Pilz PDP20 F 4 mag User manual

PDP20 F 4 mag
Operating Manual-24737-EN-03
}Decentralised periphery

Preface
This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for internal purposes. Suggestions and comments for improving this documentation will be
gratefully received.
Source code from third-party manufacturers or open source software has been used for
some components. The relevant licence information is available on the Internet on the Pilz
homepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual PDP20 F 4 mag
24737-EN-03 3
Introduction 4
Validity of documentation 4
Using the documentation 4
Definition of symbols 4
Safety 5
Intended use 5
Safety regulations 5
Safety assessment 5
Use of qualified personnel 6
Warranty and liability 6
Disposal 6
For your safety 6
Unit features 7
Block diagram 7
Function description 7
Timing diagram 8
Installation 9
Wiring 9
Permitted sensors from Pilz 9
Preparing for operation 10
Operation 11
Status indicator 12
Fault indicator 12
Technical details 13
Safety characteristic data 15
Order reference 15
Product 15
Accessories 15
EC Declaration of Conformity 16

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 4
Introduction
Validity of documentation
This documentation is valid for the product PDP20 F 4 mag. It is valid until new documenta-
tion is published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 5
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The sensor interface PDP20F4mag enables up to 4 sensors to be connected in series.
Permitted sensors are sensors with a N/O / N/O combination and the Pilz sensors listed in
the section entitled "Permitted sensors from Pilz".
The sensor interface meets the requirements in accordance with:
}EN 60204-1
}EN 60947-5-3
}EN 62061: up to max. SIL CL 3
}EN ISO 13849-1: up to max. PL e
If multiple sensor interfaces PDP20F4mag are connected in series, 3 additional sensors
per sensor interface may be connected in series.
The following is deemed improper use in particular:
}Any component, technical or electrical modification to the product
}Use of the product outside the areas described in this manual
}Use of the product outside the technical details (see Technical details [ 13]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
Safety regulations
Safety assessment
Before using a unit it is necessary to perform a safety assessment in accordance with the
Machinery Directive.
Functional safety is guaranteed for the product as a single component. However, this does
not guarantee the functional safety of the overall plant/machine. In order to achieve the re-
quired safety level for the overall plant/machine, define the safety requirements for the
plant/machine and then define how these must be implemented from a technical and organ-
isational standpoint.

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 6
Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by competent persons.
A competent person is a qualified and knowledgeable person who, because of their train-
ing, experience and current professional activity, has the specialist knowledge required. To
be able to inspect, assess and operate devices, systems and machines, the person has to
be informed of the state of the art and the applicable national, European and international
laws, directives and standards.
It is the company’s responsibility only to employ personnel who
}Are familiar with the basic regulations concerning health and safety / accident preven-
tion,
}Have read and understood the information provided in this description under "Safety"
}Have a good knowledge of the generic and specialist standards applicable to the spe-
cific application.
Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended
}Damage can be attributed to not having followed the guidelines in the manual
}Operating personnel are not suitably qualified
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
Disposal
}In safety-related applications, please comply with the mission time TM in the safety-re-
lated characteristic data.
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
For your safety
The unit meets all the necessary conditions for safe operation. However, please note the
following:
}Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a
rated insulation voltage of at least 250 V.

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 7
Unit features
}Connection of 4 sensors with a N/O / N/O combination
}2 safety outputs
}1 signal output
}LED display for:
– State of the outputs
– State of the inputs
– Operational readiness
}Multiple PDP20F4mag may be connected in series
}Plug-in connection terminals:
Either spring-loaded terminal or screw terminal available as an accessory (see order
reference [ 15])
Block diagram
InputInput
A1 A2 I20 I21
Input
I30 I31I10 I11
=
Power
T0
Diag-
nostics
SI
T1 SO O0 O1
&
Input
I40 I41
A1 I30 T0 I31
I10 I11 I20 I21
PDP20 F 4 mag
X3
X1
O0 O1 T1 SI
A2 I40 I41 SO
X2
X4
773310
Power
O0/1
I10/11
I20/21
I30/31
I40/41
Function description
The inputs of the PDP20F4mag are AND-linked. The result of the logic AND operation is
expressed via safety outputs O0 and O1.
A signal output (SO) indicates the state of the sensors.
Safety outputs
}There is a high signal at safety outputs O0, O1 when all the input circuits I10 ... I41 are
closed.
}If at least one of the input circuits is open or a sensor is partially operated, the safety
outputs will switch to a low signal.

