusty, such as when building
work is being completed, for example, problems of false alarms are
likely to occur after commissioning unless cleaning of the sensor is
undertaken. At commissioning, the dust cover should be removed and
discarded.
NOTE: THE PLASTIC DUST COVER MUST BE REMOVED FROM THE SENSOR
IN ORDER FOR THE SENSOR TO FUNCTION CORRECTLY.
Section 5 - MAINTENANCE AND
CLEANING
Maintenance
The ST-H2-AS sensor is a high quality product engineered for
reliability. If proper preventative maintenance is not carried out, there
is a likelihood of malfunction, including false alarms.
Servicing:
Servicing of the system should be carried out in accordance with the
requirements of BS5839 Part 1, Fire Detection and Alarm Systems
for Buildings: Code of Practice for System Design, Installation and
Servicing.
3