NTI ENVIROMUX Series User manual

MAN426 Rev Date 10/04/2022
E-CO2-LC
Carbon Dioxide Sensor
Installation and Operation Manual
ENVIROMUX®Series

TRADEMARK
ENVIROMUX and the NTI logo are registered trademarks of Network Technologies Inc in the U.S. and other countries. All other
brand names and trademarks or registered trademarks are the property of their respective owners.
COPYRIGHT
Copyright © 2022 by Network Technologies Inc. All rights reserved. No part of this publication may be reproduced, stored in a
retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise,
without the prior written consent of Network Technologies Inc, 1275 Danner Drive, Aurora, Ohio 44202.
CHANGES
The material in this guide is for information only and is subject to change without notice. Network Technologies Inc reserves the
right to make changes in the product design without reservation and without notification to its users.

TABLE OF CONTENTS
Introduction......................................................................................................................................................................1
Materials..........................................................................................................................................................................1
Wiring ..............................................................................................................................................................................2
Technical Specifications..................................................................................................................................................3
Warranty Information.......................................................................................................................................................3

NTI ENVIROMUX Low Cost Carbon Dioxide Sensor
1
INTRODUCTION
E-CO2-LC carbon dioxide sensor adopts a new type of infrared verification technology for CO2concentration measurement, and
the response rapid and sensitive. This carbon dioxide sensor includes an ABS waterproof shell. It is a professional industrial CO2
sensor and supports 0-5VDC output. This is a wall-mounted CO2sensor that can be used in greenhouses, industrial waste gas
monitoring, farming monitoring, etc.
Features:
Measures CO2 in a range of 0 to 5,000 ppm.
oAccuracy: ±(3% of reading + 50ppm) at 77°F (25°C)
oSensing element: Single Beam Non-Dispersive Infrared (NDIR)
0 to 5 VDC output.
Includes 12V/1A power supply.
Current consumption: 60mA @ 12VDC.
Weatherproof enclosure.
oIP65-rated water and dust protection.
Operating temperature: 14 to 122°F (-10 to 50°C).
Operating relative humidity: 0 to 80% non-condensing RH.
Regulatory approvals: CE
Requires the E-S5VDC sensor converter to operate with E-2D/5D/16D.
oE-S5VDC maximum cable length: 1000 ft (305 m).
oE-S5VDC powered by E-2D/5D/16D.
MATERIALS
Materials supplied with this kit:
NTI ENVIROMUX E-CO2-LC Carbon Dioxide Sensor
110-240VAC, 50 or 60Hz-12VDC/1A AC Adapter With Country-specific line cord
Wall Mount Hardware
2- WC-UY2 Butt Splices
URL Slip with path to ENVIROMUX sensor manuals
Materials Not supplied but REQUIRED:
ENVIROMUX E-S5VDC 0-5VDC Sensor Converter (Sold separately)