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 8
Signal Output
}There is a high signal at the signal output SO when the connected sensors are oper-
ated (N/O contact closed).
}If at least one of the sensors is not operated or is partially operated, the signal output
SO will switch to a low signal.
Detection of shorts across contacts
2 test pulse outputs T0 and T1 enable shorts across contacts to be detected at the inputs.
The two test pulse outputs are permanently assigned to the inputs. If the test pulses are
swapped or there is a short circuit at the inputs, the device switches off the safety outputs
safely (low signal) and registers an error.
Series connection
The safety outputs of a PDP20F4mag may be connected to the cascading inputs I40 - I41
on another PDP20 F 4 mag. 3 additional sensors may be AND-linked via this device. In the
event of a short across the contacts, the safety outputs will be switched off safely (low sig-
nal).
Input SI
The input SI is reserved for future functions and may not be used.
Timing diagram
POWER
t2
Unit 1
I10...I41
Unit 1
O0/O1
Unit 2
I40-I41
Unit 2
I10...I31
Unit 2
O0/O1
t2t3t2t3t3
t2t2
t1
t1t3
12
t1t2
t1
Legend
}: Single connection with Unit 1
}: Series connection of Unit 1 and Unit 2
}Power: Supply voltage
}Unit 1, I10 ... I41: Input circuits of Unit 1
}Unit 1, O0/O1: Safety outputs of Unit 1
}Unit 2, I40- I41: Cascading input of Unit 2
}Unit 2, I10 ... I31: Input circuits of Unit 2

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 9
}Unit 2, O0/O1: Safety outputs of Unit 2
}t1: Max. processing time for input when signal changes from "0" to "1"
}t2: Typ. switch-on delay
}t3: Max. processing time for semiconductor output when signal changes from "1" to "0"
Installation
}The unit should be installed in a control cabinet with a protection type of at least IP54.
}Use the notch on the rear of the unit to attach it to a DIN rail (35mm).
}When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle)
}Push the device upwards or downwards before lifting it from the DIN rail.
Wiring
Please note:
}Information given in the "Technical details [ 13]" must be followed.
}Calculation of the max. cable length lmax in the input circuit:
Rlmax
Rl / km
Imax =
Rlmax = max. overall cable resistance (see Technical details [ 13])
Rl/km = cable resistance/km
}Use copper wiring with a temperature stability of 75 °C.
}The power supply must comply with the regulations for extra low voltages with protect-
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.
}1 wire may be connected per terminal. Use a terminal block if you need multiple con-
nections per terminal.
}Ensure the wiring and EMC requirements of IEC 60204-1 are met.
Permitted sensors from Pilz
}PSENmag:
– PSEN1.1p-10, PSEN1.1p-20
– PSENma1.3-20M12, PSENma1.3a-20, PSENma1.3b-20, PSENma1.3b-23,
PSENma1.3n-20, PSENma1.3p-20
– PSENma1.4-51M12, PSENma1.4a-50, PSENma1.4a-51, PSENma1.4n-50,
PSENma1.4n-51, PSENma1.4p-50, PSENma1.4p-51
}PSENhinge
– PSENhs1.1p
– PSENhs1.2p
}PSENrope
– PSENrs1.0
– PSENrs2.0

PDP20 F 4 mag
Operating Manual PDP20 F 4 mag
24737-EN-03 10
}PITestop
– PITes Set1s-5, PITes Set1s-5c, PITes Set1s-5ns
– PITesc1, PITesc1c, PITesc2, PITesc2c
Preparing for operation
Single connection
X1: Terminal block
Grey area: Control cabinet
T0
PDP20 F 4 mag
T1
I10
I31
I30
I21
I20
I11
I41
I40
A1
A2
24 V
0 V
X1
T0
T0
T0
T0
T1
T1
T1
T1
F1
NOTICE
– The test pulses are permanently assigned to the inputs (T0 to I10,
I20, I30, I40 and T1 to I11, I21, I31, I41) and must be connected as
shown in the wiring diagram.
– Unused inputs must also be connected to the assigned test pulse.
Table of contents